User guide

107
or OPERATOR.
3. Run the following commands from a CLI to configure settings. For details, refer to
"Commands."
Configuring community name
To use the SNMP function, the write community setting is required. Read and trap
community settings are optional.
Configure community names (the default community name value for read, write, and
trap operations is "public").
SET SNMP COMMUNITY READ <the community name that allows a read
operation>
SET SNMP COMMUNITY WRITE <the community name that allows a write
operation>
SET SNMP COMMUNITY TRAP <the community name that allows a trap
operation>
― Configuring contact name (optional)
Configure a SNMP contact name.
Configure the contact address on SNMP (e.g., the address of the server room where the
rack is located).
SET SNMP CONTACT <the contact name>
Location information setting (required to display location information correctly on
NEC ESMPRO Manager)
Configure the location information of the blade enclosure.
Specify <the location in the rack of the blade enclosure> and <the
height of the rack> by unit (number).
SET SNMP LOCATION <the LOCATION name>
SET SNMP LOCATION ENCLOSURE <the location within rack of the
blade enclosure>
SET SNMP LOCATION RACKHEIGHT <the height of the rack>
― Specifying SNMP trap destination
When you use the SNMP function, it is required to set one or more IP address for trap
destination.
Specify SNMP trap destination.
You can specify up to three addresses.
ADD SNMP TRAPRECEIVER <the IP address to be notified trap>
― Enabling the TrapACK function (Optional)
Enable the TrapACK function (the function to wait Ack for SNMP trap).
ENABLE SNMP TRAPACK
Hint
Execute the SHOW NETWORK command to confirm that the SNMP function is
enabled (the SNMP function is enabled by default). If disabled, execute the ENABLE
SNMP command to enable the SNMP function. For information on the commands,
refer to "Commands."
4. Execute the command below on the CLI to check that the settings you made have taken effect.