Install Instructions

51
109837-01 - 5/20
PVCG-C
Installation, Operating & Service Manual
Table 13.1: Faults Without Error Code Present
Displayed
Codes Problem Possible Cause
StA 1
tt OFF
dh OFF
Burners and
Circulator Off
Thermostat/s not calling for heat
Loose connection in thermostat, zone valve end switch, or zone panel wiring.
Thermostat, zone valve, or zone panel miswired
Defective thermostat, zone valve, or zone panel
StA 1
tt On
Burners Off
Circulator On
Boiler Warm
Boiler off on high limit (normal operation)
Boiler off on thermal purge (normal operation - See Table 11.7)
tt On
Heating
Circulator Off
Heating Circulator is being forced off on DHW priority (normal operation if Pt=ON - see
Table 11.8).
See causes for “DHW Circulator off “ below
dh On
DHW
Circulator Off
Loose connection in circulator wiring
Defective circulator
Circulator is running, but system problem is preventing circulation
StA 15
Burners Off
and Fan is Off.
Limit or LWCO connected to auxilary limit connection is open.
Nothing is connected to auxilary limit connection and jumper plug is missing.
Flame roll-out switch (FRS) open due to blocked heat exchanger. Correct problem and
replace FRS with exact replacement (see parts list)
StA 6
No spark at
pilot
Loose connection in ignition cable or pilot ground
Damaged electrode porcelain or ignition wire insulation (replace pilot)
Pilot electrode or Ground strap damaged (replace pilot)
If you cannot hear spark at all, replace control
StA 6
Spark, but no
pilot flame
Low inlet gas pressure
Plugged, kinked, or leaking pilot tubing
Plugged pilot orifice
Gas line not purged of air
Defective pilot assembly
Defective gas valve (before replacing, confirm that there is 24VAC between PV and MV/
PV. If there is not, control harness is loose or the control itself is defective).
Loose connection in harness between control and gas valve.
StA 6
Pilot flame
present, but
spark does not
shut off
Low inlet gas pressure
Partially plugged, kinked, or leaking pilot tubing
Partially plugged pilot orifice
Loose connection in ignition cable or pilot ground
Damaged electrode porcelain or ignition wire insulation (replace pilot)
Pilot electrode or Ground strap damaged (replace pilot)
Defective Control
STA 8
Pilot flame
present, spark
off, but Main
Burner does
not light at all
Loose connection in harness between control and gas valve
Defective gas valve (before replacing, confirm that there is 24VAC between MV and MV/
PV. If there is not either there is a loose connection in the control harness or the control
itself is defective).
StA 10
Main burner
lights, but
shuts off
immediately
Low inlet gas pressure
Partially plugged, kinked, or leaking pilot tubing
Partially plugged pilot orifice
StA 10
or StA 13
No spark or
pilot
Pilot was either never established or proof of pilot was lost after it was lit. Cycle power to
the boiler and look for symptoms above.
13 Troubleshooting (continued)