User guide
2 Assembly and installation
BU 0135 GB-2713 Pre-series version 27
2.5.3 Electro-mechanical brake
Connection of an electromagnetic brake is possible for all SK 1x5E devices. To control the brake, an output
voltage is generated to terminals 79 / 80 (MB+ / MB-) by the motor starter to terminals 79 / 80 (MB+ / MB-)
(also refer to Sections 2.6.1 to 2.6.2). This depends on the supply voltage. The assignment is as follows:
Mains voltage / Alternating current (AC) Brake coil voltage (DC)
230 V ~ 105 V =
400 V ~ 180 V =
460 V ~ / 480 V ~ 205 V =
The allocation of the correct brake or brake coil voltage must be taken into account in the design with refer-
ence to the mains voltage of the motor starter.
NOTE
For the connection of a mechanical brake to the terminals of the motor starter, parameters
P
107 / P114 (brake application time / release time ) must be adjusted. In order to prevent
damage to the brake control, a value ≠ 0 must be set in parameter (P107).
The following settings for (P107/P114) are recommended for NORD brakes:
BRE5, BRE10, BRE40 : 0.02s,
BRE20, BRE60, BRE100, BRE150: 0.03s,
BRE250: 0.04s,
Connection terminals: Screw terminals, 0.6 x 3.5 mm slot-head screwdriver
Connection cross-section: 0.2 ... 2.5mm
2
, AWG 24-14, rigid or flexible, without wire end sleeves
Brake connection terminal 79/80