280 Subject to technical alterations BU 0200 GB-4411
Size 4
Device type:

-112-340-A
-152-340-A
-182-340-A
-222-340-A
Nominal motor power
(4-pole standard motor)
400V
11.0 kW
15.0 kW
18.0 kW
22.0 kW
480V
15 hp
20 hp
25 hp
30 hp
Input
Mains voltage
3~ 400V
3 AC 380 ... 500V, -20 / + 10%, 47 ... 63 Hz
Typical input current
at 400V
3~ rms
23.6 A
32.0 A
40.5 A
46.5 A
3~ FLA
20.5 A
28.0 A
35.5 A
42.5 A
Rec. mains fuse
1 AC
slow-acting [A]
35 A
50 A
50 A
63 A
Permissible
mains fuses (UL)
RK5 or faster
fuses,
min 230V/400V
30 A
40 A
60 A
60 A
Bussmann
FRS-R-30
FRS-R-40
FRS-R-60
FRS-R-60
Circuit breaker*
min. 230V/400V
30 A
40 A
60 A
60 A
Output
Output voltage
3~ 400V
3 AC 0 - Mains voltage
Nominal output cur-
rent at 400V
rms
23.0 A
32.0 A
40.0 A
46.0 A
Motor Assem-
bly**
23.0 A
32.0 A
40.0 A
46.0 A
Wall-mounted**
23.0 A
29.0 A
40.0 A
46.0 A
Min. braking resistor
47
33
27
24
Recommended braking
resistor
Sec. 2.3
100
100
50
50
Motor Assembly
Max. continuous power / max. continuous current:
S1-50
S1-40°C
11.0 kW / 23 A
11.0 kW / 23 A
15.0 kW / 32 A
15.0 kW / 32 A
15.0 kW / 29 A
18.5 kW / 40 A
15.0 kW / 29 A
22.0 kW / 40 A
Max. permissible ambient temp. with nominal output current
S1
S3 70%ED 10min
S6 70%ED 10min (100% / 20%Mn)
50°C
50°C
50°C
50°C
50°C
50°C
45°C
46°C
46°C
40°C
42°C
42°C
Wall-mounting
Max. continuous power / max. continuous current:
S1-50°C
S1-40°C
11.0 kW / 23 A
11.0 kW / 23 A
15.0 kW / 32 A
15.0 kW / 32 A
15.0 kW / 29 A
18.5 kW / 40 A
15.0 kW / 29 A
22.0 kW / 40 A
Max. permissible ambient temp. with nominal output current
S1
S3 70%ED 10min
S6 70%ED 10min (100% / 20%Mn)
50°C
50°C
50°C
50°C
50°C
50°C
45°C
46°C
47°C
40°C
42°C
42°C
* Circuit Breaker (inverse time trip type) as per UL489
** FLA (S1-40 °C)