Instruction Manual

06
.
30
Han
Modular
"https://b2b.harting.com/ebusiness/en/09 11 000 6114"
"https://b2b.harting.com/ebusiness/en/09 11 000 6116"
"https://b2b.harting.com/ebusiness/en/09 11 000 6125"
"https://b2b.harting.com/ebusiness/en/09 11 000 6135"
Han
®
100 A Crimp module
Features
• Crimp termination
• Unlock of contacts from mating side
• Connect PE contact with special cable shoe
• Compatible to Han
®
100 A module with axial
screw terminal
Current carrying capacity
The current carrying capacity of the connectors is limited by the
thermal load capability of the contact element material including
the connections and the insulating parts. The derating curve
is therefore valid for currents which ow constantly (non-inter-
mittent) through each contact element of the connector evenly,
without exceeding the allowed maximum temperature.
Measuring and testing techniques according to
DIN EN 60 512-5-2
Operating current
Ambient temperature
➀
24 B hoods/housings with 3 modules; wire gauge: 16 mm²
➁
24 B hoods/housings with 3 modules; wire gauge: 25 mm²
➂
24 B hoods/housings with 3 modules; wire gauge: 35 mm²
Technical characteristics
Specications DIN EN 60 664-1
DIN EN 61 984
Approvals
Inserts
Number of contacts 2
Electrical data
acc. to EN 61 984 100 A 1000 V 8 kV 3
Rated current 100 A
Rated voltage 1000 V
Rated impulse voltage 8 kV
Pollution degree 3
Rated voltage
acc. to UL 600 V
Insulation resistance ≥ 10
10
Ω
Material polycarbonate
Limiting temperatures -40 °C ... +125 °C
Flammability acc. to UL 94 V 0
Mechanical working life
- mating cycles ≥ 500
Contacts
Material copper alloy
Surface
- hard-silver plated 3 µm Ag
Contact resistance ≤ 0.3 mΩ
Crimp terminal
- mm² 10 ... 35 mm²
Max. cable diameter 14 mm
Crimp zone (C)