Ordering Information
Example: ECL31UNVWHR2SD
Series Version Voltage Housing Color Letter Color Number of Faces Remote Capable Self Diagnostic
ECL3 1 (Version 1) UNV (120/277VAC) WH (White) G (Green) 2 (Single and Double) _ (Non-remote) SD
R (Red) R (Remote capable)
ECL3
Self Diagnostic LED Combo Exit Sign & Emergency Light
Product Description
The NICOR ECL3 Series provides self diagnostic testing and reporting in an Exit/Emergency combo.
This UL924 code compliant solution for exit and emergency requirements oers high output and
adjustable LED heads to deliver direct illumination for path of egress. The evenly illuminated exit
sign is available with red or green stencils. The ECL3 Series oers exible installation for surface
ceiling or wall mount options along with eld removable chevrons for universal conguration
based on your application’s directional needs. Supplied with two faces for single or double face
installation.
Construction
• Injection molded thermoplastic ABS housing
• UL-94 5VA Flame rating
• Test switch and charge/status indicator
• Adjustable heads for aiming light where required:
• Vertical head tilt: 330°
• Horizontal head rotation: 200°
Optical System
• Uniform lighting with specially designed plastic diuser to prevent shadowing
Electrical
• Operating temperature rating of 50°F to 104°F (10°C to 40°C)
• Remote version supports up to two (2) 3.6VDC NICOR remote lamps (see compatibility chart)
• 90 minute capacity (including remote lamps)
• Fully-illuminated 6” letter height with 3/4” stroke
• Self Diagnostic feature automatically tests and reports on xture status
LED
Light engine provides consistently bright and even EXIT legend illumination with red or green LEDs
Finish
• White textured thermoplastic housing
• Available with either red or green lettering
Installation
• Surface, ceiling or wall mount installation options
• Snap-in mounting bracket
• Universal mounting plate with EZ quick connect
• Universal knockout pattern provided on housing for surface mount install
• Field-installable, removable chevron directional indicators for all congurations
• Supplied with two faces for single or double face installation
Compliance
• UL 924
• Meets NFPA 70 and 101requirements
• Listed for damp locations
Warranty
• 1-year limited system warranty standard
• Warranty does not cover product failure due to an overvoltage event (power surge)
Specications and dimensions subject to change without notice
ECL3SD
200 lumen
LED Self Diagnostic Exit/Emergency Unit
Type
Catalog
Project
Date
ECL3SD NonRemote
Input Voltage (VAC)
120/277
System Level Power (W)
3.3
Delivered Lumens (Lm)
203
System Ecacy (Lm/W)
61.5
Correlated Color Temp (K)
6000
Color Rendering Index (CRI)
70
Photometric Data
Compatible NICOR Remote Lamps*
ERH3SD
ERH4SD
ERH3WPSD
ERH4WPSD
*Not a complete list. Check compatibility before installation.