Pos : 1 /T ec hnis che Infor mationen/Info Änder ung der Hauptanlei tung - TIs i m Anhang beac hten @ 4\mod_1394536795020_388.doc x @ 121561 @ @ 1 Additional information to BU 0200 NOTICE Modification of BU 0200 Please regard the additional information attached at the end of the document concerning: • • AS-Interface (TI 800 0000 0000 7) DIP-Switch (TI 800 0000 0000 8) Bargteheide, 11.03.2014 Getriebebau NORD GmbH & Co. KG Getriebebau-Nord-Straße 1 22941 Bargteheide, Germany http://www.nord.
Commissioning from page 148 GB BU 0200 SK 200E Frequency inverter manual
SK 200E Manual for frequency inverters 2 Safety information BU 0200 GB-4411
NORDAC SK 200E Manual Safety information NORD frequency inverters Safety and operating instructions for drive power converters (as per: Low Voltage Directive 2006/95/EEC ) 1. General During operation, drive power converters may, depending on their protection class, have live, bare, moving or rotating parts or hot surfaces. Unauthorised removal of covers, improper use, incorrect installation or operation causes a risk of serious personal injury or material damage.
SK 200E Manual for frequency inverters Concerning this document Documentation Designation: BU0200 GB Part No.: 607 20 02 Device series: SK 200E, SK 210E, SK 220E, SK 230E, SK 205E, SK 215E, SK 225E, SK 235E Device types: SK 2xxE-250-112-O ... SK 2xxE-750-112-O, 0.25 - 0.75kW, 1~ 100-120V, Output 230V SK 2xxE-250-123-A ... SK 2xxE-111-123-A, 0.25 - 1.1kW, 1~ 220-240V 1 SK 2xxE-250-323-A ... SK 2xxE-112-323-A, 0.25 - 11.0kW, 3~ 220-240V 2 SK 2xxE-550-340-A ... SK 2xxE-222-340-A, 0.55 - 22.
SK 200E Manual for frequency inverters Concerning this document Intended use of the frequency inverter Compliance with the operating instructions is necessary for fault-free operation and the acceptance of possible warranty claims. These operating instructions must be read before working with the device! These operating instructions contain important information about servicing. They must therefore be kept close to the device.
SK 200E Manual for frequency inverters 1 GENERAL INFORMATION .................................................................................................... 10 1.1 Overview ............................................................................................................ 11 1.2 Delivery .............................................................................................................. 12 1.3 Scope of supply ..........................................................................
Table of Contents 3 OPTIONS ................................................................................................................................67 3.1 Overview of optional modules ............................................................................68 3.1.1 Overview of internal customer units SK CU4-… ..................................................... 68 3.1.2 Overview of external technology units SK TU4-… .................................................. 70 3.
SK 200E Manual for frequency inverters 6 PARAMETERISATION ........................................................................................................ 168 6.1 Parameterisation of frequency inverter SK 2xxE............................................. 170 6.1.1 Operating displays ................................................................................................ 173 6.1.2 Basic parameters (Frequency inverter) ................................................................. 175 6.1.
Table of Contents 9 ADDITIONAL INFORMATION ..............................................................................................281 9.1 Setpoint processing in the SK 2xxE .................................................................281 9.2 Process controller .............................................................................................282 9.2.1 Process controller application example ................................................................. 282 9.2.
SK 200E Manual for frequency inverters 1 General information The SK 200E series is based on the tried and tested NORD platform. These devices feature a compact design with optimum control characteristics. These devices are provided with sensorless vector current control which in combination with asynchronous three-phase motor types constantly ensures an optimised voltage-to-frequency ratio. This has the following significance for the drive: Peak start-up and overload torques at constant speed.
1 General information 1.1 Overview This manual describes two very similar basic versions of the SK 200E product family. Wherever the SK 2xxE is referred to, this concerns information which applies to all devices in this family. If the information exclusively applies to the versions SK 205E / SK215E / SK225E / SK235E, this is apparent from the designation SK 2x5E.
SK 200E Manual for frequency inverters Additional features, Size 4 Feature 200E 210E 220E 230E Integrated 24V power supply x x x x Number of digital inputs (DIN) 4 3 4 3 Number of digital outputs (DO) 2 2 2 2 Number of analog inputs (AIN) 2 2 1 1 Additional 2 potentiometers for minimal configuration x x x x Electromechanical brake control x x x x Safe pulse block (STO / SS1) (see BU 0230) x x x AS interface (4I / 4O) x 1.
1 General information external SK TU4-IOE, external I/O extension SK TU4-PBR, external Profibus module SK TU4-CAO, external CANopen module SK TU4-DEV, external DeviceNet module SK TU4-ECT, external EtherCAT® module SK TU4-24V-123-B, external 24V mains unit 1~ 230V SK TU4-24V-140-B, external 24V mains unit 1~ 400V SK TU4-POT-123-B, external 24V and potentiometer/switch module 1~ 230V SK TU4-POT-140-B, external 24V and potentiometer/switch module 1~ 400V SK TI4-TU-BUS or NET or MSW, connection unit TU4 SK T
SK 200E Manual for frequency inverters CAUTION The heat sink and all other metal components can heat up to temperatures above 70°C. When mounting, sufficient distance from neighbouring components must be maintained. When working on the components, allow sufficient cooling time beforehand Protection against accidental contact may need to be provided. ATTENTION The frequency inverter can carry voltages for up to 5 minutes after being switched off at the mains.
1 General information 1.5 Certifications 1.5.1 European EMC Directive If the NORDAC SK 2xxE is installed according to the recommendations in this instruction manual, it meets all EMC Directive, requirements, as per the EMC product standard for motor-operated systems EN 61800-3. (see also Section 9.3, Electromagnetic Compatibility [EMC].) 1.5.2 Approval for UL and cUL The section applies for all devices of sizes 1 – 3. The approval for size 4 is at present in preparation.
SK 200E Manual for frequency inverters „The torque value for the field wiring terminals for mains circuit terminals, motor terminals, break terminals and breaking resistor terminals must be 11 … 15 lb-in (1.2 … 1.5Nm). The torque value for the field wiring terminals for control circuit terminals must be 4.4 … 5.3 lb-in (0.5 … 0.6Nm).” The tightening torque value for the terminals the mains and motor cables, the brake and the brake resistor must be between 11 … 15 lb-in (1.2 … 1.5Nm).
1 General information 1.6 Nomenclature / type codes Unique type codes have been defined for the individual modules and devices. These provide individual details of the device type and its electrical data, protection class, fixing version and special versions.
SK 200E Manual for frequency inverters 1.6.1 Type codes / Frequency inverter - basic device SK 205E-370-323-A (-C) IP protection class: Standard = IP55, C = “coated“ IP66 (Size 1 to Size 3 = IP66) Radio interference filter: O = without, A = Class A1, B = Class B1 Mains voltage: x12 = 115V, x23 = 230V, x40 = 400V Number of mains phases: 1xx = single phase, 3xx = 3-phase Digits before decimal point for power: 0 = 0.xx, 1 = 0x.x0, 2 = 0xx.0 Device nominal power: 250 = 0.25kW, 370 = 0.37kW, ... 222 = 22.
1 General information 1.6.3 Type codes / Adapter unit - Technology Unit SK TI4-TU-BUS (-C-WMK-TU) Wall mounting kit: -1 = Size 1 + 2, -2 = Size 3, -3 = Size 4 IP protection class: Standard = IP55, C = “coated“ IP66 Suitable device types: NET = optional net module (e.g. TU4-24V-… ) BUS = optional bus module (e.g. CANopen: TU4-CAO) Group: TU = Technology unit Device series: SK TI4 = Adapter unit SK TI4 (...) Options, only implemented if required.
SK 200E Manual for frequency inverters 1.6.4 Type codes / Optional modules For bus module or I/O extension SK TU4-CAO (-C-M12) M12 system connector: only TU4, alternative to terminals IP protection class: Standard = IP55, C = “coated“ IP66 Option type: CAO = CANopen, PBR = Profibus, ECT = EtherCAT® DEV = DeviceNet, IOE = I/O-Erweiterung Option series: TU4 = external Technology Unit CU4 = internal Customer Unit (...) Options, only implemented if required.
1 General information 1.7 Version with protection class IP55 / IP66 The SK 2xxE frequency inverters in sizes 1 to 3 and the additional modules are available in protection classes IP55 (standard) or IP66 (optional). The SK 2x0E frequency inverters in size 4 are only available in protection class IP55. Protection class IP66 must always be stated when ordering! There are no restrictions or differences to the scope of functions in either protection class.
SK 200E Manual for frequency inverters 2 Assembly and installation 2.1 Installation and assembly SK 2xxE frequency inverters are available in various sizes depending on their output. Connection of the SK 2xxE to the motor or the wall-mounting unit is made by means of the a suitable size of connection unit SK T14-… .The frequency inverter is mounted by means of integrated plug contacts. The devices require adequate ventilation to protect against overheating.
2 Assembly and installation 2.1.1 Mounting the adapter unit If a complete drive unit is supplied (gear unit + motor + frequency inverter) the SK 2xxE frequency inverter and the SK T14-... connection unit are always completely assembled and tested. The adapter unit can also be ordered separately for subsequent mounting on an existing motor or to replace a different motormounted frequency inverter.
SK 200E Manual for frequency inverters 2.1.2 Adapters for Different Motors In some cases, the terminal box attachments are different for different sizes of motor. Therefore, it may be necessary to use an adapter to mount the frequency inverter. In order to guarantee the maximum protection class IP55 / IP66 of the entire unit, motor must also have a corresponding protection class.
2 Assembly and installation 2.1.3 Installing the SK 2xxE In order to make the electrical connections to the SK 2xxE it may first be necessary to remove it from the connection unit. To do this, remove the 4 fastening screws, so that the frequency inverter can be lifted off vertically. After the electrical connection of the power cables has been made, the frequency inverter can be replaced. This must be carried out in a vertical direction relative to the connection unit without tilting.
SK 200E Manual for frequency inverters 2.1.4 Optional locations for the "SK TI4-…" adapter unit View from left Size 1 to 3 3L 4L 3BL 3AL 5L 6L 1 7L 8L 2 3R 4R 3AR 3BR 5R 8R Top view 3R 3BR 8R 3AR 7R 9R 6R View from right Size 1 to 3 4R 4L 5R 5L 3L 9L 6L 6R View from right, Size 4 7R 3AL 3BL 7L 8L View from left, Size 4 The above drawings indicate the different installation locations for optional modules.
2 Assembly and installation Option location Position Meaning Size 1 Internal Mounting location for customer units SK CU4-… 2 Internal Mounting location for Size Size 1 - 3 Size 4 internal brake resistor SK BRI4-… 3* on side Mounting location for external brake resistor SK BRE4-… external technology units SK TU4-… Control options, e.g. SK CU4-POT HARTING plug connectors 3 A/B* on side Cable gland M25 M25 Not available if location 3 is occupied or SK TU4-… is fitted.
SK 200E Manual for frequency inverters 2.2 SK 2xxE dimensions 2.2.1 Power rating / Motor size Mains/power matching: SK 2xxE Size 3 28 4 1~ 110-120V 1~ 200-240V 3~ 200-240V 3~ 380-500V Size 1 0.25 ... 0.37kW 0.25 ... 0.55kW 0.37 ... 1.1kW 0.55 ... 2.2kW Size 2 0.55 ... 0.75kW 0.75 ... 1.1kW 1.5 ... 2.2kW 3.0 ... 4.0kW Size 3 - - 3.0 ... 4.0kW 5.5 ... 7.5kW Size 4 - - 5.5 ... 7.5kW 11.0 … 22.
2 Assembly and installation 2.2.2 SK 2xxE mounted on motor Size FI Size 1 Size 2 Size 3 Size 4 Housing dimensions SK 2xxE / Motor Motor g g1 Size 71 * 145 201 Size 80 165 195 Weight of SK 2xxE without motor n o p Approx. [kg] 214 236 236 Size 90 S / L 183 200 251 / 276 Size 100 201 209 306 Size 80 165 202 236 Size 90 S / L 183 207 156 3.0 176 4.1 218 6.9 305 17.
SK 200E Manual for frequency inverters 2.2.3 Wall mounting of the SK 2xxE The SK 2xxE can be installed in the vicinity of the motor by means of an optional wall mounting kit. 2.2.3.1 Wall-mounting kit SK TIE4-WMK-L-… The wall-mounting kit SK TIE4-WMK-L-… enables the frequency inverter to be installed close to the motor. With this kit, the frequency inverter can comply with protection class IP55. This kit is only available for inverter sizes Size 1 to 3.
2 Assembly and installation 2.2.3.2 Wall-mounting kit SK TIE4-WMK-1 (up to -3) The wall-mounting kit SK TIE4-WMK-1 (up to -3) provides a simple method of installing the frequency inverter near to the motor. With this kit, the frequency inverter can comply with protection class IP66 (Size S 4: IP55). NOTE Derating With the use of the wall-mounting kit SK TIE4-WMK-1 (or -2) the frequency inverter is no longer optimally ventilated.
SK 200E Manual for frequency inverters 2.2.3.3 Frequency inverter installation positions with wall-mounting kit Installation of the frequency inverter close to the motor is permissible in the following installation orientations.
2 Assembly and installation 2.3 Brake resistor (BR) During dynamic braking (frequency reduction) of a three phase motor, electrical energy is returned to the frequency inverter. In order to avoid switch-off of the FI due to excess voltage and internal or external braking resistor can be used. With this, the integrated brake chopper (electronic switch) pulses the link circuit voltage (switching threshold approx. 420V/720V DC, according to the mains voltage) into the braking resistor.
SK 200E Manual for frequency inverters 2.3.2 External brake resistor SK BRE4-… The external brake resistor (available for SK 2xxE, S 1 … S 3) is intended for energy feedback, e.g. in pulse drives or lifting gear. Here, it may be necessary to plan for the exact brake resistor required. For installation, an M20 screw connection with an adapter for M25 are supplied. The connecting wires for the brake resistor are fed through this into the connection unit.
2 Assembly and installation 2.3.4 Brake resistor, electrical data Internal Inverter type SK 2xxE-… Brake resistor size Max. continuous Energy Connecting consumption* cable or Resistance output / limit** (Pn) (Pmax) terminals Resistor type (IP54) 250…750-112-O 250…111-123-A SK BRI4-1-100-100 250…221-323-A SK BRI4-1-200-100 100 100 W / 25% 1.0 kWs Part No. 275272005 Silicon flex Size 1 200 100 W / 25% 1.0 kWs 2x 0.75mm 2 Part No. 275272008 550…221-340-A SK BRI4-1-400-100 approx.
SK 200E Manual for frequency inverters 2.4 Overvoltage filter SK CIF Size 1 … 3 The use of a suitable ("CSA-") overvoltage filter is mandatory (see also Section 1.5) in order to comply with cUL requirements. For 230V devices, operation of the frequency inverter with a suitable overvoltage filter is only permissible if a mains choke is used in addition. For further information about the overvoltage filter, please refer to the relevant data sheet. These data sheets can be downloaded at www.nord.com.
2 Assembly and installation 2.5 Wiring guidelines The frequency inverter has been developed for use in an industrial environment. In this environment, high levels of electromagnetic interference can influence the frequency inverter. In general, correct installation ensures safe and problem-free operation. To meet the limiting values of the EMC directives, the following instructions should be complied with.
