User Manual

6
3 Specifications
Power
100-240 V; 50/60 Hz; 10 A, IEC-320 C14 input PowerPDU 4PS
100-240 V; 50/60 Hz; 16 A, IEC-320 C20 input PowerPDU 8QS
Switched outputs
10 A in total / 10 A each output, 4x IEC-320 C13 PowerPDU 4PS
16 A in total / 10 A each output, 8x IEC-320 C13 PowerPDU 8QS
Maximum line breaker
capacity
C16A PowerPDU 4PS
C16A PowerPDU 8QS
Fuse
Integrated, non-resettable
Surge protection
Type 3 (CAT III)
Power Output relays
Micro-disconnection (µ) (resistive load), SPST-NO
1E5 switching cycles, max. 1.5 kV pulse voltage
Switch heat and fire resistance class 1
Electrical load
PowerPDU 4PS / PowerPDU 8QS: ZVS (Zero Voltage Switching)
- most load types, such as switching power supplies compatible
Digital Input (DI)
PowerPDU 8QS only:
1x Dry contact input (DI)
Aux. DC power 12V/0,05A max (+12V, GND)
Network interfaces
1x Ethernet RJ-45 10/100 Mbit/s
Attention! Device connected over LAN must be connected in
network with same earth potential (PE).
Internal consumption
Max. 2W PowerPDU 4PS
Max. 3W PowerPDU 8QS
Environment
IP30, protection rating = class 1
Operating temperature -20°C to 65°C / 10A
-20°C to 50°C / 16A
Device rated for pollution degree 2.
Designed for continuous operation in altitudes up to 2000 m.
Does not require additional cooling