Use and Care Manual

28
For Vertical Vent Termination - PVC, CPVC or PP Material
Roof Flashing
Storm Collar
Roof
Flashing
Storm
Collar
≥ 3 ft Min. ≥ 3 ft Min.
12 in. over
maximum
snow level
12 in. over
maximum
snow level
Support
Hanger
Strap
2 in. pipe*
3 in. pipe
2 in. × 3 in. Increaser
coupling
A short horizontal section is
required to prevent debris
from falling into the water
heater.
When using a horizontal
section, slope the horizontal
vent 1/4 in. upwards for
every 12 in. (305 mm)
toward the termination to
drain condensate.
When the vent
penetrates a floor or
ceiling and is not
running in a fire rated
shaft, a firestop and
support is required.
*
About the termination
When choosing intake and exhaust terminations, you must use the same type of elbow (i.e.
both 90° elbows).
This will help with proper combustion by putting both terminations in the same pressure zone.
Insert Bird Screen in End of 90° Elbow.
Bird Screen is not supplied with water heater, order separately.
To prevent excessive condensation formation, only the vent termination should be located on
the exterior of the building.
When the vent termination
is located not less than 8 ft
(2.4 m) from a vertical wall
or similar obstruction,
terminate above the roof at
least 2 ft (0.6 m), but not
more than 6 ft (1.87 m), in
accordance with the
National Fuel Gas Code
ANSI Z223.1 / NFPA 54 or
Natural Gas and Propane
Installation Code CSA
B149.1.
Provide vertical
support every 3 ft
(0.9 m) or as
required by the vent
pipe manufacturer's
instructions.
Support
Firestop
2 in. × 3 in. Increaser couplings are
required when using 3 in. (75 mm)
pipe.
The combustion
air intake of any
appliance
Any other building
opening
Firestop
Firestop
*
*
Firestop
* The length of the pipe
between the Increaser
couplings and the Exhaust
and Intake Flue of the
Water Heater should be up
to 6 in. (152 mm).
Exhaust
2 in. (50 mm)
or
3 in. (75 mm)
Intake
2 in. (50 mm)
or
3 in. (75 mm)
6.4.3 Vertical Vent Termination
Venting the Water Heater