SK 200E Manual for frequency inverters 2.6 Electrical Connection WARNING THE DEVICES MUST BE EARTHED. Safe operation of the devices requires that is installed and commissioned by qualified personnel in compliance with the instructions provided in this Manual. In particular, the general and regional installation and safety regulations for work on high voltage systems (e.g. VDE) must be complied with as must the regulations concerning correct use of tools and the use of personal protection equipment.
2 Assembly and installation Size 4: Handle or handle recess To replace the FI, proceed in the opposite sequence: 5. For sizes S 1 to 3 special attention must be paid to the correct contacting of the PE pins. These are located diagonally in 2 corners of the FI and the connection unit. 6. The FI can only be placed on the SK T14 in one orientation. 7. Evenly tighten the Allen screws in a cross-wise direction.
SK 200E Manual for frequency inverters 2.7 Electrical connection of the power unit L1 / L L2 / N L3 / PE All connection terminals are located in the connection unit of the frequency inverter. One terminal block is provided for the power connections and one for the control connections. The earthing connections (device earthing) are located on the base in the cast housing of the connection unit. For size 4 a contact is available on the power terminal block.
2 Assembly and installation 2.7.1 Mains connections (L1, L2, L3, EARTH) No special safety measures are required on the mains input side of the frequency inverter. It is advisable to use normal mains fuses (see technical data) and a main switch or circuit breaker. 115V devices may only be used with a 110…120V (L/N = L1/L2) single phase supply. 230V devices may be ordered either for single phase (...-123-, L/N = L1/L2) or three phase (...-323-, L1/L2/L3) operation.
SK 200E Manual for frequency inverters 2.7.2 Motor cable (U, V, W, earth) The motor cable may have a total length of up to 100m if this is a standard cable. If a screened motor cable is used, or if the cable is laid in a well earthed metal conduit, the total length should not exceed 20m. In order to comply with interference suppression class C2, a total length of 5m must not be exceeded. Note: Please also note Section 9.4 EMC limit value classes.
2 Assembly and installation 2.7.4 Electromechanical brake (only SK 2x5E) Connection of an electro-mechanical brake is possible for all SK 2x0 devices above S 4 and all SK 2x5E devices. For the control of the brake, the frequency inverter generates an output voltage on terminals 79 / 80 (MB+ / MB-) of the control terminal strip (SK 2x0E, S 4: separate terminal block, see illustration below), (see also Section 2.8.1 to 2.8.3). This is dependent on the supply voltage present in the frequency inverter.
SK 200E Manual for frequency inverters 2.7.5 Mains supply jumpers These jumpers are used to adapt the SK 2xxE to various types of network (e.g. IT network). As delivered, the jumpers are plugged in the "normal position" (CY=ON) and are to be used in a network which is earthed at the star point, with a neutral conductor for single phase devices! To adapt the SK 2xxE to an IT network, the capacitors C y must be disconnected from the PE.
2 Assembly and installation 2.8 Electrical connection of SK 2xxE control unit The control terminals are located on the inside of the frequency inverter connection unit. The assignment of the terminals varies according to the version (SK 200E, 205E, 210E, …, 235E). Connection terminals: Screw terminals, 3.5 mm slot-head screwdriver Connection cross-section: 0.2 ... 2.5mm , AWG 24-14, rigid or flexible, without cable sleeves (Size 4, terminal 79/80: also: … 4.0mm² rigid, AWG 24-12) Tightening torque: 0.
SK 200E Manual for frequency inverters 2.8.
2 Assembly and installation Size 4 FI type SK 200E SK 210E SK 220E SK 230E (SH) (ASI) (SH+ASI) Pin Labelling 1 43 24V (internal, output max. 200mA) 2 43 24V (internal, output max.
SK 200E Manual for frequency inverters 2.8.2 Details of the SK 2x0E control connections The frequency inverter generates its own control voltage and provides this to Terminal 43. With size 4 the connection terminals for an electro-mechanical brake are located on a 2-pole terminal block which is separate from the control terminal strip (Terminal 79/80, see Section 2.7.4).
2 Assembly and installation Terminal/ Function Name 38 TF+ Data Description / wiring suggestion Parameter {Factory setting} PTC resistor input For monitoring motor temperature with PTC 39 TF- 77 SYS H 78 SYS L PTC resistor input - A shielded cable must be used for separate mounting of the motor and the FI (note cable length).
SK 200E Manual for frequency inverters Terminal/ Function Name Data Description / wiring suggestion 24VDC … 30VDC Supply voltage connection for the FI control unit and the output DOUT1/2 Parameter {Factory setting} Additionally for size 4 44 24V 24V supply Input The frequency inverter (S IV) is equipped with its own mains unit, which if supplied with mains voltage (L1/N or L1/L2/L3) via terminal 43, provides a 24V DC control voltage.
2 Assembly and installation 2.8.3 Details of the SK 2x5E control connections Control voltage 24V external! Terminal 44. If the frequency inverter is not equipped with an optional mains unit it must be supplied with an external 24V voltage. For devices where the AS interface is used (SK 225E and SK 235E), the control voltage supply must be provided via the yellow AS interface cable.
SK 200E Manual for frequency inverters Terminal/ Function Name 77 SYS H Data Description / wiring suggestion {Factory setting} System bus + 78 SYS L System bus - 79 MB+ Brake control Internal FI system bus for Up to four SK 2xxE can be communication with optional operated on a single modules and other frequency system bus. inverters. Address = 32 / 34 / 36 / 38 For further details see Section 9.7.
2 Assembly and installation 2.8.4 Control connections for SK 2xxE communication Terminal/ Designation Function {Factory setting} Data Description / wiring suggestion Parameter all SK 2xxE, plug connector block RJ12, RS485/RS232 RX D P502 ...P513 +24V + 5V TX D GN D RS4 8 5 _B RS4 8 5 _A CAN _2 4 V CAN _G N D nc nc CAN _G N D 0V digital CAN _SH LD Termination resistor R=120 is fixed.
SK 200E Manual for frequency inverters 2.8.
2 Assembly and installation 2.9 Plug connectors The use of optionally available plug connectors for power and control connections not only makes it possible to replace the drive unit with almost no loss of time in case of servicing, but also minimises the danger of installation errors when connecting the device. The most common plug connector versions are summarised below. Possible mounting locations on the connection unit of the frequency inverter (SK TI4-…) are listed in Section 2.1.4. 2.9.
SK 200E Manual for frequency inverters Assembly Mounting of the plug connector to the connection unit off the frequency inverter (SK TI4-…) is usually only possible with a connection adapter (connection extension SK TIE4-HAN10E). Plug connector* Mat. No. Technical data plus SK TIE4-HAN10E (275274100) HAN 10E LA 2BUE 275135010 Add-on housing with 2-clamp lock, socket insert 10-pin.
2 Assembly and installation 2.9.2 Plug connectors for control connection Various M12 round plug connectors are available as flanged plugs or flanged sockets. The plug connectors are intended for installation in the connection units (SK TI4-…) from the frequency inverter (SK 2xxE-…) or technology units (SK TU4-…) and can be orientated as required. The protection class (IP67) of the plug connector only applies in the screwed state.
SK 200E Manual for frequency inverters System components Description Data Safe stop A-coded, 5-pin SK TIE4-M12-SH Part. No. 275274509 M12 flanged plug to connect a safety switching device PIN 1 PIN 2 PIN 3 PIN 4 PIN 5 n. c. n. c. GND SH +24V SH n. c. (blue) (black) Plastic body in yellow AS Interface A-coded, 5-pin PIN 1 PIN 2 PIN 3 PIN 4 PIN 5 SK TIE4-M12-ASI Part. No. 275274502 M12 flanged plug to connect an AS interface cable ASi+ (/+24V) n. c. ASi- (/GND) n. c. n. c.
2 Assembly and installation 2.10 ATEX Zone 22 for SK 2xxE General information With appropriate modification, the NORDAC SK 2xxE frequency inverter can be used in explosion hazard areas. For this it is important that all the safety information in the operating instructions is strictly complied with for the prevention of personal injury and material damage. This is essential to prevent injury and damage.
SK 200E Manual for frequency inverters 2.10.1 Modified SK 2xxE for compliance with Category 3D For the operation of an SK 2xxE in ATEX Zone 22 only a modified frequency inverter is permissible. This adaptation is only made at the NORD factory. In order to use frequency inverters in ATEX Zone 22, among other things, the diagnostic caps are replaced with aluminium / glass versions.
2 Assembly and installation Name Approved for ATEX Zone 22 3D Part Number Not approved for ATEX Zone 22 3D SK TU4-POT-123-B(-C) 275281110 / (275281160) x SK TU4-POT-140-B(-C) 275281111 / (275281161) x SK TU4-PBR-M12(-C) 275281200 / (275281250) x SK TU4-CAO-M12(-C) 275281201 / (275281251) x SK TU4-DEV-M12(-C) 275281202 / (275281252) x SK TU4-IOE-M12(-C) 275281206 / (275281206) x *Only SK 2x5E 2.10.2.
SK 200E Manual for frequency inverters 2.10.2.3 Hand-held Technology Units for ATEX Zone 22 3D All hand-held technology units are not approved for continuous use in the ATEX Zone 22 3D. The may therefore only be used during commissioning or for maintenance purposes, if it is ensured that no explosive dust atmosphere exists.
2 Assembly and installation 2.10.2.5 Other options M12 sockets and plugs for installation in the terminal box of the basic device or in technology units may only be used of they are approved for use in ATEX Zone 22 3D.
SK 200E Manual for frequency inverters 2.10.4 Commissioning information For Zone 22 the cable glands must at least comply with protection class IP 55. Unused openings must be closed with blank screw caps suitable for ATEX Zone 22 3D (minimum protection class IP 55). The motors are protected against overheating by means of the frequency inverter. This is carried out by the evaluation of the motor PTC by the frequency inverter.
2 Assembly and installation 2.10.
SK 200E Manual for frequency inverters 2.11 Outdoor installation Series SK 2xxE frequency inverters and technology units can be installed outdoors under the following conditions: IP66 version (See Special Measures, Section .1.7) UV-resistant blank screw caps and inspection windows. The UV-resistant blank screw caps and inspection windows are part of the ATEX Kit for the SK 2xxE. I.e. for the use of the ATEX option for IP66 ( Section 2.
3 Options 3 Options The SK 2xxE provides a series of optional expansion modules. These modules are preferably used for the production of the low voltage (24V control voltage) for the direct control or connection of the frequency inverter to a host field bus.
SK 200E Manual for frequency inverters 3.1 Overview of optional modules 3.1.1 Overview of internal customer units SK CU4-… Internal customer interfaces enable the expansion of the range of functions of SK 2xxE frequency inverters without changing the physical size. Either a field bus module, a mains unit or an I/O extension can be selected. The frequency inverter provides one slot for the fitting of an appropriate option.
3 Options Int. 24V mains unit 1~ 400V SK CU4-24V-140-B Part No. 275271109 Internal 24V mains unit for supply of the SK 2x5E, with a mains voltage of 1~ 380-500V, -20/+10%. Electronic brake rectifier SK CU4-MBR This option enables the direct control of an electromechanical holding brake by an SK 2x0E. Part. No. 275271010 Setpoint converter SK CU4-REL Part. No.
SK 200E Manual for frequency inverters 3.1.2 Overview of external technology units SK TU4-… External technology units enable the modular extension of the scope of SK 2xxE frequency inverter functions. Users have access to both communication modules and an internal mains unit or an I/O expansion and other modules. Bus modules with connection terminals or M12 system connectors are available as options.
3 Options This option enables connection of up to four SK 2xxE via EtherCAT®. Supported profiles: CoE Baud rate: up to 100 MBaud 8x digital inputs Low: 0-5V, High: 11-30V 2x digital outputs, 0/24V System bus This option enables connection of up to four SK 2xxE to the CANbus with the CANopen protocol. Protocol: DS301 / DS402 Baud rate: up to 1 MBit/s 4x digital inputs Low: 0-5V, High: 11-30V 2x digital outputs, 0/24V system bus EtherCAT module* SK TU4-ECT Part No. 275281117 (IP55) Part No.
SK 200E Manual for frequency inverters Mains Unit modules Mains Unit Module Description Data External 24V mains unit 1~ 230V ** SK TU4-24V-123-B Part No. 275281108 (IP55) External 24V mains unit to supply the SK 2xxE, using a 24V, ±10%, 420mA mains voltage of 230V 10V ref., ±0.2V, 5mA Part No. 275281158 (IP66) Analog input 0-10V External 24V mains unit 1~ 400V ** 500Ω burden resistor for evaluation of 0/4-20mA SK TU4-24V-140-B Part No.
3 Options 3.2 Installation of optional modules 3.2.1 Installation of internal customer units SK CU4-… WARNING Installations should only be made by qualified personnel, in strict compliance with the warning and safety information. Modules must not be inserted or removed unless the device is free of voltage. The slots can only be used for the intended modules. The customer unit SK CU4-…is not intended for installation at a location away from the frequency inverter.
SK 200E Manual for frequency inverters 3.2.2 Installation of external technology units SK TU4-… WARNING Installations should only be made by qualified personnel, in strict compliance with the warning and safety information. Modules must not be inserted or removed unless the device is free of voltage. The slots can only be used for the intended modules. Installation of the technology unit at a location away from the frequency inverter is possible with an additional wall-mounting kit SK TIE4-WMK-TU.
3 Options 3.2.2.3 Installing the SK TI4-TU-BUS on the SK 2xxE The screw connectors and seals required for installation are enclosed with the modules or are fitted to the intended locations. Installation of the technology unit on the SK 2xxE is to be carried out as follows: 1. Switch off the mains. 2. Remove the two M25 blank caps from the required side of the frequency inverter (right / left) 3. Removal of the PCB (with terminal bar) from the BUS adapter unit. 4.
SK 200E Manual for frequency inverters 3.3 Control connections and configuration The I/O and field bus option modules must be supplied with a control voltage of 24V DC (±20%). Wiring sleeves must be used for flexible cables. Name Data Rigid cable cross-section 0.14 … 2.5mm² Flexible cable cross-section 0.14 … 1.5mm² AWG standard AWG 26-14 Tightening torque (for screw terminals) 0.5 … 0.
3 Options 3.4 Details of internal Customer Units SK CU4-… 3.4.1 Mains Unit, SK CU4-24V-… The mains unit (only permissible for SK 2x5E version) is used to produce the 24V control voltage for the FI from the available mains voltage (115V/230V/380V/500V). With this, a separate external 24V control voltage is not required. With SK 2x0E models, a mains unit is integrated at the factory, so that no optional SK CU4-24V-… mains unit or no external 24V supply is required.
SK 200E Manual for frequency inverters Details of the control connections Terminal/ Function Data Description / wiring suggestion 24VDC ±10% Supply voltage (output) to supply an SK 2x5E or other module with 24V. Parameter Name 44 24V 24V supply - 40 44 40 11 14 GND/0V 24V GND/0V 10V REF AIN1+ GND Reference potential 24V supply 12 AGND/0V B1 40 DOUT GND/0V integrated short-circuit monitoring, limited overtemperature and overload monitoring GND Reference potential 10V ± 0.
3 Options Connection plan and parameterisation of SK xU4-24V-…, example 1/3~ 115/230/400V + PE L1 - L2/N - L3 L1 - L2/N 115/230/400V 115/230/400V 24V mains unit SK TU4-24V-... (+ SK TI4-TU-NET)* Frequency inverter SK 205E-.../SK 215E-... or SK CU4-24V-... Control terminal bar 24V= 44 40 . . 21 22 23 24 . . . Control terminal bar GND 44* 40 44* ... 11 14 12 B1 AGND R 0-10V L 10V= 0-100% Switch Potentiometer 10kOhm Control terminal bar Analog setpoint: 0(2) - 10V 44* 40 44* ...
