Owner's manual

Supplementary Manual EtherCAT for NORDAC SK 200E
42 Subject to technical amendments BU 0270 GB
Sw itch-on
disabled
Standby
Activated
Operation enabled
Fast stop active
Error reaction
active
Fault
From all device statuses
34568
45
5
Not on standby
Sw itching on the inverter
Loading relay applied
Fault
Error reaction complete
Bit0 = 0: Shut dow n
& Bit1 = 1: Enable voltage
& Bit2 = 1: Enable pulses
(xxxx x1xx xxxx x110)
Bit 3 = 0: Disable operation Bit0 = 1: Sw itch on
Bit3 = 1: Enable operation
Bit2 = 0: Fast stop
Bit1 = 0: Disable voltage
v Bit2 = 0: Fast stop
Priority of control commands:
1. Disable voltage
2. Fast stop
3. Shut dow n
4. Enable operation
5. Sw itch on
6. Disable operation
7. Reset error
Designation of statuses:
1: Bit 0 = 0
2: Bit 6 = 1
3: Bit 0 = 1
4: Bit 1 = 1
5: Bit 2 = 1
6: Bit 5 = 0
7: Bit 2 & Bit 3 = 1
8: Bit 3 = 1
3
5
23
364
2
2
1
2
3
7
8
f = 0 reached
(fast stop complete)
Bit7 0
1
Error acknow ledgement
Control bits
0. Ready for operation / shut dow n
1. Disable / enable voltage
2. Enable pulses / emergency stop
3. Disable / enable operation
4. Operation condition / block RUE
5. Enable / stop RUE
6. Enable / disable setpoint
7. Error acknow ledgement (0
1)
10. Control data valid / invalid
11. Rotation right
12. Rotation left
14. Parameter set Bit 0
15. Parameter set Bit 1
4
5
6
Bit4 = 0: Move dow n emergency stop ramp and
remain in 'Operation enabled'
Bit5 = 0: Hold frequency
Bit6 = 0: Setpoint = 0%
Bit0 = 0: Shut dow n
5
Bit3 = 1: Enable operation
&Bit0 = 1: Sw itch on
2
Internal status machine
2
Diagram of the FI Status Machine