GB BU 0090 AS-Interface Bus modules Supplementary manual for NORDAC frequency inverters
NORDAC AS-Interface Manual Safety information N O R D A C Frequency Inverters Safety and operating instructions for drive power converters (as per: Low Voltage Directive 2006/95/EEC ) 1.General During operation, drive power converters may, depending on their protection class, have live, bare, moving or rotating parts or hot surfaces. Unauthorised removal of covers, improper use, incorrect installation or operation causes a risk of serious personal injury or material damage.
NORDAC AS-Interface Manual About this document Documentation Designation: BU 0090 GB Part No.: 607 09 02 Device series: AS Interface for SK 300E, SK 500E (entire series), SK 700E, SK 750E Version list Designation of previous issues Software Version Comments BU 0090 DE, February 2005 V 1.0 R0 First version, prototype BU 0090 DE, March 2006 V 1.1 R0 Inclusion of inverter series SK 5xxE and SK 750E BU 0090 DE, August 2007 V 1.1 R0 Address corrections, SK 5xxE, example 6.1.
NORDAC AS-Interface Manual Intended use of the frequency inverter Compliance with the operating instructions is necessary for fault-free operation and the acceptance of any warranty claims. These operating instructions must be read before working with the device! These operating instructions contain important information about servicing. They must therefore be kept close to the device. The AS interface module can only be used with the particular defined frequency inverter series.
Contents 1 INTRODUCTION .......................................................................................................................7 1.1 General information..............................................................................................7 1.2 The bus system ....................................................................................................7 1.3 AS interface for NORDAC frequency inverters ....................................................8 1.4 Delivery............
NORDAC AS-Interface Manual 5 DATA TRANSFER / PARAMETER-STRING TRANSFER ................................................... 42 5.1 Read ID string.................................................................................................... 43 5.2 Read diagnosis string ........................................................................................ 43 5.3 Read / Write parameter string ........................................................................... 44 5.3.1 Direct parameters ........
1 Introduction 1 Introduction 1.1 General information This AS Interface documentation is valid for the NORDAC SK 300E, SK 500E, SK 700E series and for SK 750E. NORDAC frequency inverters can be equipped with various modules for parameterisation or control. A slot is provided for this in the basic device. As delivered, there is a blank cover at this location, which must be replaced by the DeviceNet technology unit. 1.
NORDAC AS-Interface Manual 1.3 AS interface for NORDAC frequency inverters Features: • Electrically isolated bus interface • Status display with 2 LEDs (SK TU1-AS1 and SK TU3-AS1: 14 additional LEDs for I/O display) • SK TUx-AS1: Slave profile 7.4.0 with cyclic 4 Bit I/O data and the facility for string transfer • SK TUx-AS3: Slave profile 7.A.
1 Introduction 1.6 Certifications 1.6.1 European EMC Directive If NORDAC frequency inverters or their options are installed according to the recommendations in this instruction manual, it meets all EMC directive requirements, as per the EMC product standard for motor-operated systems EN 61800-3. 1.6.2 RoHS compliance The AS Interface bus options described here are designed to be RoHS compliant according to Directive 2002/95/EEC 1.
NORDAC AS-Interface Manual 2 Modules 2.1 NORDAC SK 500E By the use of various modules for display, control and parameterisation, the NORDAC SK 5xxE can be easily adapted to various requirements. Alphanumerical display and operating modules can be used for simple commissioning. For more complex tasks, various connections to a PC or an automation system can be selected.
1 Introduction 2.1.1 Installation of the SK TU3 technology unit The technology units must be installed as follows: 1. Switch off the mains voltage, observe the waiting period. 2. Push the control terminals cover down slightly or remove. 3. Remove the blank cover by pressing the release on the lower edge and pulling off with an upward turning movement. If necessary, the fixing screw next to the release must be removed. 3 2 „press“ 4.
NORDAC AS-Interface Manual 2.2 NORDAC SK 700E By the use of different modules for display, control and parameterisation, the NORDAC SK 700E can be easily adapted to various requirements. Alphanumerical display and operating modules can be used for simple commissioning. For more complex tasks, various connections to a PC or an automation system can be selected.
2 Modules 2.2.1 Installation of the SK TU1 technology unit The installation of the technology units must be carried out as follows: 1. Switch off the mains voltage, observe the waiting period. 2. Remove the dummy cover by actuating the unlocking device on the top and bottom edge. 3. Allow the technology unit to engage audibly by pressing lightly on the installation surface. N O RD A C 700E 2.2.2 AS interface module SK TU1-AS1 The SK 700 E supports the AS interface technology unit from software version 3.
