Installation Manual

Wiring error quick reference guide
If the Nest Thermostat senses a problem with the wiring, you’ll receive an “E” error. These errors must be fixed
before setup can continue. “N” errors are not as critical and setup will continue but certain features may not
work. “W” errors indicate there is an issue with the Wi-Fi connection.
“E” errors related to wires not being detected can be the result of a wire not being fully inserted into the
connector or terminal. Ensure all wires are fully inserted and the connector buttons are in the down position
before performing additional troubleshooting.
Error #
Description:
What’s going on?
E155
No heating or cooling detected. W1 or
Y1 wire is required
The Nest thermostat isn't physically detecting a W1 (heating) or Y1 (cooling)
wire. One of these wires is required for any type of system that the Nest
thermostat supports.
E157
Y1 wire not detected
The Nest thermostat isn't physically detecting a Y1 wire or one isn't
attached. A wire in your */OB terminal is configured as a Heat Pump
O/B wire. Heat Pumps require a Y1 wire to function.
E158
Y1 wire not detected
The Nest thermostat isn't physically detecting a W1 wire or one isn't
attached. A wire in the */OB terminal is configured as a second stage
of heat. Your Nest thermostat needs a first stage of heat (W1) to use a
second stage of heat.
E159
No power to C wire detected
The Nest thermostat is physically detecting a wire in the C (common)
connector but isn't detecting any power to it.
E160
No power to Y1 wire detected
The Nest thermostat is physically detecting a wire in the Y1 (cooling)
connector but isn't detecting any power to it.
E162
No power to W1 wire detected
The Nest thermostat is physically detecting a wire in the W1 (heating)
connector but isn't detecting any power to it.
E164
Dual fuel requires an alternate heat
wire
The Nest thermostat was previously set up as a dual fuel system, but
it's not detecting a W1. One of these wires is required in order to have
alternate heat.
E169
Y2 wire without Y1 wire
The Nest thermostat is detecting a Y2 wire but not a Y1 wire. Both
wires are required for 2 stage conventional cooling systems.
E182
E183
E184
E188
The Nest thermostat has an
overcurrent error
The Nest thermostat may be wired incorrectly, or the system may be
incompatible. If using a C wire, ensure it is connected to the
Thermostat’s C terminal.
E194
R wire not detected
The Nest thermostat isn't physically detecting the R wire or one isn't
attached. An R wire must be connected for your Nest thermostat to
work.
E195
No power to R wire detected
The Nest thermostat physically detects the R wire, but doesn't detect
any power. If you've just installed the Nest thermostat, check to make
sure you turned the breaker back on after installation.
21