GB BU 0240 NORDAC SK 200E Brief instructions for frequency inverters
NORDAC SK 200E Manual Safety information N O R D A C SK 200E frequency inverters Safety and operating instructions for drive power converters (as per: Low Voltage Directive 2006/95/EEC ) 1. General During operation, drive power converters may, depending on their protection class, have live, bare, moving or rotating parts or hot surfaces. Unauthorised removal of covers, improper use, incorrect installation or operation causes a risk of serious personal injury or material damage.
NORDAC SK 200E Manual Concerning this document Intended use of the frequency inverter Compliance with the operating instructions is necessary for fault-free operation and the acceptance of possible warranty claims. These operating instructions must be read before working with the device! These operating instructions contain important information about servicing. They must therefore be kept close to the device.
NORDAC SK 200E Manual Documentation Designation: BU 0240 GB Part No.: 607 24 02 Device series: SK 205E, SK 215E, SK 225E, SK 235E Device types: SK 2xxE-250-112-O ... SK 2xxE-750-112-O, 0.25 - 0.75kW, 1~ 100-120V, 230V Output SK 2xxE-250-123-O ... SK 2xxE-111-123-A, 0.25 - 1.1kW, 1~ 220-240V SK 2xxE-250-323-O ... SK 2xxE-401-323-A, 0.25 - 4.0kW, 3~ 220-240V SK 2xxE-550-340-O ... SK 2xxE-751-340-A, 0.55 - 7.
Table of Contents 1 GENERAL INFORMATION ......................................................................................................6 1.1 Delivery.................................................................................................................6 1.2 Safety and installation information .......................................................................7 1.3 Wiring guidelines ..................................................................................................9 1.
NORDAC SK 200E Manual 1 General information These brief instructions for the SK 200E are based on the user manual for the frequency inverter - BU0200. In addition to information concerning safety and use, this document also contains selected information on commissioning, as well as use of the frequency inverter in explosion hazard areas (ATEX Zone 22). This manual is based on the device software V1.2 R0 (see P707) of the SK 200E.
1 General 1.2 Safety and installation information NORDAC SK 200E frequency inverters are devices for use in industrial high voltage systems and are operated at voltages that could lead to severe injuries or death if they are touched. • Installation and other work may only be carried out by qualified electricians and with the device disconnected. The operating instructions must always be available to these persons and must be strictly observed.
NORDAC SK 200E Manual CAUTION Children and the general public must be kept away from the equipment! The equipment may only be used for the purpose intended by the manufacturer. Unauthorised modifications and the use of spare parts and additional equipment which has not been purchased from or recommended by the manufacturer of the device may cause fire, electric shock and injury.
1 General 1.3 Wiring guidelines The frequency inverter has been developed for use in an industrial environment. In this environment, high levels of electromagnetic interference can influence the frequency inverter. In general, correct installation ensures safe and problem-free operation. To meet the limiting values of the EMC directives, the following instructions should be complied with.
NORDAC SK 200E Manual 1.4 Nomenclature / type codes Unique type codes have been defined for the individual modules and devices. These provide individual details of the device type and its electrical data, protection class, fixing version and special versions.
1 General Frequency inverter type code SK 205E-370-323-A (-C) IP protection class: Standard = IP55, C = „coated“ IP66 Radio interference filter: O = without, A = Class A1, B = Class B1 Mains voltage: x12 = 115V, x23 = 230V, x40 = 400V Number of mains phases: 1xx = single phase, 3xx = 3-phase Digits before comma for power: 0 = 0.xx, 1 = 0x.x0, 2 = 0xx.0 Device nominal power: 250 = 0.25kW, 370 = 0.37kW, ... 751 = 7.5kW Device series: SK 205E, SK 215E, SK 225E, SK 235E (...
NORDAC SK 200E Manual 2 Assembly and installation 2.1 Installation and assembly NORDAC SK 200E frequency inverters are available in various sizes depending on their output. Connection of the SK 200E to the motor or the wall-mounting unit is made by means of the a suitable size of connection unit SK T14-… The frequency inverter is mounted by means of integrated plug contacts. The devices require adequate ventilation to protect against overheating.
2 Assembly and installation Mounting the adapter unit For the supply of a complete drive unit (gear unit + motor + frequency inverter) the SK 200E frequency inverter and the SK T14-... adapter unit are always completely assembled and tested. The adapter unit can also be ordered separately for subsequent mounting on an existing motor or to replace a different motormounted frequency inverter. NOTE However, the IP66 compliant SK 200E must be installed by NORD, as special measures must be implemented.
NORDAC SK 200E Manual 2.2 Electrical connection WARNING THE DEVICES MUST BE EARTHED. Safe operation of the devices requires that is installed and commissioned by qualified personnel in compliance with the instructions provided in this Manual. In particular, the general and regional installation and safety regulations for work on high voltage systems (e.g. VDE) must be complied with as must the regulations concerning correct use of tools and the use of personal protection equipment.
