Installation Manual

How to Configure Complex Systems
Dual Fuel Systems
If there’s an O/B wire and one or more W wires connected to the Nest
thermostat (which indicates that the system uses a heat pump with an
additional heating source), Pro Setup will first ask if the heating system
is dual fuel or single fuel.
For single fuel, any wires inserted into the W1, W2/AUX, or Star (if W3
is chosen) connectors will be treated as auxiliary heat that will be
used simultaneously with the heat pump when needed.
Pro Setup will automatically configure the auxiliary heat wire for an
electric forced air system. The 3rd generation Nest Thermostat can only
support one wire for auxiliary heat; additional auxiliary heat wires are not
supported.
For dual fuel, any wires inserted into the W1, W2/AUX, or Star (if W3 is chosen) connectors will be treated as
alternate heat that will be used instead of the heat pump when needed. Use Pro Setup to indicate the source
(gas, electric, geothermal, etc) as well as the delivery mechanism (forced air, radiant, etc) for each of the W
wires connected. The Nest Thermostat supports two wires for alternate heat; additional alternate heat wires
are not supported.
Humidifiers and Dehumidifiers
The Nest Thermostat supports whole-home humidifiers and
dehumidifiers that connect to it with one or two low voltage wires. There
are multiple Pro Setup settings for the wire in the Star connector to
control a humidifier or dehumidifier. Whenever a humidifier/dehumidifier
is attached you’ll need to select whether or not the fan should activate.
Compatible wires have one of the following labels:
H, Hum, Hum1, H2, Hum2
D, DH, Dhum, Dehum, D2, DH2, Dhoom2, Dehum2
Regardless of whether your customer’s humidifier or dehumidifier has one wire or two, you will need to figure
out if it can be activated on its own or if it requires heating or cooling to be on at the same time. You’ll also
need to determine other settings, such as whether the fan is required during operation.
The Nest Thermostat’s Star terminal is a powered terminal. If you’re connecting a humidifier/dehumidifier that
requires unpowered terminals, add a 24 VAC relay suitable for HVAC equipment use. Consult humidifier/
dehumidifier installation manual for wiring requirements.
Important Note: In dual transformer installations (installations with both Rc and Rh wires) it's important to note
that different wires attached to the thermostat will use different power sources. The Rc wire will provide power
to the Y1, Y2, G, and O/B terminals. The Rc wire will also charge the thermostat using the C terminal. The Rh
wire will provide power to W1, W2/AUX, and Star connectors. Never connect wires from dual transformer
systems to connectors from the opposite transformer.