SK 200E Manual for frequency inverters 3.4.2 Potentiometer Adapter, SK CU4-POT The digital signals R and L can be directly applied to the corresponding digital inputs 1 and 2 of the SK 2xxE. The potentiometer (0-10) can be evaluated via a 24V module or I/O extension and converted to proportional impulses (frequency). In addition, with the inverter versions SK 2x5E, an optional 24V module (SK xU4-24V-...) provides the possibility of converting analog setpoint values into proportional pulses (frequencies).
3 Options Connection diagram and parameterisation of SK CU4-POT, example SK 2x5E 1/3~ 115/230/400V + PE L1 - L2/N - L3 L1 - L2/N 115/230/400V 115/230/400V 24V mains unit SK CU4-24V-... Frequency inverter Control terminal bar SK 2x5E-... 44 40 . . 21 22 23 24 . . . 24V= (br) GND (bl) Control terminal bar 44 40 44 ...
SK 200E Manual for frequency inverters 3.4.3 SK CU4-IOE-, I/O extension The internal I/O units can record sensor and actuator signals. These can be used for a drive function or forwarded to a host bus system (e.g. Profibus or CANopen). • 2x digital inputs • 2x analog inputs • 1x analog output • Status LEDs: Module status, module error, Dig In 1, Dig.
3 Options 3.4.3.1 Details of the control connections Terminal/ Function Data Description / wiring suggestion 24V supply 24VDC ±20% (Module) ≈ 110mA protected against reverse polarity Parameter Name 44 40 C1 24V GND/0V DIN1 Reference potential for digital signals DIN2 Digital input 1 Low 0V ... 5V (I/O IO extension DIN1) High 15V ... 30V Digital input 2 (I/O IO extension DIN2) 77 78 40 Sys+ Sys- GND - Max. permissible current load: 2A Ri = 8.
SK 200E Manual for frequency inverters 3.4.3.2 Configuration The configuration of the system bus settings and the functions of the analog inputs and outputs is made via a 12-part DIP switch element. Both analog inputs are differential inputs. The input voltage is simultaneously measured in a unipolar and bipolar manner. The evaluation is unipolar or bipolar, according to the DIP switch setting, with or without offset, as a current or voltage input.
3 Options 3.4.3.3 Signal status LEDs The statuses shown by the LED can be read out with the aid of a parameterisation tool from Getriebebau NORD (NORD CON software, SimpleBox, ParameterBox) and of course via the information parameter (P173) "Module Status" (Section 6.3.2). Displays specific to the module The status of the Technology Unit or the system bus is indicated by the LEDs DS and DE. LED (green) DS Device State LED (red) DE Device Error Meaning ... slow flashing = 2Hz (0.
SK 200E Manual for frequency inverters I/O displays The status of the additional digital inputs on the I/O module SK CU4-IOE is indicated by the relevant LEDs. I/O channel Status display Meaning LED (green) 3.4.3.
3 Options 3.4.3.6 Assignment of functions The assignment of functions for the digital and analog inputs and outputs is made in the following parameters of the frequency inverter.
SK 200E Manual for frequency inverters 3.4.4 PROFIBUS DP, SK CU4-PBR Up to four connected frequency inverters can be managed by the internal PROFIBUS DP module (control, status messages, parameterisation and diagnosis). • Baud rate: max. 12 MBaud • Protocol: DPV 0 and DPV 1 • 2x digital inputs • Automatic detection: PPO type, baud rate • DIP switches for: addressing, bus termination • Status LEDs: Module status, module error, bus status, bus error, Dig. In 1, Dig.
3 Options Details of the control connections Terminal/ Function Data Description / wiring suggestion 24V supply 24VDC ±20% (module, field and system bus level) ≈ 90mA protected against reverse polarity Parameter Name 44 40 24V GND/0V C1 DIN1 Reference potential for digital signals DIN2 Digital input 1 Low 0V ... 5V (I/O PROFIBUS DP DIN1) High 15V ... 30V Digital input 2 (I/O PROFIBUS DP DIN2) 77 Sys H 78 40 Sys L GND/0V 44 24V - Max. permissible current load: 2A Ri = 8.
SK 200E Manual for frequency inverters 3.4.5 CANopen, SK CU4-CAO Up to four connected frequency inverters can be managed by the internal CANopen module via CANopen (control, status messages, parameterisation and diagnosis). • Baud rate: max. 1 MBaud • Protocol: DS301 and DSP 402 1 • 2x digital inputs • DIP switches for: addressing, bus termination, baud rate • Status LEDs: Module status, module error, bus status, bus error, Dig. In 1, Dig.
3 Options Details of the control connections Terminal/ Function Data Description / wiring suggestion 24V supply 24VDC ±20% (module, system bus level) ≈ 50mA protected against reverse polarity Parameter Name 44 40 24V GND/0V C1 DIN1 C2 DIN2 Reference potential for digital signals Low 0V ... 5V (I/O CANopen DIN1) High 15V ... 30V (I/O CANopen DIN2) 77 Sys H 78 40 Sys L GND/0V - Max.
SK 200E Manual for frequency inverters 3.4.6 DeviceNet, SK CU4-DEV Up to four connected frequency inverters can be managed by the internal DeviceNet module via DeviceNet (control, status messages, parameterisation and diagnosis). • Baud rate: Max. 500 kBaud • Protocol: AC-Drive and NORD-AC • 2x digital inputs • DIP switches for: addressing, baud rate • Status LEDs: Module status, module error, bus status, bus error, Dig. In 1, Dig.
3 Options Details of the control connections Terminal/ Function Data Description / wiring suggestion Parameter Name 44 24V 24V supply (module, system bus level) 40 GND/0V C1 DIN1 Reference potential for digital signals ≈ 50mA protected against reverse polarity Digital input 1 Low 0V ... 5V (I/O DeviceNet DIN1) C2 DIN2 24VDC ±20% Digital input 2 (I/O DeviceNet DIN2) High 15V ... 30V Ri = 8.
SK 200E Manual for frequency inverters 3.4.7 Electronic brake rectifier, SK CU4-MBR The electronic brake rectifier SK CU4-MBR is used to control electromechanical brakes with a coil voltage of 180V DC and 205V DC and sizes 5Nm to 150Nm via the frequency inverter (primarily SK 2x0E) or its accessories (SK xU4-IOE). Monitoring of the current in the brake coil is integrated into the SK CU4-MBR.
3 Options Control connection details Terminal/ Function Data Description / wiring suggestion Parameter Name 44 24V 24V supply - 24VDC ±25% 40 GND /0V C5 DIN GND Reference potential Digital input 50 … 500mA (according to load on the digital output) Current consumption with 30VDC: 13mA 24VDC: 10mA 15VDC: 5.5 mA Supply voltage connection for the module - Digital input for DC brake switching - Switching thresholds ON: > approx. 8.5V OFF: < approx. 7.
SK 200E Manual for frequency inverters 3.4.8 Setpoint converter, SK CU4-REL The analog inputs of SK 2x0 E series frequency inverters and the optional mains units SK xU4-24V can only process unipolar setpoint values referenced to GND (0/2 … 10V; 0/4 … 20mA). If a bipolar setpoint (-10V … + 10V)) is available, this must be converted to a 0 … 10V signal by means of an SK CU4-REL setpoint converter. Two coupling relays are integrated into the module.
3 Options Control connection details Terminal/ Function Data Description / wiring suggestion 24VDC ±25% Connection of the supply voltage for the module and the reference potential of the analog signals Parameter Name 44 24V 24V supply 112 AGND/0V Reference potential for analogue signals 20mA 111 10V REF +10V Reference voltage +10V, 5mA 114 AIN1 Analog input 1 116 AIN2 Analog input 2 117 AOUT1 Connection of reference voltage from frequency inverter The conversion of the analog signal
SK 200E Manual for frequency inverters 3.4.9 Direction selection switch and potentiometer SK TIE4-SWT and SK TIE4-POT The R and L digital signals of the direction selection switch SK TIE4-SWT can be applied directly to the corresponding digital inputs 1 and 2 of the SK 2xxE. The potentiometer (0-10V) SK TIE4-POT can be evaluated via the analog inputs of the frequency inverter (only SK 2x0E) or the I/O extension. In addition, with the inverter versions SK 2x5E, an optional 24V module (SK xU4-24V-...
3 Options 3.5 Details of external Technology Units SK TU4-… The technology units are divided into three different groups. The BUS group contains all the bus modules and the I/O extension. These are connected to the SK 2xxE via the system bus. The NET group contains the mains unit and the PotentiometerBox modules. These are each equipped with a 24V mains unit to supply the SK 2xxE and provide the possibility of analog signal processing. The third group includes other technology units, e.g.
SK 200E Manual for frequency inverters 3.5.1.1 SK T14-TU-BUS connections The precise connections of the 36 spring-loaded terminals depend on the Technology Unit used. Details can be found in the relevant sections for the Technology Units 3.5.1.2 SK TI4-TU-NET Connections The terminal block of the Adapter Unit SK TI4-TU-NET is divided into two potential levels.
3 Options Details of the control connections Terminal/ Function Data Description / wiring suggestion Parameter Name 43 VO/24V 24V supply 40 GND/0V Reference potential 24VDC ±10% 43 VO/24V 24V supply 40 GND/0V Reference potential 43 VO/24V 24V supply 40 GND/0V Reference potential 11 10V REF 14 AIN1+ max. 420mA (total) integrated short-circuit monitoring, limited overtemperature and overload monitoring - +10V reference voltage 10V ± 0.
SK 200E Manual for frequency inverters 3.5.1.3 Connections of the SK TI4-TU-MSW Connection of the incoming and outgoing mains cable (incl. PE) is made on the relevant terminal blocks as shown in the illustration. With single phase mains cables the conducting phase must be connected to L1 and the neutral conductor to L2.
3 Options 3.5.2 Mains unit, SK TU4-24V-… (only SK 2x5E) The mains unit is used to produce the 24V control voltage for SK 2x5E frequency inverters from the available mains voltage (115V/230V/380V/500V). With this, a separate external 24V control voltage is not necessary. An analog output is also available for the connection of a potentiometer. • Mains unit for 100-240V, SK TU4-24V-123-B • Mains unit for 380-500V, SK TU4-24V-140-B • +24V- output voltage • 1x analog input (e.g.
SK 200E Manual for frequency inverters 3.5.3 PotentiometerBox SK TU4-POT-… The PotentiometerBox SK TU4-POT enables simple motor speed and direction control via a series SK 2x5E frequency inverter. LEDs on the enable keys indicate the selected enable direction. In addition, with the integrated mains unit, the 24V control voltage for the FI is produced from the mains voltage (115V/230V/380V/500V). With this, a separate external 24V control voltage is not necessary.
3 Options 3.5.4 I/O Extension, SK TU4-IOE, ...-M12 The internal I/O units can record sensor and actuator signals. These can be used for a drive function or forwarded to a host bus system (e.g. Profibus or CANopen). Up to two I/O modules (also combinations: 1 x SK CU4-IOE and 1 x SK TU4-IOE) can be connected to an inverter (up to firmware version V1.0 R1 of the I/O extension and firmware version V1.1 R2 of the frequency inverter, only one I/O extension is possible for each frequency inverter.).
SK 200E Manual for frequency inverters Example for the connection of SK TU4-IOE to SK 205E SK 205E…-Connection unit (SK TI4…) SK TU4-IOE…-Connection unit (SK TI4-TU-BUS) Voltage Source 24V DC NOTE Looping of the 24V supply voltage (terminals 11/15) is in principle possible, however, a maximum current load of 3A for the SK TU4-IOE(-…) must not be exceeded! Only adjacent terminals (e.g.: 11/12) may be used for looping.
3 Options 3.5.4.1 Details of the control connections Terminal/ Function Data 10V reference voltage 10V ± 0.1V Description / wiring suggestion Parameter Potentiometer supply voltage - Name 1 +10V 2 3 5 4 6 AIN1+ AIN1- AIN2+ AIN2- Analog input 1 positive Version as differential input Analog input 1 Resolution 12Bit negative Accuracy: 0.
SK 200E Manual for frequency inverters Terminal/ Function Data Description / wiring suggestion Parameter GND Reference potential for digital signals As for terminal 15 Connection of supply voltage for module and 24V source for supply of the digital inputs (DIN1 to DIN4) - Name 21 GND 22 23 24V 24V supply (Module, system bus level) As for terminal 11 Digital input 2 (I/O IO extension DIN2) Low 0V ... 5V High 15V ... 30V Digital input 4 Ri = 8.
3 Options 3.5.4.3 Signal status LEDs The definition of the LED signals of the external I/O extension (SK TU4-IOE-…) corresponds to that for the internal I/O - extension SK CU4-IOE. The appropriate details are described in Section 3.4.3.3. Exception: The signal statuses of the digital inputs and outputs (DI … / DO …) are only visualised with the M12 version (SK TU4-IOE-M12) (See also Section 3.5.4 "Details of the M12 connections of the SK TU4-IOE-M12").
SK 200E Manual for frequency inverters 3.5.5 PROFIBUS DP, SK TU4-PBR, ...-M12 Up to four connected frequency inverters can be managed by the external PROFIBUS DP module (control, status messages, parameterisation and diagnosis). • Baud rate: max. 12 MBaud • Protocol: DPV 0 and DPV 1 • 4x digital inputs • 2x digital outputs • Automatic detection: PPO type, baud rate • DIP switches for: addressing, bus termination • Status LEDs: Module status, module error, bus status, bus error, Dig.
3 Options Connection example: SK TU4-PBR to SK 205E SK 205E…-Connection unit (SK TI4…) SK TU4-PBR…-Connection unit (SK TI4-TU-BUS) Voltage Source 24V DC PROFIBUS Subscriber PROFIBUS Subscriber X-1 X+1 NOTE Looping of the 24V supply voltage (terminals 11/15) is in principle possible, however, a maximum current load of 3A for the SK TU4-PBR(-…) must not be exceeded! Only adjacent terminals (e.g.: X5:11/12) may be used for looping.
SK 200E Manual for frequency inverters Details of the control connections Terminal/ Function Data 24V supply 24VDC ±20% (module, field and system bus level) ≈ 900mA protected against reverse polarity Description / wiring suggestion Parameter Connection for module supply voltage and 24V source for the digital inputs (DIN1 to DIN4) - Name 1 24V 2 Max.
3 Options Terminal/ Function Data Description / wiring suggestion GND Reference potential for digital signals As for terminal 15 24V supply As for terminal 1 (Module, field and system bus level) However, max. permissible current load: 3A Digital input 2 Low 0V ... 5V High 15V ... 30V Ri = 8.
SK 200E Manual for frequency inverters 3.5.6 CANopen, SK TU4-CAO, ...-M12 Up to four connected frequency inverters can be managed by the internal CANopen module via CANopen (control, status messages, parameterisation and diagnosis). • Baud rate: max. 1 MBaud • Protocol: DS301 and DSP 402 1 • 4x digital inputs • 2x digital outputs • DIP switches for: addressing, bus termination, baud rate • Status LEDs: Module status, module error, bus status, bus error, Dig.
