Communication Server Large System Installation and Commissioning
Installing AC power Page 79 of 456
Communication Server 1000M and Meridian 1 Large System Installation and Commissioning
Multiple-column systems use an insulated ground bus as the point where the
logic return wires from different columns are consolidated before connecting
to the single-point ground.
Figure 25
Single column – ground and logic return distribution
Note: In an isolated ground system, the dedicated isolated ground bus
bar in the service panel serves as the ground window. It is used for all AC
safety grounds and logic returns. It also accommodates a conductor that
references the (+) battery bus in DC systems.
AC input
Service
panel
IG or ACEG
120 V
receptacle
Cord or
conduit
208/240 V
receptacle
(30 A L6 - 30
or
IG - L6 - 30)
Safety ground (#6 AWG, min)
Logic return
(#6 AWG)
AC conduit
553-3154-1
Large System