26 Installation (for qualified installers only)
Travis Industries 4060907 100-01182
Rear Vent Configuration with Horizontal Termination (no vertical rise)
The termination must fall within the shaded area shown in the chart. Use the indicated restrictor
and diffuser positions.
HINT: Travis Industries provides a minimum rear vent kit (sku 98900168). It includes a 4” section and
a horiztontal termination cap.
Optional 45° Elbow
Termination
See the charts above to
determine maximum vent
3 feet
0 feet
0 feet
4' (max)
• Exhaust Restrictor Removed
• Intake Restrictor # 1 (stock)
• Diffuser Position # 1 (stock)
Vent with No 45° Elbow
3 feet
0 feet
0 feet
2' (max)
Vent with 1 45° Elbow
Min. 4" Horizontal Section
Max. 24" Horizontal Section(s)
Min. 4" Horizontal Section
Max.48" Horizontal Section(s)
Exhaust Restrictor Removed
Intake Restrictor # 1 (stock)
Diffuser Position # 1 (stock)
If venting to the rear with no vertical rise,
remove and discard the exhaust restrictor.
Replace the screws in the same holes.
Back Wall of
Firebox
Firebox
Roof
EXHAUST RESTRICTOR REMOVAL