Manual

SK 200E Manual for frequency inverters
218 Subject to technical alterations BU 0200 GB-4411
Parameter
{Factory setting}
Setting value / Description / Note
Device
Supervisor
Parameter
set
P528
Load control delay
(Load monitoring delay))
S
P
0.1 ... 320.0 s
{ 2.0 }
From Firmware V1.3
Parameter (P528) defines the delay time for which an error message ("E12.5") is suppressed
            
triggered after half of this time has elapsed.
According to the selected monitoring mode (P529) an error message can also be generally
suppressed.
P529
Mode Load control
(Load monitoring mode)
S
P
0 ... 3
{ 0 }
From Firmware V1.3
The reaction of the frequency inverter to an infringement of the defined monitoring range

0 = Fault and warning, After the elapse of the time defined in (P528), an infringement of
the monitoring range produces a fault ""E12.5"). A warning ("C12.5") is given after the
elapse of half of this time.
1 = Warning only, After the elapse of half of the time defined in (P528) and infringement of
the monitoring range produces a warning ("C12.5").
2 = F a Warn during const, "Error and warning in constant travel", as for setting "0",
however monitoring is inactive during acceleration phases.
3 = Warning only during const, "Warning only during constant travel"
however, monitoring is inactive during acceleration phases.