6.1.1 Operating displays
The abbreviations used are described in Section 9.13 
Parameter
{Factory setting}
Setting value / Description / Note
Device
Supervisor
Parameter
set
P000
Operating para. disp.
(Operating parameter display)
0.01 ... 9999
In the SimpleBox (SK CSX-3H) display, the parameter value online selected in P100 is
displayed.
P001
Select of disp. value
(Selection of display value)
0 ... 63
{ 0 }
0 = Actual frequency [Hz]: the current output frequency being supplied by the FI.
1 = Speed [1/min]: the current rotation speed as calculated by the FI.
2 = Setpoint frequency [Hz]: the output frequency equivalent to the actual setpoint. This
need not match the actual output frequency.
3 = Current [A]: the actual output current measured by the FI.
4 = Torque current [A]: the torque developing output current of the FI.
5 = Voltage [Vac]: the actual alternating voltage being output by the FI.
6 = DC link voltage [V DC], "Link circuit voltage": is the internal DC voltage of the FI.
Amongst other things, this depends on the level of the mains voltage.
7 = cos phi, "cos ": is the actual calculated value of the power factor.
8 = Apparent power [kVA]: the current apparent power calculated by the FI.
9 = Real power [kW]: the current effective power calculated by the FI.
10 = Torque [%]: the current torque calculated by the FI.
11 = Field [%]: the current field in the motor calculated by the FI.
12 = On-time [h], "Operating hours": time that voltage is applied to the FI network.
13 = Run-time [h], "Operating hours enabled": is the time that the FI is enabled.
14 = Analog input 1 [%]: actual value AIN1 of the first I/O extension SK xU4-IOE.
15 = Analog input 2 [%]: actual value AIN2 of the second I/O extension SK xU4-IOE.
16 = … 18 reserved Posicon, BU 0210
19 = Temp. of heat sink C], "Heat sink temperature": current temperature of the FI heat sink.
20 = Usage rate motor [%]: average motor load, based on the known motor data
(P201...P209).
21 = Usage rate brakeres. [%], "Brake resistor load": is the average braking resistor load,
based on the known resistance data (P556...P557).
22 = Internal temperature [°C]: current temperature in FI housing.
23 = Motor temperature [°C]: only in combination with the analog input and appropriate
wiring (KTY84).
30 = Cur. set value MP-S [Hz], "Actual setpoint value of the motor potentiometer function
with saving": display of the setpoint which can be set in advance (without the drive unit
running) via the motor potentiometer function 71 / 72 (See parameter P420).
50 = … 54 reserved Posicon, BU 0210
60 = R Stator Ident: stator resistance, automatic determination of motor data, P220
61 = R Rotor Ident: rotor resistance, automatic determination of motor data, P220
62 = L Scat Stator Ident, "L Scatter Stator Ident": stator leakage inductance, from automatic
determination of motor data, P220
63 = L Stator Ident: stator inductance, from automatic determination of motor data, P220