3 Options Connection example: SK TU4-CAO to SK 205E SK 205E…-Connection unit (SK TI4…) SK TU4-CAO…-Connection unit (SK TI4-TU-BUS) Voltage Source Voltage Source 24V DC 24V DC CANopen Subscriber CANopen Subscriber X-1 X+1 NOTE Looping of the 24V supply voltage (terminals 11/15) is in principle possible, however, a maximum current load of 3A for the SK TU4-CAO(-…) must not be exceeded! Only adjacent terminals (e.g.: 11/12) may be used for looping.
SK 200E Manual for frequency inverters Details of the control connections Terminal/ Function Data 24V bus supply 24VDC -/+20% (field bus) ≈ 500mA protected against reverse polarity Description / wiring suggestion Parameter Supply voltage for the CANopen controller / field bus - Name 1 24V-B 2 Max.
3 Options Terminal/ Function Data Description / wiring suggestion Parameter GND Reference potential for digital signals As for terminal 15 - P174 Name 21 0V 22 23 24V (module, system bus level) As for terminal 11 Connection of supply voltage for module and 24V source for supply of the digital inputs (DIN1 to DIN4) Digital input 2 (I/O CANopen DIN2) Low 0V ... 5V High 15V ... 30V Ri = 8.
SK 200E Manual for frequency inverters 3.5.7 DeviceNet, SK TU4-DEV, ...-M12 Up to four connected frequency inverters can be managed by the internal DeviceNet module via DeviceNet (control, status messages, parameterisation and diagnosis). • Baud rate: Max. 500 kBaud • Protocol: AC-Drive and NORD-AC • 4x digital inputs • 2x digital outputs • DIP switches for: addressing, baud rate • Status LEDs: Module status, module error, bus status, bus error, Dig. • Additional LEDs, M12 version: Dig.
3 Options Connection example: SK TU4-DEV to SK 205E SK 205E…-Connection unit (SK TI4…) SK TU4-DEV…-Connection unit (SK TI4-TU-BUS) Voltage Source Voltage Source 24V DC 24V DC DeviceNet Subscriber DeviceNet Subscriber X-1 X+1 NOTE Looping of the 24V supply voltage (terminals 11/15) is in principle possible, however, a maximum current load of 3A for the SK TU4-DEV(-…) must not be exceeded! Only adjacent terminals (e.g.: 11/12) may be used for looping.
SK 200E Manual for frequency inverters Details of the control connections Terminal/ Function Data 24V bus supply 24VDC -/+20% (Field bus) ≈ 500mA protected against reverse polarity Description / wiring suggestion Parameter Supply voltage for the DeviceNet controller / field bus - Name 1 24V-B 2 Max.
3 Options Terminal/ Function Data Description / wiring suggestion Parameter GND Reference potential for digital signals As for terminal 15 - P174 Name 21 0V 22 23 24V (module, system bus level) As for terminal 11 Connection of supply voltage for module and 24V source for supply of the digital inputs (DIN1 to DIN4) Digital input 2 (I/O DeviceNet DIN2) Low 0V ... 5V High 15V ... 30V Ri = 8.
SK 200E Manual for frequency inverters 3.5.8 EtherCAT, SK TU4-ECT(-C) Up to 4 connected frequency inverters can be managed via EtherCAT® using the external EtherCAT module (control, status report, parameterisation and diagnosis). • Baud rate: max.
3 Options However, in this case it should be noted that there is an increased risk of introducing interference into the bus cables. Connection of up to 8 sensors and 2 actuators is made via the terminal bar.
SK 200E Manual for frequency inverters Control connection details Terminal/ Function Data Description / wiring suggestion Parameter Connection of supply voltage for module and 24V source for supply of the digital inputs (DIN1 to DIN8) - Name 1 24V 24V supply (Module and system bus level) 2 9 24VDC ±20% ≈ 100 mA reverse polarity protected Max. permissible current load: 500mA via DC/DC converter to Terminal 11.
3 Options Terminal/ Function Data Description / wiring suggestion GND Reference potential for digital signals As for terminal 15 24V supply As for terminal 1 (Module and system bus level) However, max. permissible current load: 3A Digital input 2 Low 0V ... 5V High 15V ... 30V Ri = 8.
SK 200E Manual for frequency inverters 3.5.9 Maintenance switch, SK TU4-MSW-… The maintenance switch can be looped into the mains supply cable of the frequency inverter in order to interrupt the voltage supply to a connected frequency inverter. The maintenance switch has a 3-pole design and can therefore be used for 1 - 3 phase AC supply networks up to 500V UNom. • Maintenance switch for AC supply networks 1~100-240V or.
4 Display and control 4 Displays and control of the SK 2xxE By the use of various modules for display, control and parameterisation, the NORDAC SK 2xxE can be easily adapted to a wide range of requirements. Alphanumeric display and control modules (Section 4.2) can be used for simple commissioning. For more complex tasks, connection to a PC system and the use of NORD CON parameterisation software is available. As supplied, without additional options, the diagnostic LEDs are externally visible.
SK 200E Manual for frequency inverters 4.1.
4 Display and control 4.1.
SK 200E Manual for frequency inverters Status LEDs LED Signal Name Colour Description Status Meaning DS dual Frequency inverter status off FI not on standby, red/green no mains and control voltage green on green flashing 0.
4 Display and control 4.2 Overview of external control devices All parameters can be easily accessed for reading or editing by means of an optional SimpleBox or ParameterBox. The changed parameter data are stored in the non-volatile EEPROM memory. This provides the possibility of transferring a dataset from one FI to another by plugging in the EEPROM. In addition, up to 5 complete frequency inverter data sets can be saved in the ParameterBox and then recalled.
SK 200E Manual for frequency inverters 4.2.1 SimpleBox, SK CSX-3H This option is used as a simple parameterisation, display and control tool for the SK 2xxE frequency inverter. Features 4-digit, 7-segment LED display Complete parameterisation of the frequency inverter. Direct control of a frequency inverter Displays the active parameter set during parameterisation and operation and the operating value set in P001.
4 Display and control Functions of the SimpleBox: Starting the frequency inverter. The frequency inverter is now enabled with the set jog frequency (P113). A preset minimum frequency (P104) may at least be provided. Parameter >Interface< P509 and P510 must = 0. Stopping the frequency inverter. The output frequency is reduced to the absolute minimum frequency (P505) and the frequency inverter shuts down. 4 permanently displayed underscores (_ _ _ _) indicate readiness for operation if there is no setpoint.
SK 200E Manual for frequency inverters Control with the SimpleBox The frequency inverter can only be controlled via the SimpleBox, if it has not previously been enabled via the control terminals or via a serial interface (P509 = 0 and P510 = 0). If the START key is pressed, the frequency inverter changes to the operating display (selection P001). The frequency inverter supplies 0Hz or a higher minimum frequency (P104) or jog frequency (P113) which has been set.
4 Display and control Parameterisation with the SimpleBox The parameterisation of the FI can be performed in various operating states. All parameters can always be changed online. Switching to the parameter mode occurs in different ways depending upon the operating states and the enabling source. 1.
SK 200E Manual for frequency inverters Menu structure with the SimpleBox Operating value display (or operational) following mains ON P7- - _ _ _ _ P0 - P0 0 1 P0 0 2 P6 - P5- P4- - P1- - P3- - P2- - P40 0 P10 0 P30 0 P20 0 P40 1 P10 1 P30 1 P20 1 P0 0 3 P48 3 P114 P327 P220 To change a parameter value, the OK key displayed. OK must be pressed when the relevant parameter number is Changes can then be made using the VALUE keys in the EEPROM and exit from the parameter.
4 Display and control 4.2.2 ParameterBox SK PAR-3H This option is for simple parameterisation and control of the frequency inverter, as well as the display of current operating settings and states. Up to 5 FI data sets can be stored and managed, stored and transferred with this device. This enables an efficient commissioning for serial applications.
SK 200E Manual for frequency inverters Functions of the ParameterBox LCD display Graphic-capable, backlit LCD display for displaying operational values and parameters for the connected frequency inverter and ParameterBox parameters. The menu levels and the individual menu items can be scrolled through with the SELECTION keys. The next higher level can be accessed by pressing the keys and at the same time. The contents of individual parameters can be altered with the VALUES keys.
4 Display and control Menu structure The menu structure consists of various levels, which are each arranged in a ring structure. The OK key moves the menu on to the next level. Pressing the SELECTION keys simultaneously moves the menu back one level. 1 205E 1.1kW / 400V Fi/Hz 45.
SK 200E Manual for frequency inverters Select language, brief description The following steps must be carried out to change the menu language used in the ParameterBox display. On switching on the ParameterBox for the first time, “German” or “English” will be offered for selection. The selection is made by pressing the selection keys (arrow R/L) and confirming with the OK key. In the following, “English” was selected on switching on for the first time.
4 Display and control Controlling the frequency inverter with the ParameterBox The frequency inverter can only be completely controlled via the ParameterBox if the parameter >Interface< (P509) is set to the >Control terminal or Keyboard< function (=0) (factory setting) and the inverter is not enabled via the control terminal.
SK 200E Manual for frequency inverters Screen layout during parameterisation If the setting of a parameter is changed, then the value flashes until it is confirmed with the OK key. In order to retain the default settings for the parameter being edited, both VALUE keys must be pressed simultaneously. Even in this case, the setting must be confirmed with the OK key in order for the change to be saved.
4 Display and control 4.2.3 ParameterBox parameters The following main functions are assigned to the menu groups : Menu group No.
SK 200E Manual for frequency inverters Parameter management Parameter Setting value / Description / Note P1201 Selection of the actual source object to be copied. Copy - Source In the selection list, only the frequency inverters and storage media detected during the bus scan are shown. Value range: FI, S1 ... S5 P1202 Selection of actual target object to copy. Copy - Target In the selection list, only the frequency inverters and storage media detected during the bus scan are shown.
4 Display and control Parameter Setting value / Description / Note P1305 The user can set up a password in this parameter. Set password If a value other than 0 has been entered in this parameter (default setting), then the settings of the ParameterBox or the parameters of the connected inverter cannot be altered. P1306 If the >Password< function is to be reset, the password selected in the >Set Password< parameter must be entered here.
SK 200E Manual for frequency inverters Display Cause Error Remedy 209_1 The ParameterBox is waiting for a response from the connected frequency inverter. The waiting time has elapsed without a response being received. INVERTER DOES NOT RESPOND Check the connection to the frequency inverter. The settings of the USS parameters for the frequency inverter have been changed during operation. Identification errors 220 UNKNOWN DEVICE Device ID not found.
4 Display and control Display Cause Error Remedy 231 Attempt to alter a parameter without a valid Box password being entered in parameter >Box Password< P 1306. INVALID PASSWORD 232 BUS SCAN ONLY WHEN IN MODE: ONLINE A bus scan (search for a connected frequency inverter) is only possible when in ONLINE mode.
SK 200E Manual for frequency inverters 5 Commissioning 5.1 Factory settings All frequency inverters supplied by Getriebebau NORD are pre-programmed with the default setting for standard applications with 4 pole standard motors (same voltage and power). For use with motors with other powers or number of poles, the data from the name plate of the motor must be input into the parameters P201...P207 under the menu item >Motor data<. NOTE: All motor data can be pre-set using the parameter P200.
5 Commissioning 5.2 Commissioning of the frequency inverter The SK 2xxE inverter series can be commissioned in various ways: a) For simple applications (e.g conveyor applications) by means of the DIP switches integrated into the frequency inverter (internal) and the (externally accessible) potentiometers (SK 2x5E only). In this configuration the plug-in EEPROM is not required. b) By adaptation of parameters using software via the ParameterBox (SK CSX-3H or SK PAR-3H) or NORD CON PC - supported software.
SK 200E Manual for frequency inverters 5.2.2 Configuration Changes to individual parameters are usually necessary for operation. However configuration can be carried out to a limited extent with the by means of the integrated 8-pole DIP switch (S1). NOTE Mixing of DIP switch configuration and (software) parameterisation should be avoided. 5.2.2.1 Parameterisation The use of a ParameterBox (SK CSX-3H / SK PAR) or NORD CON software is necessary to change the parameters.
5 Commissioning 5.2.2.2 DIP switch configuration Inverter (S1) The DIP switches provide the possibility of carrying out commissioning without additional control units. Further settings are made using the potentiometer on the top of the frequency inverter (P1 / P2, SK 2x5E only). As supplied, all DIP switches are at the "0" (Off) position, which corresponds to control via the digital inputs. The frequency setpoint is changed with P1 and P2 (P1 / P2, SK 2x5E only). No.
SK 200E Manual for frequency inverters Details of DIP switch S1: 5/4 and 3 Applies to devices SK 20xE, SK 21xE (without on board AS interface) DIP 5 4 3 off off off off on on off off off Dig 1 Dig 2 Dig 3 (P420 [01])* {01} "Enable R" (P420 [02])* {02} "Enable L" (P400 [01])* (P400 [02])* (P420 [03])* (P420 [05])* {04} “Fixed freq. 1" {04} “Fixed freq.
5 Commissioning 5.2.2.3 DIP switch configuration, analog input (only SK 2x0E) The analog inputs in the SK 2x0E are suitable for current and voltage setpoints. For correct processing of current setpoints (0-20mA / 4-20mA) the relevant DIP switch must be set for current signals ("ON"). Adjustment (to fail-safe signals in case of cable breaks (2-10V / 4-20mA) is made via parameters (P402) and (P403).
SK 200E Manual for frequency inverters 5.2.2.4 Details of the potentiometers P1 and P2 (SK 2x0E S 4 and SK 2x5E) The setpoint can be adjusted to a fixed value with the integrated potentiometer P1. Adjustment of the startup and braking ramps can be made via potentiometer P2. Potentiometer P2 P1 Potentiometer P1 (continuous) P2 (stepped) 0% P102/103 P105 - - - 10% 0.2s 10Hz 1 P102/103 P104 20% 0.3s 20Hz 2 0.2s 2Hz 30% 0.5s 30Hz 3 0.3s 5Hz 40% 0.7s 40Hz 4 0.5s 10Hz 50% 1.
5 Commissioning 5.2.3 Commissioning examples All SK 2xxE models can be operated as delivered. Standard motor data for a 4-pole standard asynchronous motor of the same power is parameterised. The PTC input must be bypassed, if a motor with PTC is not available. Parameter (P428) must be changed if an automatic startup with "Mains On" is required. 5.2.3.1 SK 2x0E - Minimal Configuration The frequency inverter provides all the necessary low voltages (24VDC / 10V DC).
SK 200E Manual for frequency inverters Minimal configuration with options In order to implement completely autonomous operation (i.e. independent of control cables etc.) a potentiometer unit (SK CU4-POT) is required. In combination with an integrated mains unit (SK CU4-…-24V) a solution can be implemented with an SK 2x5E which uses only one mains cable (1~ / 3~ according to the version), and a suitable speed and direction control can be ensured (See connection example below).
5 Commissioning Test operation The frequency inverter versions SK 2x0E in size 4 and SK 2x5E, may be commissioned without any auxiliary equipment for testing purposes. For this, after electrical connection has been made (See Sections 2.7 and 2.8) DIP switches S1: 1 to 5 (Section 5.2.2.2) of the frequency inverter must be set to the position "0" ("OFF") and the digital input DIN1 (Terminal 21) must be permanently wired to the 24 V control voltage.
SK 200E Manual for frequency inverters 5.3 KTY84-130 connection The current vector control of the SK 2xxE series can be further optimised by the use of a KTY84-130 temperature sensor (Rth(0°C)=500, Rth(100°C)=1000). By continuous measurement of the motor temperature, the highest precision of regulation by the frequency inverter and the associated optimum speed precision of the motor is achieved at all times.
