5 Parameterisation
BU 0280 GB Subject to technical amendments 51
Parameter
{Factory setting}
Setting value / Description / Note Device Supervisor
Parameter
set
P515 ... [-01]
... [-03]
CAN address (system bus)
S
0 ... 255 dec
{ all 32 dec}
or { all 20 hex}
Setting of the system bus address.
[-01] = Receive address for system bus
[-02] = Broadcast – Receive address for system bus (slave)
[-02] = Broadcast – Transmit address for system bus (master)
NOTE:
If up to four SK 200E are to be linked via the system bus, the addresses must be set as follows
FI 1 = 32, FI 2 = 34, FI 3 = 36, FI 4 = 38.
The system bus addresses should be set via the DIP switches 1/2 (Section 2.2.3).
P543[-01]
...
[-03]
Actual bus value 1… 3
S P
0 ... 22
{ [-01] = 01 }
{ [-02] = 04 }
{ [-03] = 09 }
The return value can be selected for bus actuation in this parameter.
NOTE: For further details, please refer to the description for P418.
[-01] = Actual bus value 1
… [-02] = Actual bus value 2 (only for PPO Type 2 or 4)
… [-03] = Actual bus value 3 (only for PPO Type 2 or 4)
Possible values which can be set:
0 = Off
1 = Actual frequency
2 = Actual speed
3 = Current
4 = Torque current (100% = P112)
5 = State of digital inputs and outputs
2
6 = ... 7 Reserved
8 = Setpoint frequency
9 = Error number
10 = ... 11 Reserved
12 = Bus Out bits 0...7
13 = ... 16 Reserved
17 = Value analog input 1 (P400)
18 = Value analog input 2 (P405)
19 = Setpoint frequency master value (P503)
20 = Setpoint frequency after master value ramp
21 = Actual frequency without master value slip
22 = Speed from encoder
2
The assignment of the dig. inputs for P543 = 5
Bit 0 = DigIn 1 Bit 1 = DigIn 2 Bit 2 = DigIn 3 Bit 3 = DigIn 4
Bit 4 = DigIn 5 Bit 5 = DigIn 6 Bit 6 = DigIn 7 Bit 7 = Reserved
Bit 8 = Reserved Bit 9 = Reserved Bit 10 = Reserved Bit 11 = Reserved
Bit 12 = Out 1 Bit 13 = Out 2 Bit 14 = Out 3 Bit 15 = Out 4