2 Assembly and installation 2.3 Electrical connection of power unit L1 / L L2 / N L3 / PE All connection terminals are located in the connection unit of the frequency inverter. One terminal block is provided for the power connections and one for the control connections. The earthing connections (device earthing) are located on the base in the cast housing of the connection unit. PE L3 L2 L1 Before and while the device is connected, the following must be observed: 1.
NORDAC SK 200E Manual 2.4 Electrical connection of SK 200E control unit The control terminals are located on the inside of the frequency inverter connection unit. The connections differ according to the version (SK 205E, 215E, 225E, 235E). Connection terminals: Screw terminals, 3.5 mm slot-head screwdriver Cable cross-section: 0.2 ... 2.5mm 2, AWG 24-14, rigid or flexible, without wire end sleeves Tightening torque 0.5 ... 0.
2 Assembly and installation Control terminal functions LABELLING, FUNCTION SH: "Safe stop" function 24V SH: "Safe stop" input AS: Integrated AS interface GND SH: "Safe stop" reference potential 24V: External 24V power supply SYS+/-: System bus GND: Reference potential for digital signals MB+/-: DIN: Digital input Electromagnetic brake control (105V, 180V, 205V) DO: Digital output TF+/-: Motor PTC connection CONNECTIONS AND FUNCTIONS FOR SK 200E VERSIONS FI type SK 205E SK 215E (SH)
NORDAC SK 200E Manual 3 SK 200E displays and control By combining different modules for display, control and parameterisation, the NORDAC SK 200E can be easily adapted to various requirements. Alphanumeric display and control modules (Illustration below) can be used for simple commissioning. For more complex tasks, connection to a PC system and the use of Nord Con parameterisation software is available. As supplied, without additional options, the diagnostic LEDs are externally visible.
4 Commissioning 4 Commissioning, SK 200E The SK 200E inverter series can be commissioned in various ways: a) For simple applications (e.g conveyor applications) by means of the DIP switches integrated into the SK 200E (inside) and potentiometers (externally accessible). In this configuration the plug-in EEPROM is not required. b) Through adaptation of parameters using software via the ParameterBox (SK CSX-3H or SK PAR3H) or NordCon PC - supported software.
NORDAC SK 200E Manual 4.1.2 Configuration Changes to individual parameters are usually necessary for operation. (Exceptions: see Section 4.1.3 ) Configuration can be carried out to a limited extent via the DIP switches. Configuration by means of software parameterisation is necessary for more extensive parameter changes. NOTE Mixing of DIP switch configuration and (software) parameterisation should be avoided. 4.1.2.
4 Commissioning 4.1.2.2 DIP switch configuration The DIP switches provide the possibility of carrying out commissioning without additional control units. Additional settings are made using the potentiometer on the top of the frequency inverter. As supplied, all DIP switches are at the “Off” position, which corresponds to control via the digital inputs. The frequency setpoint value is adjusted via P1 and P2. No.
NORDAC SK 200E Manual Details of DIP switches 5/4 and 3 Applies to devices SK 205E, SK 215E (without AS interface on board) DIP 5 4 Functions as per the list of analog functions (P400) Functions as per the list of digital functions (P420) 3 Dig 1 Dig 2 Dig 3 Dig 4** Poti 1 Poti 2 (P420 [01])* off {01} "Enable R" (P420 [02])* {02} "Enable L" =5Hz (P465[01]) =10Hz (P465[02]) off on off {01} "Enable R" on off off {45} "3-on" on on off {50} "F Arr Bit0" {02} "Enable L" {26} "F setpoint" {12}
4 Commissioning Details of potentiometers P1 and P2 The setpoint can be adjusted to a fixed value with the integrated potentiometer P1. Adjustment of the startup and braking ramps can be made via potentiometer P2. Potentiometer P2 P1 Potentiometer P1 (continuous) P2 (stepped) 0% P102/103 P105 - - - 10% 0.2s 10Hz 1 P102/103 P104 20% 0.3s 20Hz 2 0.2s 2Hz 30% 0.5s 30Hz 3 0.3s 5Hz 40% 0.7s 40Hz 4 0.5s 10Hz 50% 1.0s 50Hz 5 0.7s 15Hz 60% 2.0s 60Hz 6 1.0s 20Hz 70% 3.
NORDAC SK 200E Manual 4.1.3 Commissioning examples 4.1.3.1 Test operation A SK 200E series frequency inverter which is to be used to control a 4-pole motor of the same power can be operated without any aids to testing purposes. The only condition for this is the correct connection of the mains and motor cables and the supply of a 24V DC control voltage to the inverter (See Section 4.1.1). The PTC input must be bypassed, if a motor with PTC is not available.