NORDAC AS-Interface Manual 2.3 NORDAC SK 750E and trio SK 300E By the use different modules for display, control and parameterisation, the NORDAC SK 750E and trio SK 300E can be easily adapted to various requirements. Alphanumerical display and operating modules can be used for simple commissioning. For more complex tasks, various connections to a PC or an automation system can be selected.
2 Modules 2.3.1 Installation of the SK TU2 technology unit To install a technology unit, remove the 6 screws from the cover plate. Note the grounding (earthing) lead, which is connected to the plate with a plug. When installing the technology unit this lead must be connected in order to ensure complete grounding (earthing). Sealing for the maximum protection level IP55/66 is only ensured by installing the seal and correctly tightening the 6 screws.
NORDAC AS-Interface Manual 2.3.2 AS interface module SK TU2-ASx The trio SK 300E supports the AS interface technology unit as of software version 1.6 Rev.3, the SK 750E as of the software version 3.1 Rev. 1. Connector assignment: Socket I/O 1 1 AUX 24V 2 Dig In 1 3 AUX GND 4 Dig Out 1 5 Dig In 3 Socket I/O 2 1 AUX 24V 2 Dig In 2 3 AUX GND 4 Dig Out 2 5 Dig In 4 Connector PWR Device S/E LED (red/green): Status/error of module (see Section 4.3) AS- Int.
2 Modules 2.4 Schematic circuit diagram of the AS interface technology unit The following schematic circuit diagrams illustrate the internal structure or wiring of the AS interface modules. 2.4.
NORDAC AS-Interface Manual 2.4.
2 Modules 2.5 Description of connections to the AS interface module SK TU1- / TU3-AS1 By means of the AS interface cable and the AS interface master the sensors and actuators are connected to the automation device via the AS interface module. To connect an SK TU1 / TU3-AS1 module to an AS interface network, special connecting accessories must be used. An AS interface cable with an M12 connector and open cable ends is required in order to connect to the Phoenix terminals of the SK TU1 / TU3-AS1.
NORDAC AS-Interface Manual 2.5.2 Connection of the AS interface AUX power supply The black cable is used for the power supply to the sensors. The AS interface supply cable is connected to the AUX 24V and AUX GND terminals. The corresponding connection terminals on the particular AS interface module are illustrated in Sections 2.1.2 / 2.2.2 / 2.3.2. The AS interface modules have multiple supply terminals. These terminals are interconnected internally.
2 Modules c) 2 Sensors: Use of a 5-wire M12 cable with open cable ends and wiring of the sensors according to the assignment of connections. As there is no standard system connection technology, the wiring must be carried out accordingly.
NORDAC AS-Interface Manual 2.6 Recommended AS interface accessory and connection components NOTE The components listed below or in this section should only be regarded as recommendations. For further information please refer to the particular manufacturer's information and data sheets. Please observe the manufacturer's information regarding installation and the corresponding installation guidelines.
2 Modules AS-i single flat cable connector to M12 to connect the AS interface or AUX cable Connections for connection to the yellow AS-i flat cable: Pin 1: AS interface + Pin 3: AS interface for connection to the black / AUX flat cable: Pin 1: +24V DC Pin 3: 0V Supplier Designation Pepperl+Fuchs Passive connector to AS interface or auxiliary voltage to 1 x M12 round plug connector ifm Flat cable branch, M12 socket - AS-i flat cable AC5005 Flat cable branch, M12 socket - AS-i flat cable E70096 MU
NORDAC AS-Interface Manual M12 round connector for connecting sensors/actuators and options/slaves to the AS interface cable M12 x 1 round plug connectors are supplied and distributed by many manufacturers of industrial applications. When selecting the components, special attention should be paid to application-specific requirements, e.g. Type of connection, number of pins (4 or 5-pin) Plug and socket coding, straight or angled design etc.
3 Bus structure and topology 3 Bus structure and topology The AS interface network can be set up in any desired form. Linear, star, ring and tree structures are possible. An existing network can be expanded by further slaves at any time. For the sake of simplicity the standard slave application will mainly be described in this manual. Up to 31 standard slaves (i.e. a maximum of 124 binary sensors and 124 binary actuators) or 62 A/B slaves (i.e.
