Communication Server Large System Installation and Commissioning

Page 252 of 456 Cabling network modules and loops
NN43021-310 Standard 02.01 December 2007
5 Install the remaining cables according to the assignments in Table 32 on
page 248.
End of Procedure
Cabling a Superloop Network Card – single column
If the system is configured in multiple columns, see “Basic cabling for
multiple-row network connections” on page 256.
Procedure 43
Basic cabling for single-row network connections
1 Refer to the work order and the cabling layout shipped with the system to
determine:
each loop number assigned
the module and slot assignments for the NT8D04 Superloop Network
Card associated with each loop
the location of NT8D37 IPE Modules that contain NT8D01 Controller
Cards associated with each loop
2 Set the Enb/Dis switch on each superloop network card to Dis.
CAUTION
System Failure
Due to the possibility of EMI/RFI noise, do not route
cables from front to rear next to the power supply
unit.