5 Commissioning SK 2x0E Connection of a KTY-84 to either of the two analog inputs of the SK 2x0E is possible. In the following examples, analog input 2 of the frequency inverter is used. SK 2x0E * If necessary, also Terminal 40 Parameter settings (Analog input 2) The following parameters must be set for the function of the KTY84-130. 1. The motor data P201-P207 must be set according to the name plate. 2. The motor stator resistance P208 is determined at 20°C with P220 = 1. 3.
SK 200E Manual for frequency inverters 5.4 AS Interface 5.4.1 The bus system The Actuator -Sensor Interface (AS Interface) is a bus system for the lower field bus level. The transfer principle is a single-master system with cyclical polling. Up to 31 standard slaves (or 62 A/B slaves in the extended address range) can be operated on an unshielded two-wire cable up to 100m long and in any network structure (tree / linear / star). For the AS Interface, since the Complete Specification V2.
5 Commissioning 5.4.2 Features The SK 22xE and SK 23xE frequency inverter versions provide an integrated AS interface as standard. Therefore, these devices can be directly integrated into an AS interface network. Only the adaptation of various frequency inverter functions (Dip switches or parameters), addressing and the correct connection of the power supply, BUS, sensor and actuator cables needs to be carried out.
SK 200E Manual for frequency inverters 5.4.3 Bus structure and technology The AS interface network can be set up in any desired form. Linear, star, ring and tree structures are possible. An existing network can be expanded by further slaves at any time. Up to 31 standard slaves (i.e. a maximum of 124 binary sensors and 124 binary actuators) or 62 A/B slaves (i.e. a maximum of 248 binary sensors and 248 binary actuators) can be connected to an AS interface network or an AS interface master.
5 Commissioning 5.4.4 Commissioning of the AS Interface Connection Connection of the AS interface cable is made via terminals 85/85 of the terminal block and can optionally be made to an appropriately labelled M12 flange plug contact (yellow) Details of the connection terminals are explained in Section 2.8.2.
SK 200E Manual for frequency inverters Connection example: SK 225E/235E-Connection unit (SK TI4…) ASI Master + mains unit System bus connection, if necessary Mains connection (in Connection unit SK TI4…) Signal status LED / ASi-specific display – SK 2x0E S IV and SK 2x5E With these devices, the status of the ASi interface is indicated by the dual colour LED AS-i.
5 Commissioning Configuration The most important functions (function of the sensor / actuator signals via the ASi BUS and the "on board potentiometers" P1 and P2 (only SK 2x0E S 4 and SK 2x5E)) can be set on the frequency inverter via DIP4 and DIP 5 of the DIP switch block S1 (Section 5.2.2.2) Alternatively, the functions can also be assigned via the arrays [-01] … [-04] of parameters (P480) and (P481) (Section: 6).
SK 200E Manual for frequency inverters Method 1 With a normal addressing device (equipped with an M12 plug for connection to the AS-i bus) the AS-i can be integrated into the AS-i network via a suitable access point. The prerequisite for this is that the AS-i master can be switched off.
5 Commissioning 5.4.
SK 200E Manual for frequency inverters 6 Parameterisation The frequency inverter, field bus and I/O -extension modules each have their own logic systems. These can be adapted to customers' requirements by means of changeable parameters. The basic functions of the particular modues are factory-set, so that the units have basic functionalities on delivery. Limited adaptations of individual functions of the relevant devices can be implemented vie DIP switches.
6 Parameterisation Availability of the parameters Example illustration Due to certain configurations, the parameters are subject to certain conditions. The following tables (from Section 6.1 onwards) list all parameters together with the relevant information. Parameter {Factory setting} P000 [-01] ... [-04] 0.01 ... 9999 {0} Set value / Description / Note Device Supervisor Parameter set Operating para. disp.
SK 200E Manual for frequency inverters 6.1 Parameterisation of frequency inverter SK 2xxE Every frequency inverter is factory-set for a motor of the same power. All parameters can be adjusted "online". There are four parameter sets which can be switched over during operation. As delivered, all parameters are visible; however, some can be hidden with parameter P003. NOTE As there are dependencies between parameters, it is possible for invalid internal data and operating faults to be generated briefly.
6 Parameterisation Parameter list - inverter functions (selection) Parameter Description Factory setting Settings / functions (selection) P102 Start-up time Start-up time (acceleration ramp) is the time corresponding to the linear frequency rise from 0Hz to the set maximum frequency (P105). [2.00] Note: Values < 0.1 must be avoided P103 Braking time The braking time (braking ramp) is the time corresponding to the linear frequency reduction from the set maximum frequency (P105) to 0Hz. [2.
SK 200E Manual for frequency inverters Parameter list - inverter information (selection) Parameter P700 Actual operating status Description Display of current messages for the actual operating status of the frequency inverter such as errors, warnings or the cause of a switch-on block.
6 Parameterisation 6.1.1 Operating displays The abbreviations used are described in Section 9.13 “Abbreviations in this Manual". Parameter {Factory setting} P000 0.01 ... 9999 P001 Setting value / Description / Note Device Supervisor Parameter set Operating para. disp. (Operating parameter display) In the SimpleBox (SK CSX-3H) display, the parameter value online selected in P100 is displayed. Select of disp. value (Selection of display value) 0 ...
SK 200E Manual for frequency inverters Parameter {Factory setting} P002 Setting value / Description / Note Device Supervisor Display factor Parameter set S (Display factor) 0.01 ... 999.99 { 1.00 } The selected operating value in parameter P001 >Select of display< is multiplied with the scaling factor in P000 and displayed in >Operating parameter display<. It is therefore possible to display system-specific operating such as e.g.
6 Parameterisation 6.1.2 Basic parameters (Frequency inverter) Parameter {Factory setting} P100 0 ... 3 {0} Setting value / Description / Note Device Supervisor Parameter set Parameter set S (Parameter set) Selection of the parameters sets to be parameterised. 4 parameter sets are available. All parameter set-dependent parameters are identified by P. The selection of the operating parameter set is performed via a digital input or the Bus control. Switching can take place during operation (online).
SK 200E Manual for frequency inverters Parameter {Factory setting} P103 0 ... 320.00 s { 2.00 } Setting value / Description / Note Deceleration time (Deceleration time) Device Supervisor Parameter set P Deceleration time (braking ramp) is the time corresponding to the linear frequency reduction from the set maximum frequency (P105) to 0Hz. If an actual setpoint <100% is used, the deceleration time reduces accordingly. The deceleration time can be extended by certain circumstances, e.g.
6 Parameterisation Parameter {Factory setting} P106 0 ... 100 % {0} Setting value / Description / Note Device Supervisor Ramp smoothing Parameter set S (Ramp smoothing) P This parameter enables a smoothing of the acceleration and deceleration ramps. This is necessary for applications where gentle, but dynamic speed change is important. Ramp smoothing is carried out for every setpoint change.
SK 200E Manual for frequency inverters Parameter {Factory setting} P107 0 ... 2.50 s { 0.00 } Setting value / Description / Note Device Parameter set Supervisor Brake reaction time P (Brake reaction time) Electromagnetic brakes have a physically-dependent delayed reaction time when actuated. This can cause a dropping of the load for lifting applications, as the brake only takes over the load after a delay. This reaction time can be taken into account under parameter P107 (Braking control).
6 Parameterisation Parameter {Factory setting} P108 0 ... 13 {1} Setting value / Description / Note Disconnection mode (Disconnection mode) Device Supervisor S Parameter set P This parameter determines the manner in which the output frequency is reduced after "Blocking" (controller enable Low). 0 = Voltage disable:The output signal is switched off immediately. The FI no longer supplies an output frequency. In this case, the motor is braked only by mechanical friction.
SK 200E Manual for frequency inverters Parameter {Factory setting} P109 Setting value / Description / Note DC brake current (DC brake current) Device Supervisor S Parameter set P 0 ... 250 % Current setting for the functions of DC current braking (P108 = 3) and combined braking (P108 = 5). { 100 } The correct setting value depends on the mechanical load and the required deceleration time. A higher setting brings large loads to a standstill more quickly.
6 Parameterisation Parameter {Factory setting} Setting value / Description / Note Device Supervisor Jog frequency P113 S (Jog frequency) -400.0 ... 400.0 Hz { 0.0 } Parameter set P When using the SimpleBox or ParameterBox to control the FI, the jog frequency is the initial value following enabling. Alternatively, when control is via the control terminals, the jog frequency can be activated via one of the digital inputs.
SK 200E Manual for frequency inverters 6.1.3 Motor data / characteristic curve parameters Parameter {Factory setting} P200 0 ... 45 {0} Setting value / Description / Note Device Supervisor Motor list Parameter set P (Motor list) The factory settings for the motor data can be edited with this parameter. The factory setting in parameters P201...P209 is a 4-pole DS standard motor with the nominal FI power setting.
6 Parameterisation Parameter {Factory setting} P203 0.1 ... 300.0 A *** { } P204 100 ... 800 V {] P205 0.00 ... 150.00 kW *** { } P206 Setting value / Description / Note Device Supervisor Nominal current S (Nominal motor current) Parameter set P The nominal motor current is a decisive parameter for the current vector control. Nominal voltage S (Nominal motor voltage) P The >Nominal voltage< matches the mains voltage to the motor voltage.
SK 200E Manual for frequency inverters Parameter {Factory setting} P211 7 0 ... 150 % { 100 } Setting value / Description / Note Device Dynamic boost (Dynamic boost) Supervisor S Parameter set P The dynamic boost affects the torque generating current and is therefore a load-dependent parameter. The factory 100% setting is also sufficient for typical applications. Too high a value can lead to overcurrent in the FI. Under load therefore, the output voltage will be raised too sharply.
6 Parameterisation Parameter {Factory setting} P216 0.0 ... 10.0 s Setting value / Description / Note Time boost prectrl. (Time boost precontrol) Device Supervisor S Parameter set P This parameter is used for 3 functionalities { 0.0 } Time limit for the boost lead: Effective time for the increased starting current. Only with linear characteristic curve (P211 = 0% and P212 = 0%). Time limit for suppression of pulse switch-off (P537): enables start-up under heavy load.
SK 200E Manual for frequency inverters Parameter {Factory setting} P219 25 ... 100 % / 101 { 100 } Setting value / Description / Note Device Parameter set Supervisor Auto. magn. adjustment S (Automatic magnetisation adjustment) With this parameter, an automatic adjustment of the magnetic flux to the motor load can be made. P219 is a limiting value, to which the field in the motor can be reduced. As standard, the value is set to 100%, and therefore no reduction is possible.
6 Parameterisation Parameter {Factory setting} P220 Setting value / Description / Note Device Supervisor Parameter set Par.-identification (Parameter identification) ... up to 240s {0} P The motor data is automatically determined by the FI with this parameter. In most cases this leads to considerably better drive characteristics, as DC asynchronous motors are subject to manufacturing tolerances which are not documented on the name plate. The identification of all parameters takes some time.
SK 200E Manual for frequency inverters 6.1.4 Speed control In combination with an HTL incremental encoder, a closed speed control loop can be set up via digital inputs 2 and 3 of the FI. Alternatively, the incremental encoder signal can be used for other purposes. For this, the required function must be selected in parameter 325. In order for this parameter to be visible, the supervisor parameter P003 = 2/3 must be set. Parameter {Factory setting} P300 0 ...
6 Parameterisation Parameter {Factory setting} P311 Setting value / Description / Note Device Speed Ctrl I (Speed controller I) Supervisor Parameter set S P 0 ... 800 % / ms I-component of the encoder (Integration component). { 20 } The integration component of the controller completely eliminates any control deviation. The value indicates how large the setpoint change is per ms. Values that are too small cause the controller to slow down (reset time is too long). P312 0 ...
SK 200E Manual for frequency inverters Parameter {Factory setting} P318 0 ... 800 % { 150 } P319 Setting value / Description / Note P-Weak (Field weakening controller P) Device Supervisor S Parameter set P The field weakening controller reduces the field setpoint when the synchronous speed is exceeded. Generally, the field weakening controller has no function; for this reason, the field weakening controller only needs to be set if speeds are set above the nominal motor speed.
6 Parameterisation Parameter {Factory setting} P326 0.01 ... 100.00 { 1.00 } Setting value / Description / Note Device Supervisor Ratio encoder (Encoder transformation ratio) Parameter set S If the incremental encoder is not mounted directly onto the motor shaft, then the respectively correct transformation ratio of motor speed to encoder speed must be set. P326 Motor speed Encoder speed Only when P325 = 1, 2, 3 or 4, therefore not in Servo mode (motor speed control) P327 0 ...
SK 200E Manual for frequency inverters 6.1.5 Control clamps Parameter {Factory setting} P400 [-01] ... [-09] Setting value / Description / Note Fnct. setpoint inputs (Function of setpoint inputs) a) Device Supervisor SK 2x0E P b) 0 ... 33 SK 2x0E S 1 … 3 { [-01] = 1 } [-01] = Analog input 1, Function of analog input 1 integrated into the FI { [-02] = 0 } [-02] = Analog input 2, Function of analog input 2 integrated into the FI { [-03] = 0 } [-03] = Ext.
6 Parameterisation Parameter {Factory setting} Setting value / Description / Note Device Supervisor Parameter set The basic equipment of SK 2x5E devices does not include an analog input. An analog function can only be implemented by the use of options (Array [-01]...[-05] and [-08]…[-09]) or by use of the digital input 2 or 3 (Array [-06]...[-07]). The following settings are then possible: For standardisation of actual values: See also (Section 9.10). 0 = Off, the analog input has no function.
SK 200E Manual for frequency inverters Parameter {Factory setting} Setting value / Description / Note Device Parameter set Supervisor calculates the actual setpoint speed, so that neither of the two drives travels faster than the guide speed in the curve. 19 = Servo mode torque, in servo mode, the motor torque can be set or limited using this function. As of firmware version V1.3 this function is also without speed feedback, however it can be used at a lower quality.
6 Parameterisation Parameter {Factory setting} P401 [-01] ... [-06] Setting value / Description / Note Device Supervisor Mode analog in Parameter set S (Mode analog input) 0 ... 5 [-01] = Ext analog in 1, "External analog input 1", AIN1 of the first I/O extension (SK xU4-IOE). { all 0 } [-02] = Ext analog in 2, "External analog input 2", AIN2 of the first I/O extension (SK xU4-IOE). ... only with SK CU4-IOE or SK TU4-IOE [-03] = Ext. A.
SK 200E Manual for frequency inverters Parameter {Factory setting} Setting value / Description / Note Device Supervisor Parameter set NOTE: The SK xU4-IOE provides the frequency inverter with a value standardised to 0…100%. In addition, the frequency inverter also receives a bit, which confirms that the analog input signal is within the defined limits.
6 Parameterisation Parameter {Factory setting} P402 [-01] ... [-06] -50.00 ... 50.00 V Setting value / Description / Note Supervisor Adjust: 0% (Analog input adjustment: 0%) Parameter set S [-01] = Ext analog in 1, "External analog input 1", AIN1 of the first I/O extension (SK xU4-IOE). [-02] = Ext analog in 2, "External analog input 2", AIN2 of the first I/O extension (SK xU4-IOE). [-03] = Ext. A.
