RESDELUX Steam Humidifiers Installation, Operation, Maintenance and Troubleshooting Guide IMPORTANT: READ AND SAVE THESE INSTRUCTIONS. This guide to be left with equipment owner.
Table Of Contents INSTALLATION 1 RECEIVING & UNPACKING EQUIPMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 PRE-INSTALLATION CHECKPOINT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 HUMIDIFIER CONFIGURATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 LOCATION & MOUNTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 HUMIDIFIERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PRINCIPLE OF OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 FILL RATE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 DRAIN TIME . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 RATED AMPERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 SHORT CYCLING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
HUMIDIFIER CONFIGURATION INSTALLATION To avoid any danger, never operate the humidifier with a door off. RECEIVING & UNPACKING EQUIPMENT 1. Check packing slip to ensure ALL material has been delivered. 2. All material shortages are to be reported to NORTEC within 48 hours from receipt of goods. NORTEC assumes no responsibility for any material shortages beyond this period. 3. Inspect shipping boxes for damage and note on shipping waybill accordingly. 4.
Figure #3 Wall Mounting Detail nozzle will have to be mounted from the inside of the duct. Remove internal insulation material if necessary. (See Figure #5). Figure #5 Steam Distribution Nozzle Mounting Arrangement Wall 0.6” (1.6 cm) Fasten Humidifier To Wall Using Screws 2” long (2) supplied by other 12.1” A(30.7cm) 5. Make sure humidifier is level. 6. DO NOT mount humidifier on hot surfaces. 3.
Figure #7 Steam Plumbing Arrangement Below Humidifier 12” (300 mm) 12 ” (3 00 mm ) 12” min. (300 mm) min. 10º Nortec Humidifiers All Models m) mi min. 10º m in. 0 m Rm ” (30 12 ) 12” (300 mm) min. 2º BLOWER PACK CONNECTION The RESDELUX humidifier can be purchased with an optional blower pack for direct room humidification. The blower pack is field installed on the RESDELUX humidifier cabinet or located remote from the RESDELUX humidifier. Nortec Humidifiers All Models 12” min. (300 mm) min.
switched off at the electrical panel, or that it is unplugged (RESDELUX/C). 4. Put the power leads from the blower pack through this opening as you position the blower pack on top of the RESDELUX humidifier 3. Find a suitable location for mounting the remote blower pack. The surface should be flat with adequate clearances for the top, side, and front: 5. Push the blower pack forward until the locating tabs on the bottom of the blower pack with slots in the top of the RESDELUX push forward to engage.
NOTE: Improper wiring could damage the blower pack or RESDELUX PCB. 9. Remove the front door and service cover from the RESDELUX humidifier. 10. Connect the power leads for the blower pack to terminal P7 on the RESDELUX control board located next to the capacity adjustment potentiometer. 11. more corrosive. Some hardware changes may be required, at the time of order or in the field. 3. DO NOT supply hot water to the humidifier.
current) across terminals 1 and 2 on the low voltage control terminal. Control Installation 1. Wall Humidistat: Mount any wall humidistat (control or high limit) over the standard electrical box at a height similar to a typical thermostat. Any wall humidistat should be in a location representative of overall space being humidified and not in the path of the blower pack or air supply grille. Do not mount on an outside wall where temperature fluctuation can affect the control response. 2.
A flashing yellow light indicates a fault of the humidifier and the controller shuts off the humidifier. Please refer to troubleshooting section. valves operation. Green and yellow lights flash during this time. If there is no call for humidity, the humidifier is standing by and green light flashes. When control loop is closed, the green light is steady on and the humidifier starts its operation. The controller waits 10 seconds before energizing the on-board relays.
(Life varies from 500 to 2000 operating hours, as illustrated in Figure #16.) cylinder or quote the unit’s serial number, model and voltage located on the spec label (nameplate). The RESDELUX control board constantly monitors unit performance and will shut down the humidifier and alert the customer to change the cylinder. The yellow light will flash 4 times in sequence. 1. Turn off the water supply to the unit. 2. The used cylinder must be drained completely before removal.
12. Push the two slip-on terminals back onto the two tabs on the coil. The terminals, although not identical, are reversible. 3. This color-coding must be adhered to when replacing cylinder plugs on pins. 4. The electrode plug with the orange wire always goes on the single pin surrounded by a plastic shoulder. WARNING: To prevent the possibility of electrical shock the green ground wire must be reinstalled before power is restored. 5. Ensure that cylinder plugs fit snugly on the pins.
is provided in the section titled OPERATION. For a more detailed understanding please contact your NORTEC representative. TROUBLESHOOTING PLEASE READ THIS SECTION BEFORE REFERENCING SPECIFIC DIAGNOSTIC MESSAGES. 1. Ensure the installation detail conforms with the recommendations contained in the Installation section of this manual. 2. Understanding the Principle of Operation is an asset when troubleshooting. A basic description 3.
SHORT CYCLING PROCEDURES AND TERMS USED IN DIAGNOSING When the ‘on time’ of the humidifier is less than ten minutes upon a call for humidity. To correct short cycling, all humidifiers have a capacity adjustment which allows the output of the humidifier to be reduced as low as 25% of rated output, thus extending the ‘on time’ required to maintain output. Excessive short cycling may cause higher water conductivity (mineral content) than designed for the unit.
- 13 -
- 14 -
SPARE PARTS LIST AND EXPLODED VIEW - RESDELUX Item Number Part Number Description 1 151-9002 Cylinder type 202 2 158-1820 Steam distributor kit 3 153-5062 Steam distributor 4 158-1830 Steam blower pack 5 158-1821 Steam Hose 4’ long 6 158-7104 Cabinet front door 7 185-3104 Lock assembly with keys 8 145-6000 Drain valve complete 8a 145-5002 Screw Drain Valve 9 132-6002 Drain valve coil assembly 10 132-6004 Drain valve o-ring 11 131-3244 Fill valve assembly 11a 145-5000
4 23 22 24 5 2 3 21a 17 16 18 21b 21c 1 7 13a 13d 13e 20 8a 13b 10 19 13c 11b 15 11a 14 12 12a 14a - 16 - 11 8 9 6
PERIODIC MAINTENANCE CHECKLIST PREVENTIVE MAINTENANCE AND SERVICE CHECK LIST FOR NORTEC’S RESDELUX Customer ______________________________________________________________ Address ____________________________________________________________________________ Equipment Location ________________________ Serial # _______________________ Date Last Inspected _________________ Date of this Inspection __________________ Inspected By ________________________________________________________________________ Humidifier _
LIMITED WARRANTY Walter Meier Inc. and/or Walter Meier Ltd. (hereinafter collectively referred to as THE COMPANY), warrant for a period of two years from date of shipment, that THE COMPANY’s manufactured and assembled products, not otherwise expressly warranted (with the exception of the cylinder) are free from defects in material and workmanship. No warranty is made against corrosion, deterioration, or suitability of substituted materials used as a result of compliance with government regulations.
Model #: Serial #: Cylinder #: Cylinder Last Replaced: _________________________ MTH/DAY/YR _________________________ MTH/DAY/YR _________________________ MTH/DAY/YR PRINTED IN CANADA E6518 Walter Meier (Climate USA) Inc. 826 Proctor Avenue, Ogdensburg, New York 13669 Walter Meier (Climate Canada) Ltd. 2740 Fenton Road, Ottawa, Ontario K1T3T7 Tel: 866 NORTEC 1 Fax: 613 822 7964 nortec@humidity.com www.humidity.