MES Electrode Steam Humidifiers Installation, Operation, Maintenance, Spare Parts, and Exploded Views Guide IMPORTANT: Read and save this guide for future reference. This guide to be left with equipment owner.
Table of Contents INSTALLATION 1 RECEIVING EQUIPMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 PRINCIPAL OF OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 WATER SUPPLY AND PLUMBING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 WATER CONNECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 START-UP AND OPERATION . . . . . . . . . . . . . . . . . . . . . .
Figure #1 INSTALLATION O p erS ati o n c h em RECEIVING EQUIPMENT CONDENSATE RETURN (OPTIONAL) 1. Check packing slip to ensure ALL material has been received. 2. Inspect box for damage and note on shipping waybill accordingly. FILL CUP 1 3. After unpacking, inspect unit for damage and if damage is found, advise shipper as soon as possible. 2 3 1” AIR GAP STEAM HOSE ELECTRODES 1. INLET CHAMBER 2. FILL CHAMBER 3.
are designed for water pressure from 30 to 80 psi and are protected by the built-in strainer. WATER SUPPLY AND PLUMBING 1. The fill valve is sized for an extended water pressure range of 30 to 80 psi. 4. For inlet water pressure outside this range, the factory should be contacted. (See Water Supply and Plumbing section of this manual.) 2. For cases below 15 psi add a pressure boost pump, notify the factory and a fill valve with an oversized orifice will be supplied. START-UP AND OPERATION 3.
Figure #4 MES-P Adjustable Pot The red light simply acts as a safety to shut off the fill valve and prevent over-filling. With the red light on, the water in the cylinder will continue to heat and, after a few minutes, start to boil. After the boiling action of the water has lowered the water level below the sensor at the top of the cylinder, the red light will go out and the fill solenoid will again open until the cylinder is again full.
dependent on water supply conditions and humidifier usage. Failure to replace the cylinder at the end of cylinder life may result in unit damage. NORTEC is not responsible for any damages resulting from, or attributable to, the failure to replace a used cylinder (see Manufacturer’s Warranty). INSTALLING THE NEW CYLINDER 1. The reverse procedure should be followed to install a new cylinder. The main disconnect is to be left open until the cylinder is completely installed and reconnected.
FOAMING: The phenomenon which can occur in water when the impurities, already in the water reach an excess concentration as a result of boiling away pure water and the continued boiling action agitating the contained water. The humidifier electronics are designed to prevent this occurrence although in extreme cases, water will foam with little concentration making it necessary to have the drain time of the water, contained in the cylinder, increased.
Water remains at high level and won’t concentrate: This is normal on cold start-up and can be accelerated by adding maximum 1/2 tsp. of dissolved salt to the cylinder (through the plastic fill cup) on fill cycle. See “Low Water Conductivity” section of this manual. If unit has been operating extensively, observe for normal fill-boil-fill-boil cycle; no drain should be occurring. If drain occuring, check for leaking drain valve or back pressure.
DIAGNOSTIC PROCEDURES - TROUBLESHOOTING GUIDE Unit Status Lamp Yellow On Green On Symptom Corrective actions Maximum water level This usually happens on initial start-up after replacing the cylinder inside cylinder. (normal). Water is concentrated with minerals inside the cylinder. Let unit run, yellow light will disappear when the unit is at full output. This may take a day or two. Off Off No power to the board. Check for main power supply fault. Turn power switch to ‘Drain’ position.
Software requirements for Modbus RTU Modbus addresses: 4XXXX – R/W 3XXXX - R Command Output Control Description MODBUS address OFF ON Disables the humidifier and places the humidifier in standby mode Enables the humidifier (humidifier will operate based on the SET OUTPUT command input) Details 40262 255: inhibit actions of humidifier 0: allow normal operation After a microprocessor reset, the default setting for Output Control shall be OFF.
Change the humidifier controller’s MODBUS parity. Range is None, Even, Odd This setting shall be non-volatile with a default setting of Even. Resets the humidifier controller’s run hour counter to zero hours 40554 Current damping Electrode current Buffers the measured current 40910 The value of the electrode current in Amps 30850 Steam output The current steam output in Kg/Hr.
Maximum production The rated maximum steam production for the humidifier 30802 Alarms The humidifier shall describe any faults Too long to fill Excess Current End of cylinder life No current 30364 Units Unit type Unit voltage Required by the control board for capacity calculations Required by the control board for current and capacity calculations Value written into Unit type (40600) is also stored here Bit Allocation Note More than one bit can be active at any time.
DIMENSIONS MES-U / MES-P 5* 10 15 20 25 30 DEPTH WIDTH in.(cm) WIDTH in.(cm) in.(cm) (REMOTE ELECTRICAL) (ATTACHED ELECTRICAL) 6.6 (16.7 cm) 8.6 (21.9 cm) 10.7 (27.1 cm) 6.6 (16.7 cm) 8.6 (21.9 cm) 10.7 (27.1 cm) 8.4 (21.3 cm) 10.5 (26.7 cm) 12.6 (32.2 cm) 8.4 (21.3 cm) 10.5 (26.7 cm) 12.6 (32.2 cm) 10.5 (26.7 cm) 10.5 (26.7 cm) 12.6 (32.2 cm) 10.5 (26.7 cm) 10.5 (26.7 cm) 12.6 (32.2 cm) HEIGHT in.(cm) 13.5 (34.4 cm) 17.3 (43.9 cm) 19.4 (49.3 cm) 19.4 (49.3 cm) 21.3 (54.0 cm) 21.3 (54.
PRIMARY POWER PRIMARY CONTACTOR 24 vac (By Others) PRIMARY TERMINAL BLOCK (provided with PVC unit) 24 VAC INPUT (By Others) ON/OFF CONTROLS .
- 13-
- -14- 41 42 43 40 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 1 POS. NO Cylinder - To order replacement cylinder, quote the 3-digit number on the cyl. Being replaced or quote the unit serial number, model and voltage from the spec label. Cylinder Plug - Sensor H.W.
- 15-
LIMITED WARRANTY Walter Meier Inc. and/or Walter Meier Ltd. (hereinafter collectively referred to as THE COMPANY), warrant for a period of two years from date of shipment, that THE COMPANY’s manufactured and assembled products, not otherwise expressly warranted are free from defects in material and workmanship. No warranty is made against corrosion, deterioration, or suitability of substituted materials used as a result of compliance with government regulations.
PRINTED IN CANADA Walter Meier (Climate USA) Inc. 826 Proctor Avenue, Ogdensburg, New York 13669 Walter Meier (Climate Canada) Ltd. 2740 Fenton Road, Ottawa, Ontario K1T3T7 Tel: 866 NORTEC 1 Fax: 613 822 7964 northamerica.climate@waltermeier.com www.humidity.