SK 200E Manual for frequency inverters Parameter Setting value / Description / Note {Factory setting} Device Parameter set Supervisor Standardisation to typical signals, such as 0(2)-10V or 0(4)-20mA is carried out via the DIP switch on the I/O extension module. In this case, additional adjustment of parameters (P402) and (P403) must not be carried out. P400 ... P403 Output frequency Output frequency P105 P105 positive positive P104 P104 z.B.
6 Parameterisation Parameter {Factory setting} Setting value / Description / Note Device Supervisor Nom. val. process ctrl. P412 (Nominal value process controller) S Parameter set P -10.0 ... 10.0 V Fixed specification of a setpoint for the process controller that will only occasionally be altered. { 5.0 } Only with P400 = 6 or 7 (PID process controller). Further technical details can be found in Section 9.2. PI control P comp. P413 (P-component of PI controller) S P 0.0 ... 400.
SK 200E Manual for frequency inverters Parameter {Factory setting} ... only with SK CU4-IOE or SK TU4-IOE Setting value / Description / Note Device Supervisor Parameter set Analog functions (max. load: 5mA analog): An analog (0 ...+10 Volt) voltage can be obtained from the control terminals (max. 5mA). Various functions are available, whereby: 0 Volt analog voltage always corresponds to 0% of the selected value.
6 Parameterisation Parameter {Factory setting} P419 [-01] [-02] Setting value / Description / Note Device Supervisor Standard. Analog out Parameter set S (Scaling of analog output) P -500 ... 500 % [-01] = First IOE, AOUT of the first I/O extension (SK xU4-IOE) { all 100 } [-02] = Second IOE, AOUT of the second I/O extension (SK xU4-IOE) ... only with SK CU4-IOE or SK TU4-IOE Using this parameter an adjustment can be made to the analog output for the selected operating zone.
SK 200E Manual for frequency inverters Value Function Description Signal 05 1 Fixed frequency 2 The frequency from P465 [02] is added to the actual setpoint value. High 06 1 Fixed frequency 3 The frequency from P465 [03] is added to the actual setpoint value. High 07 1 Fixed frequency 4 The frequency from P465 [04] is added to the actual setpoint value. High If several fixed frequencies are actuated simultaneously, then they are added with the correct sign.
6 Parameterisation Value Function 45 Description Signal 3-W-Ctrl. Start-Right 01 Flank “3-Wire-Control Start-Right” (Closing button) 46 3-W-Ctrl Start-Left “3-Wire-Control Start-Left” (Closing button) 49 3-Wire-Ctrl. Stop This control function provides an alternative to enable R/L (01/ 02), in which a permanently applied level is required. Here, only a control impulse is required to trigger the function. The control of the FI can therefore be performed entirely with buttons.
SK 200E Manual for frequency inverters Value Function 75 Description Signal Dig.out. 2 man/auto set "Set digital output 2 manually / au- As for function 67, however for digital output 2 (only SK 2x0E) tomatically" 76 Dig.out. 2 man.
6 Parameterisation Parameter {Factory setting} P434 [-01] [-02] Setting value / Description / Note Device Supervisor Parameter set Digital output function (Function of digital outputs) 0 ... 39 [-01] = Digital output 1, Digital output 1 of the frequency inverter {7} [-02] = Digital output 2, Digital output 2 of the frequency inverter (only SK 2x0E) Control terminals 1/40 (Section 2.8.2): The settings 3 to 5 and 11 work with 10% hysteresis, i.e.
SK 200E Manual for frequency inverters Parameter {Factory setting} Setting value / Description / Note Device Supervisor Parameter set 16 = Reference value Ain1, SK 2x0E: Setpoint AIN1 of the FI is compared with the value in (P435[-01 or -02]). SK 2x5E: Setpoint AIN1 of the 1st IO extension is compared with the value in (P435[-01]). 17 = Reference value Ain2, SK 2x0E: Setpoint AIN2 of the FI is compared with the value in (P435[-01 or -02]).
6 Parameterisation Parameter {Factory setting} Setting value / Description / Note Fixed frequency mode P464 (Fixed frequency mode) 0 ... 1 Device Supervisor Parameter set S This parameter determines the form in which fixed frequencies are to be processed. 0 = Add main set, "Addition to main setpoint": (Addition of the fixed frequency to the main setpoint) Fixed frequencies and the fixed frequency array are added to each other. I.e.
SK 200E Manual for frequency inverters Parameter Setting value / Description / Note {Factory setting} P475 [-01] ... [-04] -30.000 ... 30,000 s { 0.000 } Device Delay on/off switch Supervisor Parameter set S (Digital function switch on/off delay) Adjustable switch-on/switch-off delay for the digital inputs. Use as a switch-on filter or simple process control is possible.
6 Parameterisation Parameter {Factory setting} P481 [-01] ... [-10] 0 ... 39 Setting value / Description / Note Device Supervisor Parameter set Funct Bus I/O Out Bits (Function of Bus I/O Out Bits) The Bus I/O Out Bits are perceived as multi-function relay outputs. They can be set to the same functions (P434). { [-01] = 18 } These I/O bits can also be used in combination with the AS Interface (SK 22xE or SK 23xE) (Bit 0 … 3) or the I/O extension (SK xU4-IOE) (Bit 4 … 5 and flag 1 … 2).
SK 200E Manual for frequency inverters Parameter {Factory setting} P483 1 … 100 % [-01] ... [-10] Setting value / Description / Note Device ... Hyst. BusIO Out Bits Supervisor Parameter set S (Hysteresis of bus I/O Out bits) Difference between switch-on and switch-off point to prevent oscillation of the output signal.
6 Parameterisation 6.1.6 Extra functions Parameter {Factory setting} Parameter set Free input of a designation (name) for the device (max. 20 characters). With the the frequency inverter can be uniquely identified for processing with NordCon software or within a network. {0} { all 0 } Supervisor (Inverter name) A…Z (char) 0 ... 24 Device Inverter name P501 P502 Setting value / Description / Note [-01] ...
SK 200E Manual for frequency inverters Parameter {Factory setting} P503 0 ... 3 {0} Setting value / Description / Note Leading func. output (Master function output) Device Supervisor Parameter set S For master-slave applications this parameter specifies on which bus system the master transmits the control word and the master values (P502) for the slave.
6 Parameterisation Parameter {Factory setting} Setting value / Description / Note Device Supervisor Automatic acknowled. P506 S (Automatic error acknowledgement) 0 ... 7 Parameter set In addition to the manual error acknowledgement, an automatic acknowledgement can also be selected. {0} 0 = No automatic error acknowledgement 1= 1 ... 5 = Number of permissible automatic error acknowledgments within one mains-on cycle. After mains off and switch on again, the full amount is again available.
SK 200E Manual for frequency inverters Parameter {Factory setting} P511 0 ... 3 {3} P512 0 ... 30 {0} P513 -0.1 / 0.0 / 0.1 ... 100.0 s { 0.0 } Setting value / Description / Note Device Parameter set Supervisor USS baud rate S (USS baud rate) Setting of the transfer rate (transfer speed) via the RS485 interface. All bus participants must have the same baud rate setting. 0 = 4800 baud 2 = 19200 baud 1 = 9600 baud 3 = 38400 baud USS address (USS address) Setting the FI Bus address.
6 Parameterisation Parameter {Factory setting} P515 [-01] … ... [-03] Setting value / Description / Note Device CAN bus address (CAN bus address) Supervisor Parameter set S 0 ... 255dec Setting of the system bus address.
SK 200E Manual for frequency inverters Parameter {Factory setting} P520 0 ... 4 {0} Setting value / Description / Note Device Supervisor Flying start S (Flying start) Parameter set P This function is required to connect the FI to motors which are already rotating, e.g. in fan drives. Motor frequencies >100Hz are only picked up in speed controlled mode (Servo mode P300 = ON). 0 = Switched off, no flying start. 1 = Both directions, the FI looks for a speed in both directions.
6 Parameterisation Parameter {Factory setting} P525 [-01] ... [-03] Setting value / Description / Note Device Load control max (Load monitoring maximum value) 1 ... 400 % / 401 Selection of up to 3 auxiliary values: { all 401 } [-01] = Auxiliary value 1 [-02] = Auxiliary value 2 Supervisor S Parameter set P [-03] = Auxiliary value 3 From Firmware V1.3 Maximum load torque value. Setting of the upper limit of load monitoring. Up to 3 values can be specified.
SK 200E Manual for frequency inverters Parameter {Factory setting} P528 0.1 ... 320.0 s { 2.0 } From Firmware V1.3 P529 0 ... 3 {0} From Firmware V1.3 Setting value / Description / Note Load control delay (Load monitoring delay)) Device Supervisor S Parameter set P Parameter (P528) defines the delay time for which an error message ("E12.5") is suppressed on infringement of the defined monitoring range ((P525) … (P527)). A warning ("C12.5") is triggered after half of this time has elapsed.
6 Parameterisation Parameter {Factory setting} P525 … P529 From Firmware V1.3 Setting value / Description / Note Device Supervisor Parameter set Load monitoring With the load monitoring, a range can be specified within which the load torque may change depending on the output frequency. There are three auxiliary values for the maximum permissible torque and three auxiliary values for the minimum permissible torque. A frequency is assigned to each of these auxiliary values.
SK 200E Manual for frequency inverters Parameter {Factory setting} Setting value / Description / Note Device Supervisor Factor I2t Motor P533 Parameter set S 2 (Factor I t-Motor) 50 ... 150 % 2 The motor current for the I t motor monitoring P535 can be weighted with the parameter P533. Larger factors permit larger currents. { 100 } P534 [-01] [-02] 25 ... 400 % / 401 { all 401 } Torque disconn.
6 Parameterisation Parameter {Factory setting} P536 Setting value / Description / Note Device Current limit Supervisor Parameter set S (Current limit) 0.1 ... 2.0 / 2.1 (x FI current rating) The inverter output current is limited to the set value. If this limit value is reached, the inverter reduces the actual output frequency. { 1.5 } With the analog input function in P400 = 12/13, this limit value can also be varied and cause an error message (E12.4). 0.1 ... 2.
SK 200E Manual for frequency inverters Parameter {Factory setting} P540 0 ... 7 {0} Setting value / Description / Note Device Mode phase sequence (Rotation direction mode) Supervisor Parameter set S P For safety reasons this parameter can be used to prevent a rotation direction reversal and therefore the incorrect rotation direction. This function does not operate if the position control is active (P600 ≠ 0).
6 Parameterisation Parameter {Factory setting} Setting value / Description / Note Device Supervisor Set relays P541 S (Set digital output) 000 ... 1FF(hex) Parameter set This function provides the opportunity to control the relay and the digital outputs independently of the frequency inverter status. To do this, the relevant output must be set to the function "External control". This function can either be used manually or in combination with a bus control.
SK 200E Manual for frequency inverters Parameter {Factory setting} P543 [-01] ... [-03] Setting value / Description / Note Device Bus actual value 1… 3 S (Actual bus value 1) 0 ... 24 In this parameter the returned value on bus actuation can be selected. { [-01] = 1 } NOTE: P For further details, please refer to the relevant bus manual or the description for (P418). (Values from 0% … 100% correspond to 0000 hex … 4000hex) For standardisation of the actual values: See also (Section 9.10).
6 Parameterisation Parameter {Factory setting} P546 Setting value / Description / Note Device Supervisor Func. bus-set point 1 ... 3 Parameter set S (Function of bus - setpoint 1 ... 3) 0 ... 24 In this parameter, a function is assigned to the output setpoint during bus actuation. { [-01] = 1 } NOTE: { [-02] = 0 } { [-03] = 0 } P For further details, please refer to the relevant bus manual or the description for (P400).
SK 200E Manual for frequency inverters Parameter {Factory setting} P552 [-01] [-02] 0.0 / 0.1 … 100.0 ms { all 0.0 } Setting value / Description / Note Device Supervisor CAN master circle Parameter set S (CAN master cycle time) In this parameter, the cycle time for the system bus master mode and the CAN open encoder is set (see P503/514/515): [01] = CAN Master function, cycle time for system bus master functions [02] = CANopen Abs.
6 Parameterisation Parameter {Factory setting} Setting value / Description / Note Brake resistor type P557 (Brake resistor power) 0.00 ... 20.00 kW { 0.00 } Device Supervisor Parameter set S Continuous power (nominal power) of the resistor, to display the actual utilisation in P737. For a correctly calculated value, the correct value must be entered into P556 and P557.
SK 200E Manual for frequency inverters 6.1.7 Positioning The parameter group P600 is used to adjust the positioning control of the SK 2xxE. In order to make this parameter visible, the supervisor parameter P003 = 3 must be set. A detailed description of these parameters can be found in Manual BU 0210.(www.nord.
6 Parameterisation 6.1.8 Information (Frequency inverter) Parameter P700 Setting value / Description / Note [-01] ... [-03] 0.0 ... 21.4 Device Supervisor Parameter set Present operating status (Present operating status) Display of current messages for the actual operating status of the frequency inverter such as errors, wanings or the cause of a switch-on block. For details of messages see Section 7 [-01] = Current fault, shows the currently active (unacknowledged) error (Section 7.2.
SK 200E Manual for frequency inverters Parameter P705 Setting value / Description / Note [-01] ... [-05] 0 ... 1000 V DC Device Supervisor Dc.lnk volt. last er. Parameter set S (Last link circuit voltage fault 1...5) This parameter stores the link voltage that was being delivered at the time the error occurred. The values of the last 5 errors are stored. With the SimpleBox, the corresponding memory location 1...
6 Parameterisation Parameter P709 Setting value / Description / Note [-01] ... [-09] -100.0 ... 100.0 % Device (Voltage of analog inputs) Displays the measured analog input value. SK2x5E** [-01] = Analog input 1, function of analog [-01] = input 1 integrated into the FI [-02] = Analog input 2, function of analog input 2 integrated into the FI. [-02] = [-01] [-02] 0.0 ... 10.0 V P711 Potentiometer 1, Internal potentiometer P1 in the FI (Section 5.2.
SK 200E Manual for frequency inverters Parameter Setting value / Description / Note Supervisor Parameter set Running time P715 (Enablement time) 0.00 ... ___ h This parameter shows the time for which the FI was enabled and supplied current to the output. Current frequency P716 (Actual frequency) -400.0 ... 400.0 Hz Displays the actual output frequency. Current speed P717 (Actual rotation speed) -9999 ... 9999 rpm P718 Device [-01] ... [-03] -400.0 ... 400.
6 Parameterisation Parameter P727 -99.99 ... 99.99 kW P728 0 ... 1000 V P729 -400 ... 400 % P730 0 ... 250 % P731 0 ... 3 P732 0.0 ... 999.9 A Setting value / Description / Note 0.0 ... 999.9 A 0.0 ... 999.9 A Displays the actual calculated effective power of the motor. Basis for calculation is the motor data P201...P209 ... . Input voltage (Mains voltage) Displays the actual mains voltage at the FI input. Torque (Torque) Displays the actual calculated torque.
SK 200E Manual for frequency inverters Parameter Setting value / Description / Note Device Supervisor Parameter set Usage rate brakeres. P737 (Actual brake resistor usage rate) 0 ... 1000 % This parameter provides information about the actual degree of modulation of the brake chopper or the current utilisation of the braking resistor in generator mode. If parameters P556 and P557 are correctly set, the utilisation related to P557, the resistor power, is displayed.
6 Parameterisation Parameter P741 Setting value / Description / Note [-01] ... [-10] 0000 ... FFFF (hex) Device Parameter set Supervisor PZD bus out S (Process data bus out) This parameter provides information about the actual status word and the actual values that are transferred via the bus systems. For standardisation of actual values: See also (Section 9.10).
