User Guide

10-10
Page 11
2008-02-18
Table 7. Humidifier Variable Addresses
Unit #4
Unit #4 BACnet Lonworks N2
Variable Name Type Instance SNVT SNVT # Element Type Instance
nvoHourOpt_4 AV 46 time_hour 124 67 AI 46
nvoCapLimit_4 AV 47 lev_percent 81 68 AI 47
nvoRHDem1_4 AV 48 lev_percent 81 69 AI 48
nvoSet1_4 AV 49 lev_percent 81 70 AI 49
nvoRHDem1_4 AV 50 lev_percent 81 71 AI 50
nvoSet2_4 AV 51 lev_percent 81 72 AI 51
nvoSysDemand_4 AV 52 lev_percent 81 73 AI 52
nviCapLimit_4 AV 53 lev_percent 81 74 AO 53
nviSet1_4 AV 54 lev_percent 81 75 AO 54
nviSet2_4 AV 55 lev_percent 81 76 AO 55
nviRHDem1_4 AV 56 lev_percent 81 77 AO 56
nviRHDem2_4 AV 57 lev_percent 81 78 AO 57
nviDisable_4 AV 58 switch 95 86 AO 58
Expansion_4 AV 59 N/A N/A N/A AO 59
Expansion_4 AV 60 N/A N/A N/A AO 60
nvoFault_4 BV 46 switch 95 79 Binary In 46
nvoHWSensor_4 BV 47 switch 95 80 Binary In 47
nvoNetSensor_4 BV 48 switch 95 81 Binary In 48
nvoDisable_4 BV 49 switch 95 82 Binary In 49
nvoSecurity_4 BV 50 switch 95 83 Binary In 50
nvoService_4 BV 51 switch 95 84 Binary In 51
nvoStatus_4 BV 52 switch 95 85 Binary In 52
Expansion_2 BV 53 N/A N/A N/A Binary Out 53
nviNetSensor_4 BV 54 switch 95 87 Binary Out 54
nvoConnection_4 BV 55 switch 95 88 Binary Out 55
Expansion_4 BV 56 N/A N/A N/A Binary Out 56
Expansion_4 BV 57 N/A N/A N/A Binary Out 57
Expansion_4 BV 58 N/A N/A N/A Binary Out 58
Expansion_4 BV 59 N/A N/A N/A Binary Out 59
Expansion_4 BV 60 N/A N/A N/A Binary Out 60