User's Manual

39
Chapter 5 Installing the Network Element
3. Affix the iPasolink network element to the rack with four M6 screws and nuts. Figure below
shows the installation of the chassis to the rack.
Connecting the Grounding Cables
iPasolink network element is grounded through the 48 V power connector to the rack ground.
iPasolink network element is grounded through an external screw terminal to the building earth.
This option is also mandatory even if the network element is installed in a rack. The location of
the main earthing cable is connected to the screws on the rear side of the network element. For
additional safety, grounding facility is also provided as a part of the power cord.
NOTE: All the cables used for connectivity must be labeled according to the site engineering
practices.
Before grounding the network element, ensure that the following tools and meters are available:
Standard installer tool kit
Grounding cable
Philips screw driver (PH3, PH1)
Multimeter
Figure 10: Installing Chassis into the Rack