Communication Server Large System Installation and Commissioning

Installing AC power Page 85 of 456
Communication Server 1000M and Meridian 1 Large System Installation and Commissioning
Installing UPS ground cabling
Use the manufacturer’s documents to install and cable a UPS. If the UPS does
not contain an integral bypass switch, add one externally during initial UPS
wiring. Figure 31 is a block diagram of a UPS installation and associated
wiring.
Follow Procedure 5 to install UPS ground cabling.
Note: Because UPS installation can be complex, Nortel recommends
that installers attend vendor training programs.
Figure 31
AC reserve power configuration
Battery bank
(may be inside UPS)
UPS bypass
switch
Note:
The ac safety ground (green wire) must route from the service
panel, through the UPS, to the Large System panel or receptacles.
Receptacle and
cord, or conduit, to
pedestal(s)
UPS
CS 1000M Large SystemExternal power distribution
553-3163A
AC/DC
Converter
DC/AC
Inverter
208/240 V ac
AC input
Service
panel