SK 200E Manual for frequency inverters Parameter P748 Setting value / Description / Note Device Supervisor Parameter set Status CANopen (CANopen status (system bus status)) 0000 ... FFFF (hex) Displays the system bus status. or Bit 0: 24V Bus supply voltage 0 ... 65535 (dec) Bit 1: CANbus in "Bus Warning" status Bit 2: CANbus in "Bus Off" status Bit 3: System bus → Bus module online (field bus module, e.g.: SK xU4-PBR) Bit 4: System bus → Additional module 1 online (I/O - module, e.g.
6 Parameterisation Parameter Setting value / Description / Note (Overcurrent statistics) 0 ... 9999 Stat. Overvoltage (Overvoltage statistics) 0 ... 9999 S S Number of overvoltage messages during the operating period P714. Stat. mains failure P752 (Mains failure statistics) 0 ... 9999 S Number of mains faults during the operating period P714. Stat. overtemperature P753 (Overheating statistics) 0 ... 9999 S Number of overtemperature faults during the operating period P714. Stat.
SK 200E Manual for frequency inverters 6.2 Parameterisation of I/O - extension SK xU4-IOE-… In order to access the parameters of the I/O extension, the parameterisation tool (ParameterBox, SimpleBox, NordCon) must be connected directly to the device. If the I/O extension is on an active system bus, it can be accessed with the ParameterBox SK PAR-3H or the NORD CON software as well as via another device (e.g. frequency inverter SK 2xxE).
6 Parameterisation Parameter {Factory setting} P161 0 ... 400.00 ms { [-01] = 100 } { [-02] = 100 } [-01] ... [-09] Setting value / Description / Note Device Supervisor Parameter set Filter time (Filter time) The analog and digital inputs are read cyclically every 250µs, this results in an input uncertainty of 0.25ms. In order to eliminate bounce and smooth the input signals, the information which is read in is passed through a filter routine.
SK 200E Manual for frequency inverters 6.2.2 Information (I/O - extension) Parameter P170 Setting value / Description / Note ... [-01] ... [-02] 0 ... 9999 Device Parameter set Supervisor Present errors (Present errors) Actual fault present. Further details in Section 7 "Operating status messages".
6 Parameterisation Parameter Setting value / Description / Note Device Supervisor Parameter set Module status P173 (Module status) 0 ...
SK 200E Manual for frequency inverters 6.3 Parameter overview, User settings (P) Depends on parameter set. These parameters can be set in various ways in the four parameter sets. [- xx] Array parameter. A parameter can be set in various sub-groups. S Supervisor parameter, visibility depends on P003. 6.3.1 Overview of frequency inverter parameters Parameter No. [Array] Name Factory setting Super visor Setting after commissioning P1 P2 P3 P4 OPERATING DISPLAYS (Section 6.1.
6 Parameterisation Parameter No. [Array] Factory setting Name Super visor Setting after commissioning P1 P2 P3 P4 MOTOR DATA / CHARACTERISTIC CURVE PARAMETERS (Section 6.1.3) P200 (P) Motor list P201 (P) Nominal frequency [Hz] 50.0 * S P202 (P) Nominal speed [rpm] 1385 * S P203 (P) Nominal current [A] 4.8 * S P204 (P) Nominal voltage [V] 230 * S P205 (P) Nominal power [kW] 1.10 * P206 (P) cos phi 0.78 * S P207 (P) Star Delta con.
SK 200E Manual for frequency inverters Parameter No. [Array] Name Factory setting Super visor P319 (P) Field weakening controller I [%/ms] 20 S P320 (P) Field weakening border [%] 100 S P321 (P) Speed control I brake off 0 S P325 Function encoder 0 S P326 Encoder ratio 1.00 S 0 (Off) S 0.0 S P327 (P) Speed slip error [rpm] P328 (P) Speed slip delay [s] Setting after commissioning P1 P2 P3 P4 CONTROL CLAMPS (Section 6.1.
6 Parameterisation Parameter No. [Array] Name Factory setting Super visor P402 [-04] Adjustment: 0% [V] Ext. analog input 2 2nd IOE 0.0 S P402 [-05] Adjustment: 0% [V] reserved 0.0 S P402 [-06] Adjustment: 0% [V] reserved 0.0 S P403 [-01] Adjustment: 100% [V] Ext. analog input 1 10.0 S P403 [-02] Adjustment: 100% [V] Ext. analog input 2 10.0 S P403 [-03] Adjustment: 100% [V] Ext. analog input 1 2nd IOE 10.0 S P403 [-04] Adjustment: 100% [V] Ext.
SK 200E Manual for frequency inverters 246 Parameter No. [Array] Name P428 Automatic starting Factory setting Super visor 0 (Off) S P434 [-01] Digital output 1 function 1 P434 [-02] Digital output 2 function 1 P435 [-01] Digital output 1 scaling [%] 100 P435 [-02] Digital output 2 scaling [%] 100 P436 [-01] Digital output 1 hysteresis [%] 10 S P436 [-02] Digital output 2 hysteresis [%] 10 S 10.
6 Parameterisation Parameter No.
SK 200E Manual for frequency inverters Parameter No. [Array] Name Factory setting Super visor P482 [-08] Norm. Bus IO Out Bits [%] Bus / 2nd IOE Dig Out2 100 P482 [-09] Norm. Bus IO Out Bits [%] Bit10 Bus status word 100 P482 [-10] Norm.
6 Parameterisation Parameter No. [Array] Name Factory setting Super visor P515 [-01] CAN address slave address 32(dec) S P515 [-02] CAN address broadcast slave address 32(dec) S P515 [-03] CAN address * Master address 32(dec) S Setting after commissioning P1 P2 P3 P4 *) System bus P516 (P) Skip frequency 1 [Hz] 0.0 S P517 (P) Skip frequency area 1 [Hz] 2.0 S P518 (P) Skip frequency 2 [Hz] 0.0 S P519 (P) Skip frequency area 2 [Hz] 2.
SK 200E Manual for frequency inverters Parameter No. [Array] Factory setting Super visor P543 [-03] (P) Actual bus value 3 9 S P546 [-01] (P) Function Bus setpoint 1 1 S P546 [-02] (P) Function Bus setpoint 2 0 S P546 [-03] (P) Function Bus setpoint 3 0 S P549 PotentiometerBox function 1 S P550 EEPROM copy order 0 Name P552 [-01] CAN master cycle [ms] CAN Master function 0 S P552 [-02] CAN master cycle [ms] CANopen abs.
6 Parameterisation Parameter No.
SK 200E Manual for frequency inverters Parameter No.
6 Parameterisation Parameter No. [Array] Superv Actual status and displayed values isor Name INFORMATION (6.1.8), read only P704 [-01…-05] Voltage, last error 1...5 S P705 [-01…-05] VDC last error 1...5 S P706 [-01…-05] P-set, last error 1...
SK 200E Manual for frequency inverters Parameter No. [Array] Superv Actual status and displayed values isor Name INFORMATION (6.1.8), read only P744 Configuration [hex] P747 Inverter voltage range 230/400V P748 Status CANopen * [hex] *) System bus 254 P749 Status DIP switches [hex] P750 Stat. overcurrent S P751 Stat. overvoltage S P752 Stat. mains failure S P753 Stat. overtemperature S P754 Stat. parameter loss S P755 Stat. system error S P756 Stat. timeout S P757 Stat.
6 Parameterisation 6.3.2 Parameter overview, I/O extension Parameter No. [Array] Factory setting Name Super visor Setting after commissioning BASIC PARAMETERS (Section 6.2.1) P150 Set relays 0 P152 Factory setting 0 P153 [-01] Min. system bus cycle time (SDO) 10 P153 [-02] Min. system bus cycle time (PDO) 5 P160 Set analog output -0.
SK 200E Manual for frequency inverters 6.4 Parameterisation adapter SK EPG-3H The SK EPG-3H parameterisation adapter is used as and interface between the plug-in EEPROM ("Memory © Module") and the parameterisation software for Windows PCs "NORD CON".
6 Parameterisation Step Description Comments 3 Connect the parameterisation adapter to the USB port (USB 2.0 or higher) of the PC using the enclosed cable. 4 Start NORD CON 5 Search for connected device 6 With an SK2xxE frequency inverter, the parameterisation adapter, which is ready for operation or the memory module are shown in the device overview with status "ready for switch-on". 6.1 To edit individual parameters: Open the parameterisation window (parameterise device) 6.
SK 200E Manual for frequency inverters ATTENTION Only plug in or disconnect the the memory module from parameterisation adapter if the connection to the PC has been disconnected! Otherwise the memory module and the SK EPG – 3H may be damaged. In addition, communication errors may occur during the operation of NORD CON. 6.4.3 Parameterisation adapter LEDs The operating status of the SK EPG-3H parameterisation adaptor is indicated by 2 frontmounted LEDs.
7 Status messages 7 Operating status messages In case of deviation from the normal operating state, frequency inverters and Technology Units generate a message according to the cause. A differentiation is made between warnings and error messages. If the frequency inverter is in a "switch-on block" status, the cause of this can also be displayed. Display of the Technology Unit messages is carried out via parameter (P170).
SK 200E Manual for frequency inverters 7.1 SimpleBox display The SimpleBox displays an error with its number and the prefix "E". In addition the actual error can be displayed in array element [-01] of parameter (P700). The last error messages are stored in parameter P701. Further information on the FI status when errors occur can be found in parameters P702 to P706 / P799.
7 Status messages Display in the SimpleBox Group Details in P700[-01] / P701 E003 3.0 Error Cause Text in the Parameter Box Remedy Overcurrent I²t lim "Overcurrent I²t limit" Rectifier I t limit has triggered, e.g. > 1.5 x In for 60s (Please also note P504) 2 Continuous overload at inverter output 3.1 Overcurrent, chopper "Overcurrent, chopper I2t" 2 I t limit for brake chopper has triggered (Attainment of 1.
SK 200E Manual for frequency inverters Display in the SimpleBox Group Details in P700[-01] / P701 E008 8.0 Error Cause Text in the Parameter Box Remedy Parameter lost (EEPROM - Maximum value exceeded) Error in EEPROM data Software version of the stored data set not compatible with the software version of the FI. NOTE: Faulty parameters are automatically reloaded (factory setting). EMC interferences (see also E020) 8.1 Inverter ID error EEPROM faulty 8.2 External EEPROM error -- 8.
7 Status messages Display in the SimpleBox Group Details in P700[-01] / P701 E010 10.0 Error Cause Text in the Parameter Box Remedy Bus timeout Data transfer is faulty. Check P513. (Telegram timeout / Bus off 24V int. CANbus) Check external bus connection. Check bus protocol program process. Check Bus master. Check 24V supply of internal CAN/CANopen Bus. Nodeguarding error (internal CANopen) Bus Off error (internal CANbus) 10.2 Bus timeout Option Telegram transfer is faulty.
SK 200E Manual for frequency inverters Display in the SimpleBox Error Cause Text in the Parameter Box Remedy 12.0 External watchdog The Watchdog function is selected at a digital input and the impulse at the corresponding digital input is not present for longer than the time set in parameter P460 >Watchdog time<. 12.1 Limit moto /Customer "Motor switch-off limit" The drive switch-off limit P534 [01] has triggered. Group Details in P700[-01] / P701 E012 Reduce load on motor.
7 Status messages Display in the SimpleBox Error Cause Text in the Parameter Box Remedy Group Details in P700[-01] / P701 E015 15.0 reserved E016 16.0 Motor phase error A motor phase is not connected. Check P539 Check motor connections 16.1 Magn Current Watch "Magnetisation current monitoring" Required excitation current not achieved at moment of switch-on. Check P539 Check motor connections E018 18.
SK 200E Manual for frequency inverters 7.2.2 Table of possible error messages in the I/O extension module Error number Error Cause Group Text in the Parameter Box Remedy EEPROM error EMC interference on the SPI bus Details in P170 E1000 1000 Module faulty 1030 System bus, Bus Off Check connections and cables Ensure 24V power supply Check Bus master.
7 Status messages 7.3 Table of possible warning messages Display in the SimpleBox Warning Cause Group Details in P700 [-02] Text in the Parameter Box Remedy C001 1.0 Inverter overtemp "Inverter overtemperature" (inverter heat sink) Warning from output stage module (static) Reduce ambient temperature <50°C or <40°C (see also Section 8 Technical data). Check control cabinet ventilation C002 2.
SK 200E Manual for frequency inverters Display in the SimpleBox Warning Cause Group Details in P700 [-02] Text in the Parameter Box Remedy C004 4.1 Overcurrent measurem "Overcurrent from overcurrent measurement" Warning: Pulse switch-off is active The limiting value for the activation of the pulse switch-off (P537) has been reached (only possible if P112 and P536 are switched off) FI is overloaded Check motor data (P201 … P209) C012 12.
7 Status messages 7.4 Table of possible reasons for the operating status "Switch-on block" The following table summarises the messages which are generated if the frequency inverter cannot be enabled, although no fault is present. Group Details in P700 [-03] I000 0.1 Reason Cause Text in the Parameter Box Remedy Volt blocked by IO "Voltage blocked by IO" With the function "Block voltage" the parameterised input (P420 / P480) is set to Low Set input to "High" Check signal cable (broken cable) 0.
SK 200E Manual for frequency inverters 8 Technical data 8.1 General data for frequency inverter series SK 2xxE Function Specification Output frequency 0.0 … 400.0Hz Pulse frequency 3.0 … 16.0kHz, standard setting = 6kHz Power reduction > 8kHz for 115/230V device, >6kHz for 400V device. Typical overload capacity 150% for 60s, 200% for 3.
8 Technical data 8.2 General data for mains/setpoint modules Mains/setpoint modules (SK CU4/TU4-24V-..., SK TU4-POT-...) Function Specification Analog setpoint input / PI input 0/2 ... 10V, 0/4 ... 20mA (if necessary with 500Ω burden), scalable Analog setpoint resolution 10 bit based on measurement range Analog output 0/2 ... 10V, 0/4 ... 20mA scalable Setpoint consistency Analog < 1% Digital < 0.
SK 200E Manual for frequency inverters 8.3 Electrical data for frequency inverter The following table lists the electrical data for SK2xxE series frequency inverters. The details based on measurement series for the operating modes are for orientation purposes and may deviate in practice.
8 Technical data 8.3.1 Electrical data 1~115V Size 1 Device type: SK 2x5E… Nominal motor power 230V (4-pole standard motor) 240V Input Permissible mains fuses (UL) -370-112-O -550-112-O -750-112-O 0.25 kW 0.37 kW 0.55 kW 0.75 kW ½ hp ¾ hp 1 hp 1 1 AC 110 … 120V, 10%, 47 … 63Hz 8.9 A 11 A 13.1 A 20.1 A 1~ FLA 8.9 A 10.8 A 13.1 A 20.1 A 1 AC slow-acting [A] 16 A 16 A 16 A 25 A RK5 or faster fuses, min.
SK 200E Manual for frequency inverters 8.3.2 Electrical data 1~230V Size 1 Device type: SK 2xxE… 230V Nominal motor power (4-pole standard motor) Input Permissible mains fuses (UL) -370-123-A -550-123-A -750-123-A -111-123-A 0.25 kW 0.37 kW 0.55 kW 0.75 kW 1.1 kW ½ hp ¾ hp 1 hp 1½ hp 1 1 AC 200 ... 240V, 10%, 47 ... 63 Hz 1~ rms 3.9 A 5.8 A 7.3 A 10.2 A 14.7 A 1~ FLA 3.9 A 5.8 A 7.3 A 10.1 A 14.
