Details of potentiometers P1 and P2
The setpoint can be adjusted to a fixed value with the integrated potentiometer P1. Adjustment of the start-
up and braking ramps can be made via potentiometer P2.
Potentiometer
P1 (continuous) P2 (stepped)
0% P102/103 P105 - - -
10% 0.2s 10Hz 1 P102/103 P104
20% 0.3s 20Hz 2 0.2s 2Hz
30% 0.5s 30Hz 3 0.3s 5Hz
40% 0.7s 40Hz 4 0.5s 10Hz
50% 1.0s 50Hz 5 0.7s 15Hz
60% 2.0s 60Hz 6 1.0s 20Hz
70% 3.0s 70Hz 7 2.0s 25Hz
80% 5.0s 80Hz 8 3.0s 30Hz
90% 7.0s 90Hz 9 5.0s 35Hz
100% 10.0s 100Hz 10 7.0s 40Hz
The function of P1 and P2 depends on DIP 4/5. The meaning
changes according to the setting.
As standard, P1 sets the setpoint value of 0-100% and P2 sets the
ramp from 0.2-7sec.