User Manual

43
Telnet protocol does not contain energy measurement data and counters. This protocol is
recommended to Outputs control only.
When the Telnet is enabled, other M2M protocols are disabled except SNMP. After clicking Save
changes, the notification message about the deactivation of the other protocol appears.
Start Telnet connection to a NETIO device IP address and its Telnet port
When the connection is established, the NETIO device returns the following response and is ready to
receive commands.
Telnet welcome message
100 HELLO 489F6C4F - KSHELL V2.1
Note: The Telnet connection is automatically terminated after 60 seconds of inactivity. It is possible
to use the noop command to keep the connection alive for the next 60 seconds.
Command set
Command
Description
login <username>
<password>
Log in a user.
Replace <username> and <password> by the
equvalent attributes defined in the Telnet
protocol configuration (Figure 28)
<password>
Example log in with username netio and
password netio:
login netio netio
quit
Log out and terminate Telnet connection.
noop
Keep the Telnet connection alive for the next
60 seconds.
No-operation
port list [xxxx]
Control/monitor of all outputs based on the
parameters xxxx (described below) for each
output. All parameters x must have valid value
otherwise the command will not be accepted
(e.g. port list 10x1 is invalid). If no parameters
are provided, then it returns states of all
outputs.