Owner's manual

4 Commissioning - ATEX
BU 0240 GB 29
4.2.2.3 Hand-held Technology Units for ATEX Zone 22 3D
All hand-held technology units are not
approved for continuous use in the ATEX Zone 22 3D. The may
therefore only be used during commissioning or for maintenance purposes, if it is ensured that no explosive
dust atmosphere exists.
Name Part Number
Approved for
ATEX Zone 22 3D
Not approved for
ATEX Zone 22 3D
SK CSX-3H 275281013
x
SK PAR-3H 275281014
x
ATTENTION
The diagnostic opening of the basic unit for the connection of a hand-held
technology unit or a PC must not
be opened in an atmosphere containing
explosive dust.
4.2.2.4 Braking resistors
External braking resistors of type SK BRE4-x-xxx-xxx are not permitted for use in ATEX Zone 22 3D.
Name Part Number
Approved for
ATEX Zone 22 3D
Not approved for
ATEX Zone 22 3D
SK BRI4-1-100-100 275272005
x
SK BRI4-1-200-100 275272008
x
SK BRI4-1-400-100 275272012
x
SK BRI4-2-100-200 275272105
x
SK BRI4-2-200-200 275272108
x
SK BRE4-1-100-100 275273005
x
SK BRE4-1-200-100 275273008
x
SK BRE4-1-400-100 275273012
x
SK BRE4-2-100-200 275273105
x
SK BRE4-2-200-200 275273108
x
ATTENTION
If an internal braking resistor of type SK BRI4-x-xxx-xxx is used, the power limitation for
this must be activated under all circumstances. This is usually done by setting DIP
switch 8 to "ON". Alternatively, parameters (P555), (P556) and (P557) can be
parameterised with the appropriate values. Only the resistors assigned to the relevant
inverter type may be used.