Communication Server Large System Installation and Commissioning

Page 100 of 456 Installing DC power
NN43021-310 Standard 02.01 December 2007
Large Candeo sample configurations
Example configuration #1
1.05 m (42 in.) Frame with battery kit, LVD and distribution 500 (with
20 breaker positions).
17 mid trip breakers (30 A), one GMTX fuse block (takes up 3 breaker
positions).
System monitor.
Up to 10 rectifiers (500 A capacity).
Example configuration #2
1.05 m (42 in.) Frame with battery kit, LVD and distribution 500 (with
20 breaker positions). 17 mid trip breakers (30 A), one GMTX fuse block
(takes up 3 breaker positions).
Additional distribution 500 (with 20 breaker positions). 11 mid trip
breakers (30 A), three GMTX fuse blocks (takes up 3 breaker positions
per block).
System monitor.
Up to 6 rectifiers (300 A capacity).
Example configuration #3
2.1 m (84 in.) Frame with battery kit, LVD and distribution 500 (with 20
breaker positions). 20 mid trip breakers (30 A).
Second 2.1m (84in.) Frame with battery kit, LVD and distribution 500
(with 20 breaker positions). 11 mid trip breakers (30 A), three GMTX
fuse blocks (takes up 3 breaker positions per block).
Additional distribution 500 (with 20 breaker positions), 10 mid trip
breakers (30 A).
System monitor.
Up to 10 rectifiers (500 A capacity) in frame one, up to 10 rectifiers
(500 A capacity) in frame two.
One interframe DC link bar kit.