NORDAC AS-Interface Manual The AS interface system replaces the expensive parallel wiring of decentralised sensors (inputs) and actuators (outputs) with a few bits (1-4 bits). The AS interface options from Getriebebau NORD, which need to be supplied with an additional +24V DC supply (AUX, black cable connection) for the electrical components, can also be used as I/O expansions for customer-specific applications.
3 Bus structure and topology An additional bit is required in order to address an A/B slave. This bit is inserted into the reference data area, so that the content of the 4 data bits must be divided over 2 protocols, i.e. 2 transmission cycles. On the other hand, the response telegrams contain all 4 data bits, so that the telegrams from the slave to the master are completely updated after each order. Also, due to the extended address range, A/B slaves can only be accessed every 2nd cycle.
NORDAC AS-Interface Manual Power on Initialisation OK Configuration Parameter call up received Reset outputs In the "configuration" status the slave waits to be identified by the master and ultimately to be activated. This is performed by means of a command "Exchange parameters" After this the slave reverts to normal operation and responds to calls for data. A timeout function "watchdog" monitors the current data communication.
3 Bus structure and topology AS interface properties Topology free structure, i.e. linear, tree, star, spur branches etc. Medium for data + energy unshielded 2-wire AS interface cable (= yellow standard AS interface cable) AUX connection (black cable) Insulation piercing technology as per IEC 60352-6 AUX voltage according to PELV (IEC 60364-4-41) Length of bus cable max. 100 m (without repeater), can be extended to 300 m with a maximum of 2 repeaters Number of slaves max.
NORDAC AS-Interface Manual 3.2 Cable type A simple 2-wire cable with a cross section of 2 x 1.5mm² should be used for networking. It is recommended that the yellow profile cable is used. Due to the mechanical profile of the cable, each slave can be simply connected without danger of incorrect polarity. As the geometrically coded position of the wires is fixed and there is no obstruction from shielding, the slaves can be connected to the AS interface bus using simple insulation piercing components.
4 Frequency inverters - settings and control elements 4 Frequency inverters - settings and control elements Parameters and settings specific to the AS interface can be made via a ParameterBox or also via the NORD CON software. For more detailed information, please refer to the corresponding operating instructions. To ensure bus monitoring of the AS interface, the telegram downtime P513 should be parameterised by the user.
NORDAC AS-Interface Manual NOTE For array parameters the sub-index (the value transferred via the bus) starts at 0, the designation of the element corresponds to 1 (index). A detailed description of the signal processing (e.g. High or Low signal) of the individual functions is documented in the relevant manuals of the device series. 4.1.1 Control terminal parameters Parameter P480 .. - 01 ... .. - 12 0 ... 72 Comments Function Bus I/O In Bits The Bus I/O In Bits are perceived as digital inputs.
4 Frequency inverters - settings and control elements 4.1.2 Additional parameters Parameter Setting value / Description / Note Comments P509 Interface SK 300E, SK 700E, SK 750E 0 ... 21 [0] Selection of the interface from which the inverter is controlled. 0 = Control terminal or keyboard control with the Control Box (option), the ParameterBox (option) or the Potentiometer option 1 = Control terminals only, the inverter can only be controlled via the 4 digital inputs and the analog input.
NORDAC AS-Interface Manual Parameter P510 ... - 01 ... - 02 0 ... 10 [0] Setting value / Description / Note Comments Setpoint source SK 500E Selection of the setpoint source to be parameterised. Main setpoint source [01] = [02] = Auxiliary setpoint source Selection of the interface via which the FI receives the setpoint.
4 Frequency inverters - settings and control elements Parameter Setting value / Description / Note Comments P543 (P) Actual bus value 1 0 ... 12 (22) The return value 1 (IW1) can be set for bus control in this parameter.
NORDAC AS-Interface Manual Parameter Setting value / Description / Note P546 (P) Bus setpoint 1 0 ... 7 (47) In this parameter, a function is assigned to the delivered setpoint 1 (SW1) for bus control. [1] NOTE: Further details can be found in the respective FI manual or in the description of P400.
4 Frequency inverters - settings and control elements 4.1.3 Information parameters Parameter P740 Setting value / Description / Note ... - 01 … ... - 06 0000 ... FFFF (hex) P740 ... - 01 … ... - 13 0000 ... FFFF (hex) P741 ... - 01 … ... - 06 0000 ... FFFF (hex) P741 ... - 01 … ... - 13 0000 ... FFFF (hex) Process data bus In Displays the actual control word and the setpoints.