4 Commissioning Minimal configuration with options In order to implement completely autonomous operation (i.e. independent of control cables etc.) a Potentiometer Unit (SK CU4-POT) is required. In combination with an integrated mains unit (SK CU4-…-24V) a solution can be implemented with only one mains cable (1~ / 3~ according to the version), and a suitable speed and direction control can be ensured (See connection example below).
NORDAC SK 200E Manual 4.2 ATEX Zone 22 for SK 2x5E General information With appropriate modification, the NORDAC SK 2x5E frequency inverter can be used in explosion hazard areas. For this it is important that all the safety information in the operating instructions is strictly complied with for the prevention of personal injury and material damage. This is essential to prevent injury and damage.
4 Commissioning - ATEX 4.2.1 Modified SK 2x5E for compliance with Category 3D For the operation of an SK 2x5E in ATEX Zone 22 only a modified frequency inverter is permissible. This adaptation is only made at the NORD factory. In order to use the frequency inverter for ATEX Zone 22, the standard cable gland plugs must be replaced by ATEX-approved brass plugs. Also, in addition to modified seals, the clear plastic diagnostic plugs are replaced by aluminium/glass versions.
NORDAC SK 200E Manual Name 4.2.2.
4 Commissioning - ATEX 4.2.2.3 Hand-held Technology Units for ATEX Zone 22 3D All hand-held technology units are not approved for continuous use in the ATEX Zone 22 3D. The may therefore only be used during commissioning or for maintenance purposes, if it is ensured that no explosive dust atmosphere exists.
NORDAC SK 200E Manual 4.2.2.5 Other options M12 sockets and plugs for installation in the terminal box of the basic device or in technology units may only be used of they are approved for use in ATEX Zone 22 3D.
4 Commissioning - ATEX 4.2.4 Commissioning information For Zone 22 the cable glands must at least comply with protection class IP 55. Unused openings must be closed with blank screw caps suitable for ATEX Zone 22 3D (minimum protection class IP 55). The motors are protected against overheating by means of the frequency inverter. This is carried out by the evaluation of the motor PTC by the frequency inverter.
NORDAC SK 200E Manual 4.2.
5 Parameterisation 5 Parameterisation of frequency inverter SK 200E The frequency inverter, field bus and I/O -extension modules each have their own logic systems. These can be adapted to customers' requirements by means of changeable parameters. The basic functions of the particular modules are factory-set, so that the units have basic functionalities on delivery. Limited adaptations of individual functions of the relevant devices can be implemented via DIP switches.
NORDAC SK 200E Manual Parameter list - inverter functions (selection) Parameter Description Factory setting Settings / functions (selection) P102 Start-up time Start-up time (acceleration ramp) is the time corresponding to the linear frequency rise from 0Hz to the set maximum frequency (P105). [2.00] Note: Values < 0.1 must be avoided P103 Braking time The braking time (braking ramp) is the time corresponding to the linear frequency reduction from the set maximum frequency (P105) to 0Hz. [2.
6 Status messages Parameter list - inverter information (selection) Parameter P700 Current operating status Description Display of current messages for the actual operating status of the frequency inverter such as errors, warnings or the cause of a switch-on block.
NORDAC SK 200E Manual Diagnostic LEDs LED Signal Name Colour Description Status Meaning DOUT 1 yellow Digital output 1 on High signal applied DIN 1 yellow Digital input 1 on High signal applied DIN 2 yellow Digital input 2 on High signal applied DIN 3 yellow Digital input 3 on High signal applied DIN 4 yellow Digital input 4 on High signal applied TEMP yellow Motor PTC on Motor overtemperature Chop yellow Brake chopper on Brake chopper active, brightness → degree of
7 Technical data 7 Technical Data Frequency Inverter Function Specification Output frequency 0.0 … 400.0Hz Pulse frequency 3.0 … 16.0kHz, standard setting = 6kHz Power reduction > 8kHz for 115/230V device, >6kHz for 400V device. Typical overload capacity 150% for 60s, 200% for 3.
NORDAC SK 200E Manual 8 Maintenance and servicing information In normal use, NORDAC SK 200E frequency inverters are maintenance free. Please note the "General Data". If the frequency converter is being used in a dusty environment, then the cooling-vane surfaces should be regularly cleaned with compressed air. If air intake filters have been built into the control cabinet, then these should also be regularly cleaned or replaced.
9 Keyword index 9 Keyword index A I Address ...................................... 38 IEC 61800-3 ................................. 8 Array parameter ......................... 33 Installation .................................. 12 AS Interface ............................... 36 Installation notes .......................... 7 ATEX Zone 22, Cat. 3D ............. 26 Installing the SK 200E ................ 13 Internet ....................................... 38 Q Queries .............................