User Guide

Neutra-Safe
®
Vertical/Horizontal Condensate Neutralizer
CN2-220V
Installation, Operation and Maintenance Manual
Neutrasafe Corporation
neutrasafe.com
421 Page Street, Suite 1
Stoughton, MA 02072
WARNING
• Neutra-Safecondensateneutralizersshouldonlybeinstalledbyaqualiedprofessional.
• Readallinstructionsbeforeinstalling.Performstepsintheordergiven.Failuretocomplycouldresultinsubstantialpropertydamage,
severepersonalinjury,ordeath.
• Donotallowuegasestoventthroughcondensateneutralizer.Allcondensatedrainlinesmusthaveagastrapbeforeenteringthe
neutralizationunit.Failuretocomplycouldresultinsubstantialpropertydamage,severepersonalinjuryordeath.
• Neutra-Safeneutralizersshouldonlybeconnectedtoacondensateoutletthatisinstalledpertheappliancemanufacturer’sinstructions.
Failuretocomplycouldresultinsubstantialpropertydamage,severepersonalinjuryordeath.
IMPORTANT
• Allpipingshouldbeinaccordancewithrelevantbuildingandmechanicalcodes,aswellasanylocal,stateorfederalregulations.
• Donotconnectmorethanoneappliancetoeachneutralizer.
• Neutralizershouldbeinstalledbelowalltrapsandcondensateoutlets.
• Donotusepipedopeonthreadedttings—useonlyTeontape.Neutra-SafeModelCN2-220Vmaybeinstalledintheverticalor
horizontalposition.Refer to page 2 for installation diagrams.
• Itisrecommendedthattheneutralizerbeinstalledbeforethecondensatepump.
• Allcondensatetrapsshouldbeprimedbeforecommencingoperationoftheappliance.
• Neutra-SafecondensateneutralizermediashouldbereplacedatleastannuallyorwhenpHfallsbelowlocalregulations.
MOUNTING OPTIONS
• ItisrecommendedthatNeutra-Safecondensateneutralizersbeinstalledascloseaspossibletotheoutletofthegastrap.
Refer to page 2 for installation diagrams.
• Usebracketsprovidedformountingneutralizer.
CN2-220V 220,000 Btu/h
Inlet
2
3
/8˝
1
3
/8˝
1
/2˝
2
3
/4˝
14
3
/4˝
Outlet 1
3
/8˝
1
/2˝
All dimensions ±
1
/8
LIMITED WARRANTY
• AllNeutra-SafeproductsarewarrantedagainstdefectsinmaterialsandworkmanshipforONE YEAR.
ThewarrantydoesNOTcoverissuesthatresultfrommisuse,improperinstallation,and/orfailuretoreplacethemedia.

Summary of content (2 pages)