NORDAC AS-Interface Manual Parameter Setting value / Description / Note P742 Comments Database version 0 ... 9999 Displays the internal database version of the FI. P744 Configuration SK 300E, SK 700E, SK 750E This parameter displays the option modules detected by the FI. 0 ... 9999 The display with the ParameterBox is in plain text. The possible combinations are displayed in code in the ControlBox.
4 Frequency inverters - settings and control elements Parameter Setting value / Description / Note P746 Comments Module status 0000 ... FFFF (hex) SK 300E, SK 500E Indicates the actual status (readiness, error, communication) of the technology unit (SK TU2/3-xxx), but only when own processor is present, therefore not for the SK TU2/3-CTR. Code details can be found in the respective BUS module manual. Different contents are shown depending on the modules. (AS interface: See Section 4.2) P746 ...
NORDAC AS-Interface Manual 4.3 LED display The status of the AS interface technology unit is displayed with 2 LEDs: • Device S/E: Module status/error (dual LEDs) • AS-Int.
4 Frequency inverters - settings and control elements 4.5 Peripheral error on AS interface module A peripheral error of an AS interface slave occurs if: • No AC line input (mains) voltage is applied to the inverter • The 24V supply (AUX 24V) to the AS interface module is not present A peripheral error is not reported if an error specific to the inverter is present.
NORDAC AS-Interface Manual 5 Data transfer / Parameter-string transfer NOTE The information in Section 5 does not apply to the AS interface Technology Unit SK TU2-AS3 (A/B slave). (only necessary for extended functionality) The Parameter string transfer is available for the modules SK TUx-AS1 (Standard slaves, slave profile S-7.4). This extended functionality is implemented in the AS interface master according to the Complete Specification 2.1.
5 Data transfer / Parameter-string transfer 5.1 Read ID string (read from slave) Via the AS interface module, specific data from the frequency inverter can be read out by means of the Read ID string command. The information and values in the ID string will first be shown when the AS interface has recognised the frequency inverter.
NORDAC AS-Interface Manual 5.3 Read / Write parameter string (read from slave / write to slave) The parameterisation of the frequency inverter can be carried out and checked with the commands Read parameter string and Write parameter string. Information parameters can also be read out in the same way. For both reading and writing, the first two bytes in the parameter string are used as an index. Then the data content is transferred. The number of data words is restricted to 8 words (16 Byte).
5 Data transfer / Parameter-string transfer Index Parameter No. of parameter sets Parameter / array elements4 No. Resolution Value range5 0040hex - 0043hex Fixed frequency 1 1–4 P429 0.1 Hz -400 – 400 Hz 0044hex - 0047hex Fixed frequency 2 1–4 P430 0.1 Hz -400 – 400 Hz 0048hex - 004Bhex Fixed frequency 3 1–4 P431 0.1 Hz -400 – 400 Hz 004Chex - 004Fhex Fixed frequency 4 1–4 P432 0.1 Hz -400 – 400 Hz 0050hex - 0053hex Fixed frequency 5 1–4 P433 0.
NORDAC AS-Interface Manual Examples of direct parameters: Writing the parameter P102 start-up time with value 1s (with 0.
5 Data transfer / Parameter-string transfer 5.4 Process data (PZD) 5.4.1 Status word (ZSW) In the inverter response telegram, in the area of the process data the status word (ZSW) is transferred as the first word. For example, the status word "Ready for switch-on" corresponds to 0B31(hex).
NORDAC AS-Interface Manual Deviations in the status word (ZSW) for SK 300E and SK 700/750E series devices With the above device types, the meanings of the two bits 10 and 13 in the status word deviate from the status word of the SK 500 E.
5 Data transfer / Parameter-string transfer 5.4.3 Actual value 2 and actual value 3 (IW2/3) It is possible to forward two more actual values to the controller if PPO type 2 or 4 is used for transfer. The actual value 2 (IW2) is transmitted in PZD4. The value to be transferred can be selected in P544 (actual bus value 2). Actual value 3 (IW3) can be transmitted in PDZ3 if actual value 1 is not a 32 Bit value. The value to be transferred can be selected in P545 (actual bus value 3).
