3.1 Features
ZVS (Zero Voltage Switching)
ZVS (Zero Voltage Switching) means switching the 110/230VAC output when
the immediate voltage is zero.
ZVS is a good solution for switching on/off devices such as switching power
supplies.
ZVS is not suitable for controlling inductive loads (transformers or motors), as
it increases the probability of relay damage when such types of loads are
frequently switched on/off.
NETIO products without energy metering support ZVS (Zero Voltage Switching) when switching
110/230V relay outputs.
ZVS is sufficient relay switching technology for most load types, such as switching power supplies in
IT solutions.
IOC (Independent Output Control)
Independent Output Control function of the NETIO device uses an independent
system that ensures a stable operation of the output even if the main system
is being restarted, updated, or is booting.
Thanks to IOC, the controlled output can power devices that, for technical
reasons, must be powered without interruption (such as servers). The output
control is completely independent from the WiFi or LAN communication
subsystem.
PowerUp State
The PowerUp State parameter (sometimes also called Cold start) defines the
behavior of the 110/230V power output during the first milliseconds to seconds
after powering up the device, before the LAN/WiFi communication with a
master system is established.
For some applications, it is important to set the correct state of a power
output immediately after power is turned on (or restored). With servers in
particular it is important to avoid undesired momentary switching.
Possible settings for NETIO device
- On
- Off
- LAST state restores the last state before the power was disconnected
IOC
Independent IO
PowerUp
state
ZVS
Zero Voltage