Product Manual
Operation (cont’d)
28
3. Starting the Generator
After you have completed the pre-start checklist procedures, you are ready to start the
generator.
Start engine
Start the engine with the guard in place.
Before starting, confirm there are no loads connected to the generator’s
outlets.
Follow the instructions provided in your engine manual for starting the
engine.
Check output
voltage without
load
Check output voltage before connecting loads to the generator.
WARNING:
The generator must be run at the correct speed in order to produce the
proper electrical voltage and frequency. Failure to do so could result
in damage to equipment powered by the generator and possible injury
to the individual.
1. Allow running generator to warm up for five minutes. Do not connect
any loads.
2. Use portable voltage meter to check output voltage at the generator’s
outlets/receptacles.
3. Measured voltage should be within the following ranges:
a. 108-132 volts at 120V receptacle(s).
b. 216-264 volts at 240V receptacle(s).
If the output voltage is NOT within the specified range:
1) Adjust the engine speed if possible.
2) If that doesn’t work, re-verify that:
a) Your engine’s rated horsepower meets the minimum
requirement,
b) Your sheave ratio is correct, and
c) The belts (or couplings) are not loose (squeaking, visibly
slipping).
3) If you are still not able to achieve acceptable output voltage, there
is a problem with the engine or the generator. Refer to your
engine’s owner’s manual for troubleshooting. If it appears that the
generator itself is the problem, call NorthStar Product Support @
1-800-270-0810 for assistance.