CFG_UPS_INPUT_LOST_DELAY
Specify the time in seconds the EM card waits until it determines that power to the UPSs
is interrupted. This prevents CPU blades from being shut down due to momentary power
interruption. If power to the UPSs is interrupted, then the system is powered by battery.
The default setting is "60" seconds.
CFG_UPS_COMMUNICATION_LOST_DELAY
Specify the time in seconds the EM card waits until it determines that a UPS is
unavailable after communication with the UPS by SNMP is lost. The default setting is
"180" seconds.
CFG_UPS_ONLINE_DELAY
Specify the time in seconds the EM card waits for connections of online UPSs at system
boot.
If the the number of online UPSs does not reach the specified value within this time, the
EM card calculates the maximum power consumption possible for the system assuming
that the remaining UPSs are not connected.
The default setting is "180" seconds.
Online UPS means one in a normal output state (online or manual bypass state).
CFG_UPS_TIMED_SLEEP_PERIOD
When CPU blades are shut down due to power interruption of UPS’s, all the UPSs can be
entered into the sleep state temporarily after completion of the shutdown.
Specify the sleep time in minutes. Set the time with multiples of 6 (from 6 to 60 minutes).
When the value is set to "0," only the battery-driven UPSs are entered into the sleep state.
The default setting is "0."
Generally, the default setting does not need to be changed.
CFG_UPS_GET_COMMUNITY_NAME
Specify the community name for SNMP Get request issued to UPSs. The default setting
is "public."
CFG_UPS_SET_COMMUNITY_NAME
Specify the community name for SNMP Set request issued to UPSs. The default setting is
"private."
CFG_UPSn_SERIAL_NUMBER, CFG_UPSn_CAPACITY
The serial numbers and power capacities [W] of up to four UPSs can be specified. The
default settings are blank characters and "0" [W]. Generally, you do not need to specify
these values.