Instruction Manual

06
.
24
Han
Modular
Han
®
200 A Axial module
Features
• Axial-screw termination
• No special tools required
• Power module for big wire gauge up to 70 mm²
• Suitable as a 3 + PE connector in a Han
®
32 B
housing
• Compatible to the Han
®
200 A module with crimp
terminal
Current carrying capacity
The current carrying capacity of the connectors is limited by the
thermal load capability of the contact element material including
the connections and the insulating parts. The derating curve
is therefore valid for currents which ow constantly (non-inter-
mittent) through each contact element of the connector evenly,
without exceeding the allowed maximum temperature.
Measuring and testing techniques according to
DIN EN 60 512-5-2
Operating current
Ambient temperature
➀
24 B hoods/housings with 3 modules; wire gauge: 50 mm²
➁
24 B hoods/housings with 3 modules; wire gauge: 70 mm²
Technical characteristics
Specications DIN EN 60 664-1
DIN EN 61 984
Approvals ,
Inserts
Number of contacts 1
Electrical data
acc. to EN 61 984 200 A 1000 V 8 kV 3
Rated current 200 A
Rated voltage 1000 V
Rated impulse voltage 8 kV
Pollution degree 3
Rated voltage
acc. to UL 600 V
Insulation resistance ≥ 10
10
Ω
Material polycarbonate
Limiting temperatures -40 °C ... +125 °C
Flammability acc. to UL 94 V 0
Mechanical working life
- mating cycles ≥ 500
Contacts
Material copper alloy
Surface
- hard-silver plated 3 µm Ag
Contact resistance 0.2 mΩ
Screw terminal
- Wire gauge
1)
25 ... 70 mm²
- AWG 2 ... 00
- Hexagonal driver SW 5
- Stripping length 16 mm
- Tightening tourque
mm² 25 35 50 70
Nm 8 8 9 10
1) geometric wire gauge