Installation Instructions

BUBBLE MUST REST BETWEEN THE TWO LINES
LOCKING DOWN THE BIO-KINETIC SYSTEM
CHECK FOR PROPER ALIGNMENT
SINGULAIR GREEN
®
BIO-KINETIC
®
INSTALLATION OF THE BIO-KINETIC
®
SYSTEM (Cont.)
must engage the top of the receiving ange.
Continue to lower the system until the discharge ange
fully engages the receiving ange and the top collar of the
Bio-Kinetic system rests on the ledge of the clarication
chamber access opening. To conrm that the discharge
ange and receiving ange are fully engaged, look through
the viewing port in the top collar. Use the locking lug tool
to twist each of the round, black locking lugs clockwise, so
that each locking lug is positioned directly into the molded
locking slots of the mounting riser.
PLACING THE BIO-KINETIC SYSTEM ON LINE
Locate the level indicator mounted above the outlet of
the Bio-Kinetic system ow distribution deck. The bubble
should be resting squarely between the two lines in the
clear plastic case. If the location of the bubble indicates
the system is not installed in a level position, the ow
distribution deck should be leveled using the four
adjustment lugs provided for this purpose. With the ratchet
drive, extension and
7
/
16
" socket from the Tool Kaddy,
turn each of the adjustment lugs the minimum amount
necessary for the bubble to rest squarely between the
two lines in the clear plastic case. Leveling of the ow
distribution deck is essential for proper operation of the
ow equalization ports, chemical feed tubes and e󰀪uent
weir within the Bio-Kinetic system.
The system service cover can now be placed into position.
Install the cover, handle side up, aligning the four holes
in the cover with the four locking lug bolts. Be sure the
optional chlorination and dechlorination feed tube access
openings are in the proper position. The cover will come
to rest on the collar of the Bio-Kinetic system. There is no
need to add fasteners to the locking lug bolts.
If the installation requires a Blue Crystal disinfection
system, the chlorine feed tube opening in the service
cover must be positioned on the inlet side of the system
nearest the aerator mounting riser. Before handling
Blue Crystal disinfecting tablets, carefully read the container
label and the “Warning” section of these instructions. To
ll the chlorine feed tube, remove the cap, hold the tube
(open end down) with one hand and insert Blue Crystal
WASTEWATER TREATMENT SYSTEM