User guide

2 Assembly and installation
BU 0135 GB-2713 Pre-series version 31
Additionally for SK 145E ... SK 175E
43 24V 24V supply
Output
24VDC ±25%
165mA
Connection of the supply voltage
for the control unit and supply to
outputs DOUT1+2 as well as any
connected initiators
-
40 GND / 0V Reference potential
for digital signals
-
C1 DIN3 Digital input 3
{ON right}
Digital input as per
EN 61131-2, Type 1
Low: 0-5V (~ 9.5k)
High: 15-30V
(~ 2.5-3.5k)
Input capacitance: 10nF
Scanning time: 1ms
Reaction time: 4ms
Digital input for the evaluation of a
connected initiator. This input is
transferred to the control unit
directly via the AS interface or the
PROFIBUS. It is not evaluated by
the starter.
-
C2 DIN4 Digital input 4
{ON left}
-
84 ASI+
Actor Sensor
Interface
4
26.5 31.6V,
max. 240mA
For control of the SK 1x5E via the
simple field bus level.
By means of jumpers it can be
selected whether only the "yellow
cable" is used, or "yellow" and
"black", i.e. supply with additional
auxiliary power.
-
85 ASI-
82 PBR-B
PROFIBUS DP
5
For control of the SK 1x5E via
PROFIBUS DP.
-
83 PBR-A
2.6.3 Control connections for SK 1x5E communication
Terminal/
Designation
Function
{Factory setting}
Data Description / wiring suggestion Parameter
all SK 1x5E, connector block RJ12, RS232
3 GND
Reference potential
for Bus signals
0V digital
RS485_A
RS485_B
GND
TXD
RXD
+ 5V
+24V
n.c.
n.c.
RJ12: Pin No. 1 … 6
1: n.c.
2: n.c.
3: GND
4: RS232_TxD
5: RS232_RxD
6: +24V
4 232 TXD
Data cable RS232
Baud rate 38400Baud
Address 0
USS protocol
5 232 RXD
6 +24V 24V supply voltage
from the FI
24V ± 20%
4
SK145E…SK175E with integrated AS interface
5
SK145E…SK175E with integrated PROFIBUS