s Manual

Emergency stop and safety gate monitoring
l
DEVICE
SAFE 4 / SAFE 4.1
Emergency stop
APPLICATIONS
and safety gate monitoring relay
APPROVALS
CE, TÜV, UL, C-UL
CONTACTS
3 normally open safety, 1 normally auxiliary closed
LED indicators for status and supply diagnostic
SPECIAL CHARACTERISTICS
Opposite polarity between channels
With (SAFE 4) and without (SAFE 4.1) start control
LED
Power, channel 1 and channel 2
24 V AC / DC (electronic fuse)
OPERATING VOLTAGE
110, 230 V AC (with galvanic disconnection/transformer)
POWER CONSUMPTION
24 V AC: ca. 5 VA, 24 V DC: 3 W, 110/230 V AC: 3,7 VA
START UP DELAY / FALLBACK TIME
< 50 ms / < 30 ms (24 V AC < 50ms) ready after time delay < 0,5 s
CONTACT CAPACITY max.
5 A, 240 V AC, 24 V AC / DC
CONTACT CAPACITY min. at 24V DC (*)
6 mA
SIMULTANEITY
ENVIRONMENTAL TEMPERATURE
-25°C to + 55°C
SWITCHING CAPACITY
1200 VA (resistive load)
CONTACT SECURITY
normally open 6,3 A quick acting or normally closed 4 A time lag
OPERATING MODE
(*) We offer all devices who have a CONTACT
CAPACITY of min. 100 mA at 24 V DC with
hard gold-plated contacts. In this way the
CONTACT CAPACITY of min. 100 mA is only 4 mA.
Please ask our sales team!
CONNECTION DIAGRAM
A supply voltage must be applied to terminals A1 and A2. Power LED
illuminates and 24 V DC is available at terminal S11. Terminals S12 and
S22 must be connected according to the application example selected to
meet the application requirements. To start the unit terminals S33 and S34
must be bridged with a normally open contact. The unit works if you close
this contact. At this time the contacts 13-14, 23-24 and 33-34 are closed.
The LEDs channel 1 and channel 2 illuminate. In series to this start button
an external contactor can be controlled.
For version with detachable clamps (screw - or cage clamps) ...
please ask our sales team!
S33 S34
S11
S12
Not-Halt
E-Stop
Start
S21
S22
FUNCTION CIRCUIT DIAGRAM
control logic
~ ~
S21
~
~
+
=
K1
S11
electronic
fuse
A1
(+)
A2
(-)
S34
S33
14
K2
K2
3424 42
13
K1
S12 S22
3323 41
Certifications according to
Safety relevant substance data
Depending on wiring (only max. values are given)
EN ISO 13849-1: PLe, Cat. 4
MTTFd: 154 years / high, DC: 99% / high
CCF: achieved
NORSTAT INC. 300 Roundhill Dr. Rockaway, NJ 07866 Tel: 973-586-2500 Fax: 973-586-1590 www.norstat.com