User Manual

Noby-420 Installation & Programming Instructions Rev3 Page 8 of 12
Zone Faults
Zone Fault LED continuously illuminated
Disconnect the relevant zone and replace with the EOL resistor (4K7) at the zone terminal. If the fault can
now be cleared then there is a possible wiring error in the zone.
Check that the correct value EOL resistor is fitted at the end of the zone.
Check that the wiring and connections at each detector are consistent, and not crossed-over at any point
along the cable run.
Check that all manual call-points in the zone are intact and fitted with an appropriate series resistor, typically
470 ohms.
If a Zone Fault LED becomes continuously illuminated when a head is removed, then that detector base may
be the wrong type. Check that a schottky diode is fitted and correctly connected.
Replace the suspect detector base if necessary.
Zone Fault LEDs Flashing
One or more zones are isolated.
Zone Fault LED intermittently winking
A detector head is either missing or incorrectly connected.
Check all detector heads on the corresponding zone are fully seated in their bases.
Some (older) detectors may be incompatible with head-removal monitoring in which case it is recommended
to set the Head Removal Monitor Inhibit (System Options 2).
Fire is detected as Zone Fault
Check all detector heads on the corresponding zone are fully seated in their bases.
The panel monitors the zone for a short circuit. Some (older) detectors and call points may be incompatible
with short circuit monitoring in which case it is recommended to set the Zone S/C Inhibit (System Options 2).
Sounder Faults
Sounder Fault LED continuously illuminated
Enter the code [6][2][5][3][1][1] to bring up the sounder fault display, shown by the zone fault LEDs.
Check the corresponding sounder fuses F2 and/or F3.
Disconnect the suspect sounder circuit and fit a 4K7 EOL resistor at the sounder terminal. If the sounder
fault clears then there is a possible wiring fault in the circuit. Check all connections between sounders.
Check that the correct value 4K7 EOL resistor is fitted in the circuit.
Some types of sounders may be incompatible with the Noby-420 sounder circuit monitoring function in which
case it is recommended to set the Sounder Circuit Fault Monitor Inhibit (System Options 2).
CPU Fault Indication
CPU Fault LED Flashing
It is normal to see a CPU Fault at power-up, and can be cleared by performing a panel reset.
Persistent CPU faults may indicate interference from electrical machinery or RF transmitters in the immediate
locality.
Common Fault Indication
Common Fault LED Flashing persistently
Check that the Fault Input polarity is correctly programmed (Engineer Programming – Sysop1), and that the
Fault_Input terminal, if used, is in the required state to hold-off the Common Fault LED. Note that the
Fault_Input Polarity option should be disabled (factory default) if the Fault Input terminal is unused or not
connected to remote equipment.
Alarm Relay
Alarm relay not working
Check that the relay is not isolated.
User Keypad Operation
Reset command [3][6][3][6] [5] is ignored – nothing happens.
Both the external sounders and internal panel piezo sounder must first be muted before the reset button is
acknowledged. This can be performed in one operation by performing a Quick Reset [3][6][3][6] [1][4][5].