4.9.2 CANopen profile DS301
The available objects are defined according to communication profile DS301.
4.9.2.1 Communication objects (1000
hex
- 1200
hex
)
Index Sub Object Description Unit Access Type
0x1000 0 Device type Device type and functionality RO U32
0x1001 0 Error register
The Error Register is set to 1 (=generic error) if one of
the connected frequency inverters is in an error state.
In addition, it is monitored whether a registered
inverter goes missing. In this case, this register will
also be set.
RO U8
0x1002 0 Status register Status of the module RO U32
0x1003 ARR Pre-defined error Error signaled by an emergency object U8
0 Number of errors
Number of errors;
0 deletes the error list
RW U8
1 Error code Error number RO U32
0x1005 0 COB-ID SYNC
Identifier for SYNC messages (default 80h)
(see parameter (P161 [-01]))
RW U32
0x1008 0 Device name Device name RO STR
0x1009 0 Hardware version Hardware version RO STR
0x100A 0 Software version Software version FI+CO RO STR
0x100C 0 Guard time
Guard time (0=off)
(see parameter (P166 [-01]))
ms RW U16
0x100D 0 Life time factor
Life time = Life time factor * Guard time
(see parameter (P167))
RW U8
0x1010 0 Store parameters
With this object it is possible to permanently save
settings made by the user. To do this, the signature
“Save“ (lower case letters ASCII – MSB - 0x65 76 61
73 - LSB) must be written in Index 0x1010 Sub-index
1. The saving process runs in the background and is
confirmed with an SDO response telegram.
Caution
: If the module ID is changed with the DIP
switches after saving a configuration, the saved
configuration will still be used. The default mapping
is restored with the object 0x1011.
RW U32
0x1011 0
Restore default
parameters
With this object it is possible to restore parameters
saved by the user to the default settings. By writing
the signature "load" (lower case letters ASCII - MSB
0x64 0x61 0x6F 0x6C LSB) in Index 0x1011 Sub-
index 1, the standard factory settings will be loaded
after the following Power ON and every other Power
ON (until the next SAVE command).
(see parameter (P152))
RW U32
0x1014 0
COB-ID
Emergency Object
Identifier Emergency Object
(80h+Node-ID)
RO U32
0x1015 0 Inhibit time EMCY Minimum repeat time ms RW U16
0x1017 0
Producer Heartbeat
time
Cycle time of the heartbeat function
(see Parameter (P166 [-02]))
ms RW U16
0x1018 REC Identity object General device information U32
0 Largest sub-index Number of elements RO U8
1 Vendor ID CiA-listed manufacturer code RO U32
2 Product code Device version (product number) RO U32
3 Revision number Software version and revision number (2x16 bit) RO U32