Install Instructions

38
109837-01 - 5/20
PVCG-C
Installation, Operating & Service Manual


1sec.
1sec.
1sec.
Figure 11.4: Typical Operating Mode Display (Boiler Temp Shown)
Table 11.3: Status Codes
Status # Description Meaning
1
Standby
No call for heat or DHW
OR
Call for heat present , but boiler is in thermal purge (See PP on page 40)
OR
Call for heat/DHW present but boiler temperature is above high limit (HL) setting.
2
Waiting for Pressure
Switch to open
Control is confirming that air pressure switch contacts are open before starting
fan.
3
Waiting for Pressure
Switch to close
Fan is on and control is waiting for air pressure switch contacts to close.
4
Prepurge
Pressure switch is closed and control is waiting 30s before starting trial for igni-
tion.
6
Spark Control is attempting to light pilot
7
Flame proving Control is verifying that the pilot flame is on and stable.
8
Running Main burner is on
10
Retry/Recycle Delay
Control was unable to establish pilot and is waiting 60 seconds before trying
again
OR
Proof of pilot was lost after pilot was established and control is waiting 60 sec-
onds before attempting to relight.
11
Pressure Switch failed to
open.
Control waited in Status #2 for 60 seconds and air pressure switch remained
closed. Boiler will remain in this state until the air pressure switch opens.
12
Pressure Switch failed to
close.
Control waited in Status #3 for 60 seconds and air pressure switch failed to close.
Boiler will remain in this state until the air pressure switch closes.
13
Soft Lockout
A fault is preventing the boiler from firing. Boiler will be allowed to fire after prob-
lem clears itself AND a forced delay period has passed.
14
Hard Lockout
A fault has occurred which requires manual intervention before the boiler will
again operate. This intervention can be in the form of interruption of the power
supply to the boiler or resetting the control in Adjustment mode.
15
Waiting for limit to close LWCO open, limit jumper plug missing, or flame rollout switch open
16
Flame Present out of
Sequence
A flame was detected when none should have been present.
17
Self test Boiler was just energized and control is running a self check.
Note: In operating mode, holding either the or button while viewing a given parameter will keep
the display on the actual reading. For example, pressing while reading boiler temperature as
shown in Figure 11.4 will keep the display on 180 for as long as the button is held. This makes it
easier to view readings “live” if they are changing rapidly.
11 Operation (continued)