User Manual

1.
A
40 mm
B
1.
Slide the boot (1.) and the chuck (2.) onto the cable.
To ease the boot assembly apply some cable pulling
lubricant to the cable ends.
1. Prepare the cable as shown and strip the jacket at a
length of 40 mm.
2. A. S / FTP
Cut off braided shield to approx 10 mm and fold the
shield backwards.
B. U / FTP
Remove the foil of the paired wires and bend back
the drain wire for easier handling during assembly.
Drain wire to be used for grounding.
C. SF / UTP
Cut off braided shield to approx 10 mm and fold the
shield backwards. Cut and remove the foil screen.
3. Remove the pair screening (if existing) to max. 6 mm.
4. Presort, untwist and straighten the wires as shown.
Unstraightened wires could potentially harm the IDC.
C
Insert the wires into the designated position of the wire
management as per below wiring scheme, either T568A
or T568B
ASSEMBLY INSTRUCTION
etherCON NE8MX6* - CAT6A Cable Connector
|
R
Page 1BDA 428
A
B
C
2.
10 mm
6 mm
3.
4.
7
8
2
1
A
2
1
8
7
Component
side!
A
B
S / FTP
U / FTP
10 mm
C
SF / UTP
7
8
2
1
A
B
Tools: HX-CAT6A or pliers wrenchl
Wire cutterl
l Cable pulling lubricant
Insulation Diameter: > 1.10 - 1.60 mm
Wire Size: AWG 24/1 - AWG 22/1 (solid)
AWG 24/7 - AWG 22/7 (stranded)
2.
1 2 8 7
3 6 4 5
Component
side!
Color code
RJ 45
PIN No.
Connection
W - G
G
W - O
BL
W - BL
O
W - BR
BR
W - O
O
W - G
BL
W - BL
G
W - BR
BR
T568A T568B
1
2
3
4
5
6
7
8