Owner's manual

NORDAC SK 200E Manual
36 BU 0240 GB
Diagnostic LEDs
LED Signal
Name Colour Description Status Meaning
DOUT 1 yellow Digital output 1 on High signal applied
DIN 1 yellow Digital input 1 on High signal applied
DIN 2 yellow Digital input 2 on High signal applied
DIN 3 yellow Digital input 3 on High signal applied
DIN 4 yellow Digital input 4 on High signal applied
TEMP yellow Motor PTC on Motor overtemperature
Chop yellow Brake chopper on Brake chopper active, brightness degree of load
Brake yellow Mech. brake on Mech. Brake released
BUS-S green System bus status off No process data communication
Flashing
(4 Hz)
"BUS Warning"
on Process data communication active
Reception of at least 1 telegram / s
SDO transfer is not indicated
BUS-E green System bus error off No error
Flashing
(4 Hz)
Monitoring error P120 or P513
E10.0 / E10.9
Flashing
(1 Hz)
Error in an external system bus module
Bus module Æ Timeout on the external BUS (E10.2)
System bus module has a module error (E10.3)
on
System bus in state “BUS off”
Status LEDs
LED Signal
Name Colour Description Status Meaning
DS dual
red/green
Frequency
inverter status
off FI not on standby,
no mains and control voltage
green on FI on standby
green
flashing
0.5 Hz FI is ready for switch-on
2 Hz FI is in switch-on block
red/green 0.5 Hz Warning
alternating 1 … 25Hz Degree of overload of switched-on FI
green on +
red flashing
FI not on standby,
Control voltage available but no mains
voltage
red flashing
Error, flashing frequency Error number
AS-I dual
AS-i status
off No voltage to the AS-i module (PWR)
red/green green Normal operation
red No exchange of data
Slave Address = 0 / Slave not in LPS /
Slave with incorrect IO/ID /
Master in STOP mode / Reset active
alternately
flashing
red / green
Peripheral error