disinfecting tablets, one tablet at time, until the tube is lled.
Each tablet must lie at in the stack. When the feed tube
has been completely lled, replace the cap. Twist the cap
clockwise until it locks securely into position on the chlorine
feed tube. Install the feed tube, slotted end down, through
the plastic collar molded into the top of the Bio-Kinetic
system service cover. The feed tube will begin to engage
the round recess in the ow distribution deck. Rotate the
chlorine feed tube clockwise until it locks into position.
NOTE: The chlorine feed tube must always be installed
through the mounting collar nearest the aerator mounting
riser. If the installation requires disinfection and
dechlorination, there will be two openings in the protective
cover. The dechlorination feed tube must be installed
nearest the system outlet.
WARNING
Blue Crystal disinfecting tablets are a strong oxidizing agent
and highly corrosive. Tablets should be stored in a cool, dry,
well-ventilated area away from combustible materials such
as paper, petroleum products, chemicals, rags or cardboard.
Contact with other liquids or chemicals may cause re.
Improper use of this product may cause personal injury or
property damage. Always wear rubber gloves and either
safety goggles or a face shield when handling Blue Crystal
disinfecting tablets or working with the chlorine feed tube.
Keep tablets out of the reach of children, as they can cause
skin and eye damage, irritate the nose and throat, and may
be fatal if swallowed. If on skin, wash with plenty of soap and
water for fteen minutes, call a doctor if irritation persists. If
swallowed, immediately drink large quantities of water, do
not induce vomiting, avoid alcohol and get medical attention
immediately. If inhaled, immediately remove victim to fresh
air. In the case of re, apply liberal quantities of water. It
INSTALLATION OF THE BIO-KINETIC
®
SYSTEM (Cont.)
BLUE CRYSTAL AND BIO-NEUTRALIZER
FEED TUBE INSTALLATION
is a violation of Federal law to use Blue Crystal tablets in
a manner inconsistent with the instructions printed on the
storage container label.
If the installation requires a Bio-Neutralizer dechlorination
system, the Bio-Kinetic system will be supplied with a
dechlorination feed tube. Before handling Bio-Neutralizer
dechlorination tablets, carefully read the container label
and the “Warning” section of these instructions. To ll
the dechlorination feed tube, remove the cap, hold the
tube (open end down) with one hand and insert the
Bio-Neutralizer dechlorination tablets, one tablet at a time,
until the tube is lled. Each tablet must lie at in the stack.
When the tube has been completely lled, replace the cap.
Twist the cap clockwise until it locks securely into position
on the dechlorination feed tube. Insert the dechlorination
feed tube, slotted end down, into the mounting collar closest
to the system outlet. The bottom of the tube must come to
rest evenly on the oor of the ow deck.
WARNING
Bio-Neutralizer dechlorination tablets must be stored in
a cool, dry place away from acids and oxidizers. Do not
allow Bio-Neutralizer tablets to come into contact with
chlorine tablets. Although not rated a hazardous material
by the USEPA, exercise caution when handling and wash
skin thoroughly with soap and water if contact occurs.
Inspect the Bio-Kinetic system to verify that all four locking
lugs are fully engaged into the molded locking slots in the
riser, the moisture vapor shield is properly installed over
the four locking lug bolts and the feed tubes are properly
installed. Reinstall the Bio-Kinetic system access cover
on the clarier riser. Secure the access cover to the riser
using the fasteners provided. Now proceed with the steps
outlined in the Singulair Green System Final Check and
System Start-Up instructions. DANGER: Make sure the
system access cover is in good condition and securely
installed on the mounting riser. Never allow access
risers to be left uncovered or partially covered. Failure
to secure access covers and safety nets could result
in bodily injury, illness or death. Riser safety nets are
available from Norweco for concrete or plastic risers.
SERVICING THE BIO-KINETIC SYSTEM
Each installation equipped with the Bio-Kinetic system
should be inspected and serviced during each six-month
service inspection. Refer to the Bio-Kinetic System Service
instructions for service and recordkeeping procedures.