Communication Server Large System Installation and Commissioning

Installing DC power Page 121 of 456
Communication Server 1000M and Meridian 1 Large System Installation and Commissioning
The following equipment is located in the rear of each pedestal (see
Figure 43) in Large System columns.
The PDU distributes power to the entire column.
The field wiring terminal provides the connection point for wiring
brought into the pedestal.
A circuit breaker is provided for each module in the column and for the
blower unit.
All column circuit breakers will trip if a column thermal overload is
detected or a DC power low-voltage condition is sensed.
The system monitor checks the column temperature, cooling system
status, and system voltage status and controls alarms and line transfer
states accordingly.
Figure 43
DC-power equipment in the rear of the pedestal – NT4N49AA PDU
553-8997
FLTR / PWR DIST
LRTN
BLO CB0 CB1
CB2 CB3
++
UNIT ASSY
EACH INPUT CIRCUIT MUST BE PROVIDED WITH A
LISTED FUSE OR CIRCUIT BREAKER SUITABLE FOR
BRANCH CIRCUIT PROTECTION, RATED 30A.
J6J5J3 J4
553-8997