Series Version Voltage Housing Color Letter Color Number of Faces Remote Capable Self Diagnostic
ECL3 1 (Version 1) UNV (120/277VAC) WH (White) G (Green) 2 (Single and Double) _ (Non-remote) SD
R (Red) R (Remote capable)
ECL3
Self Diagnostic LED Combo Exit Sign & Emergency Light
Product Description
The NICOR ECL3 Series provides self diagnostic testing and reporting in an Exit/Emergency combo.
This UL924 code compliant solution for exit and emergency requirements oers high output and
adjustable LED heads to deliver direct illumination for path of egress. The evenly illuminated exit
sign is available with red or green stencils. The ECL3 Series oers exible installation for surface
ceiling or wall mount options along with eld removable chevrons for universal conguration
based on your application’s directional needs. Supplied with two faces for single or double face
installation.
Construction
• Injection molded thermoplastic ABS housing
• UL-94 5VA Flame rating
• Test switch and charge/status indicator
• Adjustable heads for aiming light where required:
• Vertical head tilt: 330°
• Horizontal head rotation: 200°
Optical System
• Uniform lighting with specially designed plastic diuser to prevent shadowing
Electrical
• Operating temperature rating of 50°F to 104°F (10°C to 40°C)
• Remote version supports up to two (2) 3.6VDC NICOR remote lamps (see compatibility chart)
• 90 minute capacity (including remote lamps)
• Fully-illuminated 6” letter height with 3/4” stroke
• Self Diagnostic feature automatically tests and reports on xture status
LED
• Light engine provides consistently bright and even EXIT legend illumination with red or green LEDs
Finish
• White textured thermoplastic housing
• Available with either red or green lettering
Installation
• Surface, ceiling or wall mount installation options
• Snap-in mounting bracket
• Universal mounting plate with EZ quick connect
• Universal knockout pattern provided on housing for surface mount install
• Field-installable, removable chevron directional indicators for all congurations
• Supplied with two faces for single or double face installation
Compliance
• UL 924
• Meets NFPA 70 and 101requirements
• Listed for damp locations
Warranty
• 1-year limited system warranty standard
• Warranty does not cover product failure due to an overvoltage event (power surge)
Specications and dimensions subject to change without notice
ECL3SD
200 lumen
LED Self Diagnostic Exit/Emergency Unit
Type
Catalog
Project
Date
ECL3SD NonRemote
Input Voltage (VAC)
120/277
System Level Power (W)
3.3
Delivered Lumens (Lm)
203
System Ecacy (Lm/W)
61.5
Correlated Color Temp (K)
6000
Color Rendering Index (CRI)
70
Photometric Data
Compatible NICOR Remote Lamps*
ERH3SD
ERH4SD
ERH3WPSD
ERH4WPSD