User Guide

Neutra-Safe
®
Condensate Neutralizer
Model CN6T
Installation, Operation and Maintenance Manual
Neutrasafe Corporation
neutrasafe.com
421 Page Street, Suite 1
Stoughton, MA 02072
WARNING
• Neutra-Safe
®
condensate neutralizers should only be installed by a qualified professional.
Read all instructions before installing. Perform steps in the order given. Failure to comply could
result in substantial property damage, severe personal injury, or death.
Do not allow flue gases to vent through condensate neutralizer. Vent in cap is designed to allow proper flow through
neutralizer. All condensate drain lines must have a gas trap before entering the neutralizer. Failure to comply could
result in substantial property damage, severe personal injury or death.
Neutra-Safe neutralizers should only be connected to a condensate outlet that is installed per the appliance manufacturer’s
instructions. Failure to comply could result in substantial property damage, severe personal injury, or death.
IMPORTANT
All piping should be in accordance with relevant building and mechanical codes, as well as any local,
state or federal regulations.
Neutralizer should be installed below all traps and condensate outlets.
It is recommended that the installer maintain a pitch of ¼” per foot between the condensate neutralizer outlet
and the pump or drain.
Do not use pipe dope on threaded fittings—use only Teflon tape.
Neutra-Safe condensate neutralizers may NOT be installed in the vertical position.
It is recommended that the neutralizer be installed before the condensate pump.
All condensate traps should be primed before commencing operation of the appliance.
Neutra-Safe condensate neutralizer media should be replaced at least once a year or when pH falls below local regulations.