Owner manual

Alpha Wire | www.alphawire.com | 1-800-52 ALPHA
Specifications subject to change. For complete specifications and availability, visit www.alphawire.com.
287
Cable > Communication, Control and Industrial > Shielded > 600/1000 V
Series V VFD Control Cables
Enhanced Design for Superior Performance in Variable-Frequency Drives
600/1000 V Shielded
Series V cables for variable-frequency
drives (VFD) set the standard in high-
performance and reliable connectivity.
Their specially formulated cross-linked
polyethylene insulation provides superior
corona resistance, low capacitance
for longer runs, and excellent low-
temperature properties.
A symmetrical design places the ground
wires in the interstices of the conductors
for uniform conductor-to-ground
capacitance and impedance.
Smaller gauge cable feature a combination
foil/braid shield to oer exceptional
EMI/RFI protection in noisy environments.
On larger gauge cable, a double copper
tape is used to provide the same noise-
free operation.
This uniformity reduces the probability
of motor damage from common-mode
current.
Alpha Series V VFD cables are compatible
with drives from all major manufacturers.
UL RHW-2 (16 – 2 AWG)
UL XHHW-2
UL TC-ER
UL 1000V Flexible Motor
Supply Cable
CSA AWM I/II A/B FT4
CE LVD 73/23/EEC
Amendment 93/68/EEC
Pennsylvania MHSA
Operating Temperature
-40°C to +90°C
Conductor Color Coding
Black, numbered
Materials
Stranded tinned copper
conductors
Stranded tinned copper
ground wires
Cross-linked polyethylene
insulation
Shielding
16 – 4 AWG:
Aluminum/polyester/aluminum
foil and tinned copper braid
with 85% coverage
2 – 4/0 AWG:
Double-layer copper tape
Black premium PVC jacket
Voltage
600 V (UL TC-ER)
1000 V (UL Motor Supply)
Features
UL Direct Burial
UL Sunlight Resistant
10x bend radius
Suitable for use in Class I,
Division 2 locations per Article
501 of the National Electric Code
Availability
Bulk, made to order
FIT® Tubing Recommendations
FIT-221: General-purpose
cross-linked polyolen
FIT-321V: Low-shrink-
temperature, flame-retardant
cross-linked polyolen
Four-Conductor VFD Cable
Part No.
Wire Size Stranding
Shielding
Insulation Thickness Jacket Thickness Nominal Diameter
AWG mm
2
AWG mm Inch mm Inch mm Inch mm
V16016 16 1.32 26/30 26 x 0.25 Foil/Braid 0.047 1.19 0.065 1.65 0.547 13.89
V16014 14 2.09 41/30 41 x 0.25 Foil/Braid 0.047 1.19 0.065 1.65 0.584 14.83
V16012 12 3.31 65/30 65 x 0.25 Foil/Braid 0.047 1.19 0.065 1.65 0.633 16.08
V16010 10 5.37 105/30 105 x 0.25 Foil/Braid 0.047 1.19 0.085 2.15 0.746 18.95
V16008 8 8.53 133/29 133 x 0.28 Foil/Braid 0.061 1.55 0.086 2.15 0.920 23.37
V16006 6 13.57 133/27 133 x 0.36 Foil/Braid 0.061 1.55 0.086 2.15 1.017 25.83
V16004 4 21.58 133/25 133 x 0.45 Foil/Braid 0.061 1.55 0.086 2.15 1.157 29.39
V16002 2 34.32 133/23 133 x 0.57 Foil/Braid 0.061 1.55 0.088 2.15 1.308 33.22
Four-Conductor VFD Cable with 14 AWG (2.09) Brake Pair
Part No.
Wire Size Stranding
Shielding
Insulation Thickness Jacket Thickness Nominal Diameter
AWG mm
2
AWG mm Inch mm Inch mm Inch mm
V16116 16 1.32 26/30 26 x 0.25 Foil/Braid 0.047 1.19 0.065 1.65 0.717 18.21
V16114 14 2.09 41/30 41 x 0.25 Foil/Braid 0.047 1.19 0.065 1.65 0.743 18.87
V16112 12 3.31 65/30 65 x 0.25 Foil/Braid 0.047 1.19 0.065 1.65 0.785 19.94
V16110 10 5.37 105/30 105 x 0.25 Foil/Braid 0.047 1.19 0.085 2.15 0.875 22.23
V16108 8 8.53 133/29 133 x 0.28 Foil/Braid 0.061 1.55 0.085 2.15 1.032 26.21