Installation Guide

NICOR, Inc. 2200 Midtown Place NE, Albuquerque, NM 87107 P: 800.821.6283 F: 800.892.8393 www.nicorlighting.com July 26, 2021 10:46 AM
ECL3 Slim LED Combo Exit Sign & Emergency Light
INSTALLATION INSTRUCTIONS
Model: ECL310UNVWHG2SD, ECL310UNVWHG2RSD,
ECL310UNVWHR2SD, ECL310UNVWHR2RSD
GENERAL PRODUCT WARRANTY. Each NICOR product will be free from defect in materials and workmanship for a period of one (1) year from the date of delivery to the end-user. Powder Coat paint nish on products, other
than natural aluminum or brass, will not exhibit cracking, peeling, excessive fading, or corrosion during the warranty period. Exceptions apply as dened in each NICOR product’s specication sheets, which are incorporated
by reference herein. Warranty does not cover improper installation, operation, alterations, power surges, overheating due to external conditions, or acts of nature including but not limited to lightning strikes.
ALL NICOR WARRANTIES APPLY ONLY TO NICOR PRODUCTS THAT HAVE BEEN PURCHASED FROM AN AUTHORIZED NICOR DISTRIBUTOR; WHO PURCHASED THE PRODUCT DIRECTLY FROM NICOR; THE PRODUCT WAS NEW
AND IN AN UNOPENED NICOR PACKAGE AT THE TIME OF INSTALLATION; AND WAS INSTALLED BY A LICENSED ELECTRICIAN OR UNDER THE SUPERVISION OF A LICENSED ELECTRICIAN.
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, includ-
ing interference that may cause undesired operation.
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful
interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio
communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by
turning the equipment o and on, the user is encouraged to try to correct the interference by one or more of the following measures:
—Reorient or relocate the receiving antenna.
—Increase the separation between the equipment and receiver.
—Connect the equipment into an outlet on a circuit dierent from that to which the receiver is connected.
—Consult the dealer or an experienced radio/TV technician for help
NOTE
Battery Testing: Allow 24 hours of charging before testing.
Push In TEST Button - Fixture will switch to battery power and remain lit
Release TEST Button - Fixture will switch back to AC power
4
6
Operating status:
When AC power is supplied to the xture, the unit will automatically initiate a self-test and self-diagnostic test as
follows:
1. Veries battery disconnection, charger board failure, lamp failure and transformer failure every 5 seconds.
2. One minute self test every month
3. 30 minute self test on the 6th month of the year after installation
4. 90 minutes self test on the 12th month of the year after installation
Note: All functions are pre-set at the factory and do not require eld adjustment.
For manual test, press test button as follows:
5
Indicator light status: Indicator is a dual color LED that shows the following status:
Green
1. Solid On : Ready
2. Blinking : Testing
Red - Service Alert
One blink ON/pause every 4 seconds Battery is not connected
Two blinks ON/pause every 4 seconds Battery voltage drops below acceptable value
Three blinks ON/pause every 4 seconds Charger board fault
Four blinks ON/pause every 4 seconds Transformer function failure
Five blinks ON/pause every 4 seconds Emergency lamp fault
Six blinks ON/pause every 4 seconds Remote head lamp fault
Seven blinks ON/pause every 4 seconds LED strip fault (Exit Sign)
Press test button once 1 minute test
Press test button 2x (within 2 seconds) 5 minute test
Press test button 3x (within 2 seconds) 30 minute test
Press test button 4x (within 2 seconds) 90 minute test