8 Technical data 8.3.3 Electrical data 3~230V Size 1 SK 2xxE… Device type: 230V Nominal motor power (4-pole standard motor) -370-323-A -550-323-A -750-323-A -111-323-A 0.25 kW 0.37 kW 0.55 kW 0.75 kW 1.1 kW ½ hp ¾ hp 1 hp 1½ hp 1 240V 3 AC 200 ... 240V, 10%, 47 ... 63 Hz 3~ rms 1.4 A 1.9 A 2.6 A 3.5 A 5.1 A 3~ FLA 1.4 A 1.9 A 2.6 A 3.5 A 5.1 A 1 AC slow-acting [A] 10 A 10 A 10 A 10 A 16 A RK5 or faster fuses, min 230V 5.0 A 5.
SK 200E Manual for frequency inverters Size 2 Device type: SK 2xxE… Size 3 -151-323-A -221-323-A -301-323-A -401-323-A Nominal motor power 230V 1.5 kW 2.2 kW 3.0 kW 4.0 kW (4-pole standard motor) 240V 2 hp 3 hp 4 hp 5 hp 3~ rms 6.6 A 9.1 A 11.8 A 15.1 A 3~ FLA 6.6 A 9.1 A 11.7 A 14.9 A 1 AC slow-acting [A] 16 A 20 A 20 A 25 A RK5 or faster fuses, min.
8 Technical data Size 4 Device type: SK 2x0E… -551-323-A -751-323-A -112-323-A Nominal motor power 230V 5.5 kW 7.5 kW 11.0 kW (4-pole standard motor) 240V 7½ hp 10 hp 15 hp 3~ rms 23.5 A 29.5 A 40.5 A 3~ FLA 22.5 A 28.5 A 39.0 A 1 AC slow-acting [A] 35 A 50 A 50 A RK5 or faster fuses, min. 230V 30 A 40 A 60 A FRS-R-30 FRS-R-40 FRS-R-60 30 A 40 A 60 A Input Typical input current at 230V Rec. mains fuse Permissible mains fuses (UL) 3 AC 200 ... 240V, 10%, 47 ...
SK 200E Manual for frequency inverters 8.3.4 Electrical data 3~400V Size 1 SK 2xxE… Device type: -550-340-A -750-340-A -111-340-A -151-340-A -221-340-A Nominal motor power 400V 0.55 kW 0.75 kW 1.1 kW 1.5 kW 2.2 kW (4-pole standard motor) 480V ¾ hp 1 hp 1½ hp 2 hp 3 hp 3~ 400V Mains voltage 3~ rms 1.6 A 2.2 A 2.9 A 3.7 A 5.2 A 3~ FLA 1.4 A 2.0 A 2.7 A 3.4 A 4.7 A 1 AC slow-acting [A] 10 A 10 A 10 A 10 A 10 A RK5 or faster fuses, min 230V/400V 5.0 A 5.
8 Technical data Size 2 Device type: SK 2xxE… Size 3 -301-340-A -401-340-A -551-340-A -751-340-A Nominal motor power 400V 3.0 kW 4.0 kW 5.5 kW 7.5 kW (4-pole standard motor) 480V 4 hp 5 hp 7½ hp 10 hp 3~ 400V Mains voltage 3~ rms 7.0 A 8.9 A 11.7 A 15.0 A 3~ FLA 6.3 A 8.0 A 10.3 A 13.
SK 200E Manual for frequency inverters Size 4 Device type: SK 2x0E… -112-340-A -152-340-A -182-340-A -222-340-A Nominal motor power 400V 11.0 kW 15.0 kW 18.0 kW 22.0 kW (4-pole standard motor) 480V 15 hp 20 hp 25 hp 30 hp 3~ 400V Mains voltage 3~ rms 23.6 A 32.0 A 40.5 A 46.5 A 3~ FLA 20.5 A 28.0 A 35.5 A 42.
9 Additional Information 9 Additional information 9.
SK 200E Manual for frequency inverters 9.2 Process controller The process controller is a PI controller, with which it is possible to limit the controller output. In addition, the output is standardised to a percentage of a master setpoint value. This provides the possibility of controlling an upstream drive unit with the master setpoint value and adjusting it with the PI controller. Ramp time PI setpoint P416 Master setpoint value a) Analog input 1 (P400[-03]=2) Min.
9 Additional Information 9.2.2 Process controller parameter settings (Example: Setpoint frequency: 50 Hz, control limits: +/- 25%) P105 (Maximum frequency) [Hz] Setpointfr q.Hz P415% 100% : Setpointfr q. Hz Example: 50 Hz 50 Hz 25% 62,5Hz 100% P400 [-01] (Funct.
SK 200E Manual for frequency inverters 9.3 Electromagnetic compatibility As of July 2007, all electrical equipment which has an intrinsic, independent function and which is sold as an individual unit for end users, must comply with Directive 2004/108/EEC (formerly Directive EEC/89/336).. There are three different ways for manufacturers to display compliance with this directive: 1.
9 Additional Information 9.4 EMC limit value classes Please note that these limit value classes are only reached if the standard pulse frequency (6kHz) is being used and the length of the shielded motor cable does not exceed the permissible limits. In addition, it is essential to use wiring suitable for EMC. The motor cable shielding must be applied on both sides (frequency inverter shield angle and the metal motor terminal box). Jumper position Device type Max.
SK 200E Manual for frequency inverters 9.5 Reduced output power The SK 2xxE frequency inverter series is designed to handle certain overload situations. For example, 1.5x overcurrent can be used for 60 sec. For approx. 3.5 sec a 2x overcurrent is possible.
9 Additional Information 9.5.2 Reduced overcurrent due to time The possible overload capacity changes depending on the duration of an overload. Several values are cited in this table. If one of these limiting values is reached, the frequency inverter must have sufficient time (with low utilisation or without load) in order to regenerate itself. If operated repeatedly in the overload region at short intervals, the limiting values stated in the tables are reduced.
SK 200E Manual for frequency inverters 9.5.3 Reduced overcurrent due to output frequency To protect the power unit at low output frequencies (<4.5Hz) a monitoring system is provided, with which the temperature of the IGBTs (integrated gate bipolar transistor) due to high current is determined. In order to prevent current being taken off above the limit shown in the diagram, a pulse switch-off (P537) with a variable limit is introduced. At a standstill, with 6kHz pulse frequency, current above 1.
9 Additional Information 9.5.4 Reduced output current due to mains voltage The devices are designed with thermal characteristics according to the rated output currents. Accordingly, for lower mains voltages, higher currents cannot be taken off in order to maintain the stated power constant. For mains voltages above 400v there is a reduction of the permissible continuous output current, which is inversely proportional to the mains voltage, in order to compensate for the increased switching losses.
SK 200E Manual for frequency inverters 9.6 Operation with FI circuit breakers With SK 2xxE frequency inverters (except 115V devices), leakage currents of > 40mA are to be expected if the mains filter is active. If possible, an FI circuit breaker for the protection of personnel should not be used. If the frequency inverter is to be used with an FI circuit breaker for the protection of personnel, the leakage currents to earth must be reduced to 10 - 20 mA by means of jumpers.
9 Additional Information Addressing If several frequency inverters are connected to a system bus, these devices must be assigned with unique addresses. For preference, this is done via the DIP switch S1 on the underside of the SK2xxE (Section 5.2.2.2). For the use of CANopen absolute encoders, the encoders must be assigned to the relevant FI via the node ID.
SK 200E Manual for frequency inverters 9.8 Energy efficiency NORD frequency inverters have a low power consumption and are therefore highly efficient. In addition, by means of "Automatic flux adaptation" (parameter (P219)), the SK 2xxE provides a facility for improving the energy efficiency of the entire drive unit (especially in applications with partial loads).
9 Additional Information 9.9 Motor data - characteristic curves 9.9.1 50Hz characteristic curve ( Adjustment range 01:10:00) a) 115V / 230V frequency inverter For 50Hz operation, the motor can be used at the rated torque up to its rating point of 50Hz/230V. In spite of this, operation above 50Hz is possible, however the output torque reduces in a non-linear manner (see following diagram).
SK 200E Manual for frequency inverters b) 400V frequency inverter For 50Hz operation, the motor can be used at the rated torque up to its rating point of 50Hz/400V. In spite of this, operation above 50Hz is possible, however the output torque reduces in a non-linear manner (see following diagram). Above the rating point the motor enters its field reduction range, as with an increase of frequency above 50Hz, the voltage can not be increased above 400V. Due to the mains voltage, only max. 400V are available.
9 Additional Information 9.9.2 87Hz characteristic curve (only 400V devices) ( Adjustment range 01:17:00) The 87Hz characteristic curve is an extension of the speed adjustment range with a constant rated torque for the motor.
SK 200E Manual for frequency inverters 9.9.3 100Hz characteristic curve (only 400V devices) ( Adjustment range 1:20) For a large speed adjustment range up to a ratio of 1:20 an operating point of 100Hz/400V may be selected. For this, special motor data is necessary (see below), which deviates from the normal 50Hz data. Care must be taken that a constant torque is produced over the entire adjustment range, however this is smaller than the rated torque for 50Hz operation.
9 Additional Information 9.10 Standardisation of setpoint/actual values The following table contains details for the standardisation of typical setpoint and actual values. This information relates to the parameters (P400), (P418), (P543), (P546), (P740) or (P741).
SK 200E Manual for frequency inverters 9.11 Definition of setpoint and actual value processing (frequencies) The frequencies used in parameters (P502) and (P543) are processed in various ways according the following table. II III Setpoint source and setpoint selection Signal processing and ramp Control and motor model (determination of slip) Output to ...
9 Additional Information 9.12 Maintenance and servicing information 9.12.1 Maintenance Instructions In normal use, NORDAC SK 2xxE frequency inverters are maintenance free. Please note the "General data" in Section 8.1. Dusty environments If the frequency converter is being used in a dusty environment, the cooling-vane surfaces should be regularly cleaned with compressed air. If air intake filters have been built into the control cabinet, then these should also be regularly cleaned or replaced.
SK 200E Manual for frequency inverters 9.12.2 Repair information If you contact our technical support, please have the precise device type (name plate/display), accessories and/or options, the software version used (P707) and the series number (name plate) at hand. Repairs The device must be sent to the following address if it needs repairing: NORD Electronic DRIVESYSTEMS GmbH Tjüchkampstraße 37 26605 Aurich, Germany For queries about repairs, please contact: Getriebebau NORD GmbH & Co. KG Tel.
9 Additional Information 9.13 Abbreviations in this manual AS (AS1) AS interface LED ....... Light-emitting diode AIN ...... Analog input P1 .......... Potentiometer 1 (not SK 2x0E S 1 … 3) AOUT .. Analog output P2 .......... Potentiometer 2 (not SK 2x0E S 1 … 3) BW ...... Brake resistor S ........... Supervisor Parameter, P003 DI (DIN) Digital input S1 .......... DIP switch FI (8-pole) DO (DOUT) Digital output S2 .......... DIP switch FI (1-pole) EEPROM Non-volatile memory SH .........
SK 200E Manual for frequency inverters 10 Keyword index 3 3-Wire-Control........................... 203 Array parameters .... 135, 142, 169, 170 Absolute minimum frequency (P505) ................................... 212 Acceleration time (P102) .......... 175 Accessories.................................12 Actual cos phi (P725) ....................... 232 Current (P719) ...................... 232 Field current (P721) .............. 232 Frequency (P716) ................. 232 Mains current (P760) .........
10 Keyword index Current Electrical data Last error (P703) .................. 229 1~115V ................................. 273 Phase U (P732).................... 233 1~230V ................................. 274 Phase V (P733) .................... 233 3~230V ................................. 275 Phase W (P734) ................... 233 3~400V ................................. 278 Current limit (P536) .................. 221 Electromechanical brake 43, 94, 96 Current vector control ...............
SK 200E Manual for frequency inverters IT network .............................41, 44 J Maximum frequency auxiliary setpoint (P411) ..................... 198 Mechanical power (P727)......... 233 Jog frequency (P113)................ 181 Memory Module 127, 225, 227, 256 Jumper ........................................ 44 Menu group .............................. 170 Messages ......................... 127, 259 K KTY84 ....................................... 158 L Language selection ...................
10 Keyword index Posicon .................................... 228 Selection display (P001) ........... 173 Speed of rotation ...................... 233 Positioning................................ 228 Send broadcast (P162)............. 239 Speed slip delay (P328)............ 191 Potentiometer ............................. 45 Service ..................................... 299 Speed slip error (P327)............. 191 Potentiometers P1 and P2 ...... 129, 153, 154 Servo mode (P300) ..................
SK 200E Manual for frequency inverters Time boost precontrol (P216).... 185 Usage rate Analog input (P709) .............. 231 Brake resistor (P737) ........... 234 Analog output (P710)............ 231 Current controller I (P313)..... 189 Motor (P738) ........................ 234 Last error (P704) .................. 229 Current controller P (P312) ... 189 USB device driver .................... 256 Current limit (P112) ............... 180 USB driver ................................
10 Keyword index BU 0200 GB-4411 307
308 BU 0200 GB-4411 Part No.
Technical Information / Datasheet Pos : 4 /T ec hnis che Infor mationen/Sons tige D okumente/Ergänzung z um Handbuc h AS-i [SK 225E, SK235E] @ 4\mod_1393488915264_388.doc x @ 120671 @ 5 @ 1 Supplement to Manual Subject: AS Interface – Risk of short circuit Affected products and documents Product Series Document Issue Section Page SK 225E BU 0200 4411 5.4 160 SK 235E BU 0200 4411 5.
Documentation, Supplement to BU 0200 – AS-i, SK 225E, SK 235E Connection example: Variant 2 – Use of the digital output DO1 (Terminal 1) as a "power source". The digital output of the frequency inverter is protected against short circuit. A short circuit in a peripheral device connected to this output will therefore not cause damage to the frequency inverter. Therefore it is recommended that any actuators are supplied via the digital output.
Technical Information / Datasheet Pos : 5 /T ec hnis che Infor mationen/Sons tige D okumente/Ergänzung z um Handbuc h DIP-Schalter COPY [SK xxE] @ 4\mod_1393501058719_388.doc x @ 120697 @ 55 @ 1 Supplement to Manual Subject: DIP switches (S1) - Changes to function Affected products and documents Product Series Document Issue Section Page SK 2xxE BU 0200 4411 5.2.2.2 151 Change All devices of the SK 2xxE series are equipped with an 8-pole DIP switch.
Documentation – DIP-Switch (S1), SK2xxE NOTICE Incompatibility Due to the function change, there is an incompatibility with devices manufactured at an earlier date. This must be taken into account for changes to the DIP switch positions. The contents of Page 151 of BU0200 - Version 4411 will be replaced with the following content: 5.2.2.2 Inverter DIP switch configuration (S1) The DIP switches provide the possibility of carrying out commissioning without additional control units.
Documentation – DIP-Switch (S1), SK2xxE Explanation of the changed function: The frequency inverter is equipped with an internal EEPROM and a plug-in EEPROM ("Memory Module") which operates in parallel to this for the storage and management of parameter data. The data from the device are managed in parallel on both devices, so that a safe and rapid exchange of parameter settings in the device is possible for commissioning or in case of service.