User Guide
MOUNTING OPTIONS
• It is recommended that Neutra-Safe condensate neutralizers be installed as close as possible to the outlet
of the condensate trap.
• Condensate neutralizer may be installed on level ground or mounting brackets (not provided).
Model CN6T has screw inserts in its base which can be used if needed.
• Neutra-Safe condensate neutralizers may be installed on or above the floor so long as a pitch of ¼” per foot
is maintained between the neutralizer outlet and the drain or pump.
• It is recommended that unions be installed to facilitate maintenance of the condensate neutralizer
INSTALLATION
1. Neutra-Safe CN6T condensate neutralizers are provided with 1” tappings at either end to accommodate fittings of choice.
2. If using PVC pipe, apply Teflon tape to the threads of PVC socket adaptors and attach to neutralizer. Do not over tighten.
3 Identify suitable location for assembled condensate neutralizer. Observe direction of flow as indicated on neutralizer.
4. PVC unions should be secured at either end of the neutralizer.
5. Prime and glue PVC pipe to fittings.
Note: If using flexible tubing, be sure to use hose clamps at barb fittings.
Note: PVC pipe is the preferred method for piping condensate drain lines.
6. Route PVC pipe or tubing to drain or pump, maintaining a pitch of ¼” per foot.
7. Fill condensate trap with water until flow is established through neutralizer.
8. Observe neutralizer during boiler operation to ensure unrestricted condensate flow.
MAINTENANCE
1. All service items should be undertaken by a qualified professional.
2. Visually inspect unit for signs of leaking or damage.
3. Neutralizer media should be replaced at least once a year or when pH falls below local regulations.
Neutralizer efficiency can only be determined by measuring pH level of condensate outflow.
4. Refer to chart below for appropriate refill kit.
Neutra-Safe
®
Replacement Media Kit
Model # Recharge Kit
CN6T 6TKRCK
5. Disconnect condensate line from both the inlet and the outlet of the neutralizer.
6. Unscrew cap and remove spent neutralizer media. Rinse empty neutralizer with water.
7. Add replacement media and replace cap.
8. Reattach neutralizer to condensate line and prime flue gas trap with a minimum of 1 gallon of water.
9. Observe neutralizer during boiler operation to ensure unrestricted condensate flow.