Communication Server Large System Installation and Commissioning

Page 368 of 456 Adding a module to a column
NN43021-310 Standard 02.01 December 2007
5 Connect the power and system monitor cables in the module:
a. Connect the power connectors to the pedestal and to the module
above (see Figure 125 on page 366 and Figure 127 on page 369).
b. Attach the frame ground wires to the frame ground post at the base
of the module.
c. Connect the system monitor cable from the pedestal to connector J1
on the module being added.
d. Connect the system monitor cable from connector J2 in the module
being added to J1 in the module above.
6 Set all circuit breakers in the pedestal to ON.
7 Reinstall the system monitor in the pedestal:
a. Reconnect the RJ11 cable to J6, then the cable to J3. Reinstall the
system monitor.
b. If the column houses the master system monitor, load LD 37, and
software re-enable the associated SDI port:
8 Replace all module covers and the pedestal grill.
End of Procedure
LD 37
ENL TTY x enable the device associated with the port
**** exit LD 37