NORDAC AS-Interface Manual 5 Internal status machine Inverter sw itch-on Bit2 = 0: Quick stop 1 3 4 5 6 8 Not ready for sw itch-on 6 Quick stop active Bit1 = 0: Block voltage v Bit2 = 0: Quick stop Loading relay activated 2 4 5 f = 0 achieved (Quick stop completed) 2 Sw itch-on interlock From any device status Bit0 = 0: Stop & Bit1 = 1: voltage enabled & Bit2 = 1: impulse enabled (xxxx x1xx xxxx x110) Bit0 = 0: Stop 3 2 5 5 Error 7 Ready for sw itch-on Bit 3 = 0: Block operation
5 Data transfer / Parameter-string transfer 5.5 Data transfer with USS reference data / Parameter range (PKW) (only necessary for extended functionality) The reference data (without telegram framework) correspond to the USS protocol. Using the PKW mechanism, parameter processing can be carried out in the cyclical data traffic. For this the master formulates an order and the inverter formulates the response to this.
NORDAC AS-Interface Manual The following table lists all the orders which can be transferred from the master to the inverter. The right-hand column contains the response, which is normally sent (response label positive). Only certain response labels are possible, depending on the order label. In case of error (response label negative) the inverter will always supply the value 7 in the response label (AK) to the master.
5 Data transfer / Parameter-string transfer Error messages if the order cannot be executed In the response label "Order cannot be executed" (AK = 7), then an error message is added to the parameter value (PWE2) of the inverter response. For the meanings of the values transferred, please refer to the following table. No.
NORDAC AS-Interface Manual 5.5.3 Parameter value (PWE) For each parameter, the transfer of the parameter value (PWE) is always as a word (16 Bit) or double word (32 Bit). Only one parameter value can be transferred in a telegram. A 32 bit parameter value comprises PWE1 (high value word) and PWE2 (low value word, 4th word). A 16 Bit parameter value is transferred in PWE2. For negative values the high word must be set to FFFF hex. Note: 32- Bit parameter values are only used with the posicon option.
6 Examples 6 Examples For information about AS interface data, e.g. identification code (ID Code), extended ID Codes 1 and 2 and the I/O configuration (I/O Code), please refer to Section 8. NORD AS-Interface modules are Standard-Slaves (exception: SK TU2-AS3 = A/B Slave) and are set with the slave address 0 at the factory. 6.1 Example based on a Siemens Master CP343-2P This example supports the user in the design and implementation of the AS interface application.
NORDAC AS-Interface Manual For this, the following FI parameters must be set as follows: P480 [01] Bus IO In Bit 0 1 = Enable right P480 [02] Bus IO In Bit 1 2 = Enable left P480 [03] Bus IO In Bit 2 8 = Parameter switch-over P480 [04] Bus IO In Bit 3 12 = Error acknowledgement P481 [01] Bus IO Out Bit 0 2 = Inverter operating P481 [02] Bus IO Out Bit 1 7 = Error P509 interface 0 = Control terminals or keyboard control P543 Bus actual value 1 12 = Bus IO Out Bits 0-7 P546 Bus setpoint 1 17
6 Examples 6.1.4 Data transfer of the sensor signal statuses to the AS-I master alone It is often the case that the signal statuses from photoelectric beam detectors, buttons or other field components have to be communicated to the AS i master via the two-conductor AS interface network. In the parameterisation of the available BUS IO bits, there is the possibility of transferring the signal statuses of sensors connected to the AS interface module or the IO sockets 1/2 to the ASi master.
NORDAC AS-Interface Manual 6.2.1 Read ID string The command number 42hex is to be entered into DB13.DBB4 and the slave address 1 into DB13.DBB5 in the transmission buffer of the command interface. After the command or the order from the AS interface has been completed without error (DONE = 1), the response date is displayed in the reception buffer. For the allocation of the individual status Bits, please refer to the information in Section 5.1.
6 Examples Data Byte in DB13 Value in hex Meaning / Note DBB4 40 Write the command number for the parameter string DBB5 01 Slave address DBB6 04 Number of parameter Bytes, 04hex DBB7 00 Byte 0: Index DBB8 54 Byte 1: Index, start-up time P102, parameter set 1 DBB9 03 Byte 2: parameter value, taking the resolution 0.01 into account DBB10 E8 Byte 3: parameter value, taking the resolution 0.01 into account With this, the start-up time in P102 for parameter set 1 is changed to 10.00s.
NORDAC AS-Interface Manual Example of reading direct parameters: In order to check whether the direct parameter has been correctly transferred, a plausibility check should be performed. For this, the corresponding index must be sent with the function Write Parameter. For the start-up time P102 in parameter set 1, this would be the Index 0054hex. Only the Index needs to be transferred, i.e. the number of parameter Bytes is 2.
