iR2 Installation Manual Page 9 Software Revision1-0
- - -
Input / Output Terminals
External Fault Input (Terminal 1)
The Fault Input terminal permits a fault signal from external equipment to be indicated on the Noby-220i
ii
iR2
control panel. The LED indication is non-latching i.e. the LED follows the Ext. Fault Input status. The
polarity of the input is programmable. The factory setting is for a +12V signal to be applied to the terminal to
bring up a fault indication. Note that connecting external equipment also requires a ground reference
connection i.e. 0V from the external equipment must be connected to 0V on the Noby-220i
ii
iR2 (Terminal 4).
From normal standby User Mode enter the following key sequence:
Engineer Access Code-1 Select Toggle Fault Input Polarity Option
LEDs Off= +12V applied*
LEDs On= +12V removed
* Factory default setting
The green Power LED flashes rapidly upon successfully entering the Engineer Access Code-1.
The LEDs surrounding button indicate the current option status.
Toggle button to set/unset the desired option.
Press to accept OR press to quit without updating the option.
Fault Output (Terminal 2)
A 12V/20ma open-collector output signal. Normally high (12V), it falls to 0V upon detection of any fault
originating at the local panel only i.e. does not include the Ext. Fault Input, i
ii
interlink bus faults, or any fault
originating at a remote panel. Note that connecting external equipment also requires a ground reference
connection i.e. 0V on the Noby-220i
ii
iR2 (Terminal 4) must be connected to 0V on the external equipment.