6 Examples Example for the writing of a parameter (PKW data via USS protocol / Parameter string): For example, in order to set the release time of the brake P114 (parameter number PNU = 114 / 72hex) of the FI to 1 sec for parameter set 1, proceed as follows: • Select parameter label PKE (AK =1 for change parameter value (word) and parameter number PNU = 72hex) • Taking the internal resolution of the frequency inverter into account (0.01sec) => for 1 sec there must be a parameter value PWE of 1 / 0.
NORDAC AS-Interface Manual Example for the reading of a parameter (PKW data via USS protocol / Parameter string): In order to check whether the order has been correctly carried out and the new value of 1sec has been entered in parameter P114 for parameter set 1 in the inverter, the corresponding response label must be read out using the command Read Parameter String Data Byte in DB13 Value hex in Meaning / Note DBB4 41 Read the command number for the parameter string DBB5 01 Slave address The foll
6 Examples 6.4 AS interface as I/O expansion of the frequency inverter control terminals By means of the AS interface module the number of digital inputs and outputs on the frequency inverters or made available by the use of a customer interface can be expanded by 4 further inputs and two outputs. Via the 4 sensor inputs (Sensor Dig In / Bus IO In Bits 4 to 7) all functionalities specific to the frequency inverter can be assigned or parameterised via the parameter arrays in parameter P480.
NORDAC AS-Interface Manual Parameterisation of functions: Only the parameters relevant for the function of the I/Os are listed here. For further information, please refer to the manuals BU0500 and BU0510.
7 Faults 7 Faults 7.1 Troubleshooting The majority of frequency inverter functions and operating data are continuously monitored and simultaneously compared with limiting values. If a deviation is detected, the inverter reacts with a warning or an error message. Basic information on this topic is contained in the manual for the basic equipment. Errors cause the frequency inverters to switch off, in order to prevent a device fault. The following options are available to reset a fault (acknowledge): 1.
NORDAC AS-Interface Manual 7.2 Error messages Table of possible bus-specific error messages Display in the ControlBox Fault Group Details in Text in the ParameterBox P700 / P701 E010 10.0 10.2 10.4 10.1 10.3 Telegram downtime External bus module telegram timeout External bus module initialisation failure Cause • Remedy Data transfer is faulty. Check P513. • Check external Bus connection. • Check bus protocol program process. • Check Bus Master. Telegram transfer is faulty.
7 Faults 7.3 Causes of errors The following table lists possible causes of errors / error statuses and the procedure for rectifying them: Error / Status Possible cause Course of action Parameters specific to the AS interface are not displayed on the display of the FI or in NORDCON The necessary software version of the FI is not installed. ¾ Check which software version is installed using parameter P707 SK 700E ≥ Version 3.1 Rev.
NORDAC AS-Interface Manual 8 Technical data AS interface options are only supported as of a particular software version Software version requirements: SK 700E from Version 3.1 Rev.1 SK 750E from Version 3.1 Rev.1 SK 300E from Version 1.6 Rev.3 SK 5xxE from Version 1.3 Rev. 0 Electrical data Supply of AS interface connection 18.5V – 31.6V, max. 35mA PWR connection (yellow cable) Supply of communications electronics 18V -30V DC, electronics (max. 200mA) + sensors + actuators, and sensors/actuators max.
9 Additional information AS interface data SK TUx-AS1 (Standard Slave) Slave profile S-7.4.0 "Extended Slave Profile for Combined Transaction type 1 with 4 Bit mode (4I / 4O)" Required master profile M4 (in some cases M3 also possible) I/O-Code 7 ID Code 4 External ID Code 1 F External ID Code 2 0 Address 1 – 31 (Condition as delivered: 0) Toggle bit timeout 1s String transfer length max. 9 words (2 Byte for Index, and max.
NORDAC AS-Interface Manual 9 Additional information 9.1 Maintenance and servicing information In normal use, NORDAC frequency inverters and their accessories are maintenance-free. If air intake filters have been built into the control cabinet, then these should also be regularly cleaned or replaced. If you contact our technical support, please have the precise device type (rating plate/display), accessories and/or options, the software version used (P707) and the series number (rating plate) at hand.
10 Keyword index 10 Keyword index A Actual value.......................... 35, 48 F Faults.......................................... 65 AS Int. PWR/FLT LED................ 40 AS interface............................ 7, 25 AS interface slave status............ 40 R Repairs .......................................70 Repeater.....................................29 G RoHS compliance .........................9 Guidelines .................................. 30 S B Bus cable ...............................
Part No.